DENT Instruments PowerScout PS48HD-P-N-N Power Submeter (Mounting Plate, No Display)

SKU
PS48HD-P-N-N
Manufacturer:
DENT Instruments
DENT Instruments

Key Features:

  • 48 current channels: Multi-circuit submeter monitors voltage, current, power, energy, and many other electrical parameters on any combination of single and/or three-phase systems
  • Two independent voltage inputs allow the PowerScout 48 HD meter to be used on two systems simultaneously
  • Line-Powered: 90-600V Phase-to-Phase power supply
  • Revenue Grade: ANSI C12.20-2010 Class 0.2
  • Available with UL 94-V0 enclosure or as a circuit board mounted on a rugged plate to be mounted in an enclosure of your choice
  • Mounting Plate included on circuit board only version to help facilitate easy, safe installation
  • Extra level of protection: High-Voltage Cover offers additional safety
  • Communications: Utilize either BACnet or Modbus protocol over either Serial or Ethernet
  • Positive and negative Modbus registers/BACnet objects allow for the PowerScout to be used on net metering projects
  • Mix-and-match a full range of Split Core or RoCoil Rogowski-style CTs, including serveral revenue-grade options
  • Optional display shows real-time information about the meter configuration and metered data
  • PhaseChek™ confirms proper CT orientation
  • UL Listed (enclosure version) or UL Recognized (circuit board version)
  • CE Mark
  • 5 year warranty
Product Options:
$2,470.00

Secured and trusted checkout with

DENT Instruments has introduced their new revenue-grade power meter, the PowerScout 48 HD series. Monitoring power, voltage, energy, current and an expanse of other electrical parameters on a single and three-phase system with the PowerScout PS48HD-P-N-N Power Submeter from DENT Instruments. The PS48HD-P-N-N includes the mounting plate but not the display.
Technical
Service TypeSingle Phase, Split Phase, Three Phase-Four Wire (WYE), Three Phase-Three Wire (Delta)
PowerFrom L1 Phase to L2 Phase. 90-600VAC RMS CAT III 50/60Hz, 500mA AC Max
AC Protection0.5A Fuse 200kA interrupt capacity
Power OutUnregulated 12VDC output, 200 mA, self-resetting fuse.
Voltage Channels80-346 Volts AC Line-to-Neutral, 600V Line-to-Line, CAT III. Two voltage reference inputs.
Current Channels48 channels, 0.525 VAC max, 333 mV CTs, 0-4,000+ Amps depending on CT
Maximum Current Input150% of current transducer rating (mV CTs) to maintain accuracy. Measure up to 4000A with RōCoil CTs
Measurement TypeTrue RMS using high-speed digital signal processing (DSP) with continuous sampling
Line Frequency50/60 Hz
Waveform Sampling1.8 kHz
Parameter Update Rate1 second
MeasurementsVolts, Amps, kW, kVAR, kVA, aPF, dPF, kW demand, kVA demand, Import (Received) kWh, Export (Delivered) kWh, Net kWh, Import (Received) kVAh, Export (Delivered) kVAh, Net kVAh, Import (Received) kVARh, Export (Delivered) kVARh, Net kVARh, THD, Theta, Frequency. All parameters for each phase and system total
Accuracy0.2% ANSI C12.20-2010 Class 0.2
ResolutionValues reported in IEEE-754 single precision floating point format (32 bit).
Display4-line display, tri-color backlight (PhaseChek™)
AlarmsVoltage Phase Loss Alarm (SPDT Relay - 30 VDC)
Pulse OutputOpen Collector, 5mA max current, 40V max open voltage
 
Communications
HardwareRS-485, Ethernet, and USB (for configuration only)
Supported ProtocolsModbus (using SunSpec IEEE-754 single precision floating point model), or BACnet
Max Distance1200 meters with Data Range of 100K bits/second or less
Supported BAUD Rates9600, 19200, 38400, 57600, 76800, 115200 baud
Data Bits8
ParityNone, Even, Odd
Stop Bit2, 1
Data FormatsModbus, BACnet MS/TP, Modbus TCP or BACnet IP
 
Mechanical
Wire Connections12-22 AWG
MountingPanel Mount/Enclosure
PCBA Mounting0.5” Standoffs #6 (quantity 6) (user supplied)
High Voltage CoverIP40
Mounting PlateAvailable with Circuit Board Only model
Operating Temperature*-20° to 60°C (-4° to 140°F)
Humidity5% to 95% non-condensing
EnclosureABS Plastic, 94-V0 flammability rating
Enclosure Dimensions(L) 34.3cm x (W) 25.4cm x (H) 7.6cm (13.5” x 10.0” x 3.0”)
PCBA Dimensions(L) 21.6cm x (W) 21.6cm x (H) 6.4cm (8.5” x 8.5” x 2.5”)
 
Certifications
UL RecognizedCircuit board only version
UL ListedIndoor enclosure version
CEEN 61000-6-4: Class A
ANSI C12.20 Class 0.2NIST Traceable Calibration
 
Viewpoint HD Software
Operating SystemWindows® 10, Windows® 8, Windows® 7
CommunicationsEthernet or USB. One free USB port required on PC.
Security2 password levels
Write Your Own Review
Only registered users can write reviews. Please Sign in or create an account
  • • Data Centers
  • • Tenant Submetering
  • • Bi-Directional Metering
  • • Real-Time Power Monitoring in Commercial, Retail, and Industrial environments