Vaisala HMD112 Humidity and Temperature Transmitter for Ducts in HVAC and Cleanroom Applications

SKU
HMD112
Manufacturer:
Vaisala
Vaisala

Key Features:

  • Accurate humidity and temperature transmitters for measurements in cleanroom applications
  • Outdoor transmitter with professional-grade radiation shield
  • Proven HUMICAP 180R sensor for superior long-term stability
  • ±2 %RH accuracy
  • 3-point NIST traceable calibration (certificate included)
  • On-site calibration with HM70 Hand-Held Meter or PC connection
  • Current output (4 … 20 mA)
  • Default output parameters are relative humidity and temperature. Dew point temperature, wet bulb temperature, and enthalpy outputs selectable with a PC connection.
Product Options:
$377.00

Secured and trusted checkout with

Vaisala’s HMD112 Humidity and Temperature Transmitter provides reliable, precision humidity and temperature measurements in HVAC and cleanroom applications. The HMD112 boasts an RH accuracy of +/-2%RH and is equipped with the HUMICAP 180R sensor. The long-term stability of the 180R sensor lessens maintenance needs during the transmitter’s lifetime. Even more, the HMD112 can be field calibrated with an HM70 Hand-Held Humidity and Temperature Meter or a PC connection.

Note - Analog outputs are preset at the factory to:
Channel 1: 4 ... 20 mA = 0 ... 100% RH
Channel 2: 4 ... 20 mA = -40 ... +60 °C (-40 ... +140 °F) T

Performance
RELATIVE HUMIDITY
Measurement range0 ... 100 %RH
Accuracy
   Temperature range+10 ... +30 °C (+50 ... +86 °F)
     0 ... 90 %RH±2 %RH
     90 ... 100 %RH±3 %RH
   Temperature range-20 ... +10 °C, +30 ... +60 °C
(-4 ... +50 °F, +86 ... +140 °F)
     0 … 90 %RH±3 %RH
     90 … 100 %RH±4 %RH
   Temperature range-40 ... -20 °C (-40 ... -4 °F)
     0 ... 100%RH±4 %RH
Stability in typical HVAC applications±0.5 %RH/year
Humidity sensorVaisala HUMICAP® 180R
TEMPERATURE
Measurement range-40 ... +60 °C (-40 ... +140 °F)
Accuracy
   At +20 °C (+68 °F)±0.2 °C (±0.36 °F)
Temperature dependence±0.01 °C/°C
Temperature sensorPt1000 RTD Class F0.1 IEC 60751
CALCULATED PARAMETERS
Measurement range for dew
point temperature and wet bulb
temperature


-40 ... +60 °C (-40 ... +140 °F)
Measurement range for
enthalpy

-40 ... 460 kJ/kg (-10 ... +190 BTU/lb)
Accuracy of the calculated parameters should be
calculated at the actual condition based on the RH
and temperature specification.
 
Accuracy at 20°C (68°F) and 80%RH: 
   Dew point±0.7 °C (1.2 °F)
   Wet bulb temperature±0.5 °C (0.9 °F)
   Enthalpy±1.6kJ/kg (0.7 BTU/lb)
Factory calibration uncertainty at 20 °C
(+68 °F)

±1.5%RH/±0.2 °C
 
Operating Environment (All Models)
Operating temperature range-40 ... +60 °C (-40 ... +140 °F)
Operating humidity range0 ... 100 %RH
Maximum wind/flow speed30 m/s
Storage temperature-40 ... +60 °C (-40 ... +140 °F)
Electromagnetic complianceEN61326-1, Industrial Environment
 
Mechanics
Max wire size1.5 mm2 (AWG 16)
Standard housing colorWhite (RAL9003)
Housing materialPC + 10%GF (UL-V0 approved)
 
Inputs and Outputs
Analog output4 ... 20 mA, loop powered
Loop resistance0 ... 600 Ω
Supply voltage20 ... 28VDC at 600 Ω load
10 ... 28VDC at 0 Ω load
Data input for RDP100 RemoteRS485
Panel DisplayVaisala proprietary protocol