Monarch DataChart DC-2000 Paperless Recorder - DISCONTINUED

SKU
DC2000
Manufacturer:
Monarch
Monarch

Key Features:

This Product is DISCONTINUED
Please see the Monarch DataChart DC-6000 as a Recommended Replacement

  • 2, 4, 6 or 12 direct universal inputs: DC voltage, current, thermocouples, RTD's or Dry Contact.
  • 15 total channels including virtual/math channels.
  • High speed storage capability: up to 8 samples per second per channel.
  • Compact Flash card data storage (up to 2 GB).
  • 5.6" Brilliant TFT active matrix color display.
  • Intuitive Touchscreen Control with anti-glare coating.
  • Splash resistant front panel
  • Standard DIN enclosure: 144mm x 144mm bezel
  • 3 or 6 Form C relay contact outputs with 3 digital control inputs.
  • Parallel printer output.
  • Serial output options: RS232 or RS485.
  • 10BaseT Ethernet connection.
  • Companion Software for unit configuration, communication, data analysis, print and export to standard spreadsheet/database applications.
Call For Price

Secured and trusted checkout with

The Monarch DataChart DC-2000 Paperless Recorder is equipped with 2, 4, 6 or 12 direct universal isolated inputs that are menu selectable for DC voltage, DC current, thermocouples, RTD's and Dry Contacts. Operation is effortless with the intuitive 5.6” (142mm) active matrix TFT color touchscreen that also features an innovative anti-glare coating for optimum viewing.

The DC-2000 stores data in non-volatile internal RAM and allows for download to removable media automatically on a preset basis or on demand. Standard removable storage is CompactFlash® up to 2 GB. The recorder is perfect for fast changing process signals with its measurement rate of 8 samples per second for 1 channel. Even more, the DC-2000 has a wide variety of communication options: Data can be accessed and downloaded over standard RS232C option. The RS485 MODBUS option enables the DC2000 to be installed into an existing MODBUS network or you can connect up to thirty one recorders in series. The 10BaseT Ethernet port option allows direct connection to LAN’s or WAN’s and the standard TCP/IP protocol allows for data transfer over the internet.

OPERATING

Input Signals 
DC Voltage: Linear, Industrial square root, logarithmic ± 150mV, ± 1.25V, ± 2.5VAccuracy: 0.06%
± 12.5V and ± 25VAccuracy: 0.1%
DC Current: 4-20mA, 0 to 20mA and 10 to 50mA.Accuracy: 0.15% using external 50 ohm  0.1% shunt
Dry ContactOpen = 0, Closed = 1 
External:Signals can be input via serial port (Modbus). 

 

Thermocouple  Resolution: 0.1°C, Cold Junction Reference: 0.5°C  (0 to 50°C) Thermocouple burnout detection.
Thermocouple Info.DataChart® Specifications
Type Accuracy °CAccuracy°FAccuracy
J* 0.1%J -101 to 1200°C ± 1.5°C-150 to 2190°F± 3.0°F
K**0.1% K -101 to 1372°C ± 1.5°C -150 to 2500°F± 3.0°F 
T**0.2%T -101 to 400°C± 1.5°C-150 to 750°F ± 3.0°F
E**0.11%E -101 to 1000°C± 1.5°C-150 to 1832°F± 3.0°F
R0.16%R -50 to 1768°C± 3.0°C-58 to 3200°F± 6.0°F
S0.17% S -50 to 1768°C± -3.0°C-58 to 3200°F± 6.0°F
0.22% B   0 to 1820°C ± 4.0°C 32 to 3300°F± 7.0°F
C0.13%C   0 to 2400°C ± 3.0°C  32 to 4350°F± 6.0°F
N**0.10%N -101 to 1300°C± 1.5°C-150 to 2372°F± 3.0°F
* (± 2.5°C   -210 to -100°C)    **(± 2.5°C    -270 to -100°C)

 

RTD's : Base accuracy 0.2% or 0.5°C (1°F). Resolution 0.1°C  2 or 3 wire connection. Cable compensation to ± 50 Ohm Open and short circuit detection.
10 ohm Cu-70 to 170°C-94 to 338 °F
100 ohm Pt 385-220 to 850°C-364 to 1560 °F
100 ohm Pt 392-180 to 820°C-292 to 1500 °F
200 ohm Pt 385-220 to 400°C-364 to 750 °F
200 ohm Pt 392-180 to 400°C-292 to 750 °F
120 ohm Ni-70 to 300°C-94 to 570 °F
1000 ohm NI-60 to 209°C-76 to 408 °F
(DIN 43760)  
Input Resolution 0.0015% of full scale, 16 bit unless otherwise stated
Input Impedance> 10 Meg on 150mV, 1.25V and 2.5V ranges, >100 K on 12.5, 25 Volt ranges.
Input Channels 2, 4, 6 or 12 direct
Max Input50 Vdc
CMNR >100db, 50/60 Hz
Measurement Rate Measures all direct input channels every 125 milliseconds (each channel 8 times/second independent of no. of channels).
Math Functions +, -, x, /, logarithms, totalization, powers, averages, timers, and custom equations.
EMC Compliance Meets or exceeds the requirements of EMC 89/336/EEC

 

RECORDING

Recording RatesSelectable from 8/sec. to 10 minutes
Data Format Proprietary binary format for data security.
Data Storage Data stored in non-volatile RAM and recorded automatically, or on demand, to on board removable media. Full media format and verify capability.
 Media MeasurementsCapacity
RemovableCompact Flash50 millionUp to 2 GB
Internal 1 Mb RAM (Non-Volatile) or 2 Mb RAM (Non-Volatile)
File TypesData files, Alarm and Event files, Configuration files, Language files.

DISPLAY

  • Display Type Color: LED backlit Active Matrix TFT Liquid Crystal Display (5.6 inch) with touchscreen control.
  • Resolution 320 x 240 pixels.
  • Display Modes Graphics (Trending vertical or horizontal), Bar Graphs (vertical or horizontal), Digital Meters, Alphanumeric Alarm and Event Data or combinations on a split screen. Review trended data. Search by time, date or signal value.
  • Virtual Chart Speed Programmable from 0.5in/hr to 600in/hr or 10mm.hr to 15,000mm/hr. Chart speed is independent of storage rate.
  • Display Windows Time/Date, Graphics (Bars, Large Digital, Trends), Disk Status, Systems Status, Menu Button Bar, Unit Indentification,Alarms/Events.

 FEATURES

  • Touch Screen   Touch sensitive screen with Button Bar for simple programming and easy operation.
  • Math Package  Algebraic equations (basic math, powers, roots, natural and base 10 logarithms, exponentiation), peak monitoring, differentials, true rolling averages, time averages, gated timing, conditionals (Boolean logic), totalization, logarithmic scaling. 12 Programmable constants.
  • Buffer   Internal 128k buffer (RAM) enables real time browsing of historic chart data independent of recorded data. Equivalent browse capability is approximately 560 pen inches. This represents about 5½ days for 4 pens at 1 inch/hour.
  • File Browse   Any data file on disk can be browsed. File directory allows selection of different file names.
  • Disk Full Alarm   User can set disk full threshold. Disk errors and alarms can be routed to contact closure.
  • Trend direction   User selectable Horizontal or Vertical chart trending. "Pen" pointers for easy trace identification.

 POWER

  • Power Requirements 100 to 240Vac, 50/60Hz or 125 to 300Vdc, 35VA max. Optional 24Vdc +/-15%.
  • Power Fail Protection Programmed parameters stored in non-volatile memory. Clock battery backed. Data retention time without power >12 months.Chart and alarm browse buffers stored in non-volatile memory.
  • Safety CE low voltage directive 89/336/EEC. Complies with EN 61010-1.

 ENVIRONMENTAL

  • Temperature  -10°C to 50°C per UL3111-1/IEC1010-1
  • Humidity 10% to 80% RH per UL3111-1/IEC1010-1.
  • Wash Down IP65 Front panel only.

 OPTIONS

  • • Alarm Contacts 3 or 6 isolated Form C, 3 amp @ 250Vac or 26 Vdc.
  • Remote Inputs 3 isolated inputs, user selectable as dry contact or 5 to 12 Vdc (mech. relay), 12 to 24 Vdc (SS relay) activated.. Inputs share a common. Configurable for chart control, alarm acknowledge/reset, event markers, totalizer reset or logic input.
  • Communications ESD protected RS232 with full hand shaking. Supports modem or isolated RS485 port. Protocol: MODBUS RTU, MODBUS ASCII or serial printer port. Ethernet: 10BaseT. Unit may be remotely configured.
  • Printer Port Parallel printer port (25 pin D shell connector).
Write Your Own Review