We use cookies to make your experience better. To comply with the new e-Privacy directive, we need to ask for your consent to set the cookies. Learn more.
MN01 is the ideal complement for any multimeter to measure AC currents in low-power secondary or industrial applications. If there is a current in the conductor clamped, the Model MN01 is protected against over-voltages during disconnection from the measurement instrument.
ELECTRICAL | |
Range | 150A |
Measurement Range | 2A to 150A |
Accuracy in % | ≤ 2.5% + 0.15A (1Ω load) ≤ 3% + 0.15A (10Ω load) |
Phase Shift | Not specified |
Output Signal | 1mAac/Aac (1000/1) (150mA at 150A) |
Load Impedance | ≤10Ω |
Maximum Currents | 1 < 150A permanent from 48Hz to 500Hz |
Influence of Temperature | ≤ 0.2% per 10K |
Influence of Adjacent Conductor | ≤ 2mA/A at 50Hz |
Influence of Adjacent Conductor Position in Jaws | ≤ 0.1% at 50/60Hz |
Influence of Frequency | ≤ 2% from 65Hz to 500Hz |
Maximum Output Voltage (secondary open) | 30V |
MECHANICAL | |
Operating Temperature | 14° to 122°F (-10° to +50°C) |
Storage Temperature | -40° to 176°F (-40° to 80°C) |
Operating Relative Humidity | 0 to 85% RH decreasing linearly above 35°C |
Operating Altitude | 0 to 2000m |
Casing Protection Rating (leak-proofing) | IP40(2) (EN 60529 Ed. 1995) |
Fall Height | 4.92 ft (1.5m) (IEC 68-2-32) |
Shock Protection | 3.52 oz (100g)/6ms/half-period (IEC 68-2-27) |
Self-extinguishing Capability | casing UL94 V2 |
Vibration Resistance | IEC 68-2-6 |
Dimensions | 4.43 x 1.48 x 1.02" (112.5 x 37.5 x 26mm) |
Weight | approx. 6.35 oz (180g) |
SAFETY | |
Electrical | EN 61010-1, 600V CAT III, Pollution Degree 2 |
Double Insulation | Yes |
CE Mark | Yes |
(1) Conditions of reference: 23°C ± 3°K, 20 to 75% RH, sinusoidal signal with frequency of 48 to 500Hz, distortion factor < 1% with no DC component, external DC magnetic field < 40A/m, no external AC magnetic field, no external conductor with circulating current, conductor centered for measurement, measurement instrument load impedance ≥ 1MΩ (10A calibre) & ≥ 10kΩ (100A calibre).
(2) With clamp closed.
Write Your Own Review
- Measuring in breaker panels
- Industrial loads
- HVAC
- Residential and commercial sites
- Data logging/recording