We use cookies to make your experience better. To comply with the new e-Privacy directive, we need to ask for your consent to set the cookies. Learn more.
Inor Transmitter’s IPAQ R520X is the intrinsically safe version for use in Ex-Zone 1 and 2 of the IPAQ R520 series of temperature transmitters.
The temperature transmitter is both universal and isolated and compatible with the HART 6 protocol. It is equipped with a dual input with an additional input for voltage and resistance. Its sensor matching function which compensates for deviations in connected sensors and ability to identify sensor drift by checking the reading from both the RTD or thermocouple are just two of the many innovative features of the IPAQ R520X.
Type | Rail-mounted |
Input | RTD; Thermocouple; Universal |
Input RTD | Pt10, Pt50, Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000, Cu10 |
Input Thermocouple | Type B, C, D, E, J, K, N, R, S, T |
Type Of Transmitter | Digital |
Output | 4-20 mA; HART® |
Isolation | Isolated |
Measuring channels | 2 channels |
Sensor connection | 2-, 3-, 4-wire connection |
Power supply | IPAQ R520/R520S: 10 to 36 VDC; IPAQ R520X/R520XS: 10 to 30 VDC |
Approvals | ATEX, IECEx, SIL2 |
Typical accuracy | RTD: Max. of ±0.1 °C or ±0,05 % of span; TC: Typical ±0.05 of span |