We use cookies to make your experience better. To comply with the new e-Privacy directive, we need to ask for your consent to set the cookies. Learn more.
DENT Instruments has introduced their new revenue-grade power meter, the PowerScout 48 HD series. Monitoring power, voltage, energy, current and an expanse of other electrical parameters on a single and three-phase system with the PowerScout PS48HD-C-D-N Power Submeter from DENT Instruments. The PS48HD-C-D-N comes in an enclosure cover and includes the display.
Technical | |
Service Type | Single Phase, Split Phase, Three Phase-Four Wire (WYE), Three Phase-Three Wire (Delta) |
Power | From L1 Phase to L2 Phase. 90-600VAC RMS CAT III 50/60Hz, 500mA AC Max |
AC Protection | 0.5A Fuse 200kA interrupt capacity |
Power Out | Unregulated 12VDC output, 200 mA, self-resetting fuse. |
Voltage Channels | 80-346 Volts AC Line-to-Neutral, 600V Line-to-Line, CAT III. Two voltage reference inputs. |
Current Channels | 48 channels, 0.525 VAC max, 333 mV CTs, 0-4,000+ Amps depending on CT |
Maximum Current Input | 150% of current transducer rating (mV CTs) to maintain accuracy. Measure up to 4000A with RōCoil CTs |
Measurement Type | True RMS using high-speed digital signal processing (DSP) with continuous sampling |
Line Frequency | 50/60 Hz |
Waveform Sampling | 1.8 kHz |
Parameter Update Rate | 1 second |
Measurements | Volts, Amps, kW, kVAR, kVA, aPF, dPF, kW demand, kVA demand, Import (Received) kWh, Export (Delivered) kWh, Net kWh, Import (Received) kVAh, Export (Delivered) kVAh, Net kVAh, Import (Received) kVARh, Export (Delivered) kVARh, Net kVARh, THD, Theta, Frequency. All parameters for each phase and system total |
Accuracy | 0.2% ANSI C12.20-2010 Class 0.2 |
Resolution | Values reported in IEEE-754 single precision floating point format (32 bit). |
Display | 4-line display, tri-color backlight (PhaseChek™) |
Alarms | Voltage Phase Loss Alarm (SPDT Relay - 30 VDC) |
Pulse Output | Open Collector, 5mA max current, 40V max open voltage |
Communications | |
Hardware | RS-485, Ethernet, and USB (for configuration only) |
Supported Protocols | Modbus (using SunSpec IEEE-754 single precision floating point model), or BACnet |
Max Distance | 1200 meters with Data Range of 100K bits/second or less |
Supported BAUD Rates | 9600, 19200, 38400, 57600, 76800, 115200 baud |
Data Bits | 8 |
Parity | None, Even, Odd |
Stop Bit | 2, 1 |
Data Formats | Modbus, BACnet MS/TP, Modbus TCP or BACnet IP |
Mechanical | |
Wire Connections | 12-22 AWG |
Mounting | Panel Mount/Enclosure |
PCBA Mounting | 0.5” Standoffs #6 (quantity 6) (user supplied) |
High Voltage Cover | IP40 |
Mounting Plate | Available with Circuit Board Only model |
Operating Temperature* | -20° to 60°C (-4° to 140°F) |
Humidity | 5% to 95% non-condensing |
Enclosure | ABS Plastic, 94-V0 flammability rating |
Enclosure Dimensions | (L) 34.3cm x (W) 25.4cm x (H) 7.6cm (13.5” x 10.0” x 3.0”) |
PCBA Dimensions | (L) 21.6cm x (W) 21.6cm x (H) 6.4cm (8.5” x 8.5” x 2.5”) |
Certifications | |
UL Recognized | Circuit board only version |
UL Listed | Indoor enclosure version |
CE | EN 61000-6-4: Class A |
ANSI C12.20 Class 0.2 | NIST Traceable Calibration |
Viewpoint HD Software | |
Operating System | Windows® 10, Windows® 8, Windows® 7 |
Communications | Ethernet or USB. One free USB port required on PC. |
Security | 2 password levels |
Write Your Own Review
- • Data Centers
- • Tenant Submetering
- • Bi-Directional Metering
- • Real-Time Power Monitoring in Commercial, Retail, and Industrial environments
Products In This Series
As low as
Now $2,575.00As low as
Now $2,680.00As low as
Now $2,470.00