Monarch DataChart DC-6000 Advanced Paperless Recording System - DISCONTINUED

SKU
DC6000
Manufacturer:
Monarch
Monarch

Key Features:

This Product is DISCONTINUED
Please Consider the Sixth Sense PG10, PG20, or PG30

  • 6 or 12 universal inputs
  • Up to 4 pulse/frequency inputs
  • 6 or 12 relay outputs
  • Net-workable using standard Ethernet port
  • 21 CFR part 11 compliant (Available option)
  • IP65 rated front panel.
  • 24 Volt DC transmitter power supply
  • On Board Media Drives:  Compact Flash, USB memory stick or external drive, Smart Digital (SD)
  • Touch Screen Control
  • Direct on screen chart annotation with integral stylus
  • Built in OPC and web server.
  • Built in Email Client
  • Shallow installation depth (6.5")
Call For Price

Secured and trusted checkout with

Monarch’s DataChart DC-6000 Advanced Paperless Recording System fuses the newest in measurement, communication, interface and processing technologies to provide superior performance for data acquisition applications.

The DC6000 boasts a high contrast 5.6 inch color Active Matrix TFT LCD display with a rugged touch screen. The front panel is fully compliant to IP65 for use in dusty or wet areas. An instinctive icon driven menu system guides the user through effortless setup and control screens. The Display builder feature simplifies setting up custom screens. Users have the ability to design up to 50 custom displays encompassing numerous combinations of indicator types such as horizontal and vertical bar graphs, large and small digital indicators and horizontal or vertical trends.

Input Resolution: 0.0015% of full scale, 16 bit unless otherwise stated
Input Impedance: >1 Mohm
Input Channels: 6 or 12 direct input plus 6 additional calculated channels
Maximum Input: 50Vdc
Isolation: Channel to Channel: 350Vdc or RMS AC
                Channel to Chassis: 2000 Vdc or RMS AC
                Isolation category II: Pollution Degree 2
Measurement Rate: 10 times per second on all direct input channels
Common Mode Noise Rejection: >100dB, 50/60 Hz, filter enabled
Normal Mode Noise Rejection: >50dB at 50/60 Hz, filter enabled
Math Functions: Fully programmable +, -, x, /, square root, sine, cosine, tangent, log, totalization, powers, averages, conditional logic; AND, NOT, OR, +, >, <, gated timers. Can use live channels in calculation. Can define 6 constants and 6 functions per channel.

Analog Inputs
DC Voltage: +/-125mV, +/-250mV, +/-500mV, +/-1.00V, +/-3.0V, +/-6.0V, +/-12.0V, +/-24.0V
Accuracy: Ranges to 1V +/-0.06%, Ranges > 1V +/-0.1%
DC Current:  4-20mA, 0-20mA, 10-50mA
Accuracy: +/-0.15% using external 50 ohm 0.1% 1/4 watt shunt

Thermocouple (Per ITS90)
Resolution: 0.1C, thermocouple burnout detection: Automatic
Reference junction compensation accuracy: +/-0.5 °C (0 °C to 50 °C)

Type       Range (°C) Accuracy (°C)    Range (°F) Accuracy (°F)
J              -210 to 0°C +/-1.6 °C              -346 to 32°F +/-3.0 °F
                -0 to 1200 °C +/- 0.7 °C          32 to 2192 °F +/- 1.2 °F
K             -270 to -162 °C +/- 5.0 °C       -454 to -260 °F +/- 9.0 °F
                -162 to -70 °C +/- 2.2 °C         -260 to -94 °F +/- 4.0 °F
                -70 to 1372 °C +/- 0.7 °C         -94 to 2500 °F +/- 1.2 °F
T              -270 to -73 °C +/- 2.5 °C        -454 to -100 °F +/- 4.5 °F
                -73 to 200 °C +/- 1.0 °C          -100 to 400 °F +/- 1.8 °F
E              -270 to -70 °C +/- 2.5 °C        -454 to -94 °F +/- 4.5 °F
                -70 to 1000 °C +/- 0.7 °C        -94 to 1832 °F +/- 1.3 °F
N             -270 to 100 °C +/- 3.0 °C       -454 to 212 °F +/- 5.4 °F
                100 to 1300 °C +/- 0.9 °C        212 to 2372 °F +/- 1.6 °F
S              -50 to 0 °C +/- 2.8 °C              -58 to 32 °F +/- 5.0 °F
                 0 to 1000 °C +/-1.4 °C            32 to 1832 °F  +/- 2.5 °F
                 1000 to 1710 °C +/- 1.1 °C     1832 to 3110 °F +/- 2.0 °F
                 1710 to 1768 °C +/- 1.4 °C     3110 to 3214 °F +/- 2.5 °F
B              0 to 535 °C +/- 4.0 °C             32 to 1000 °F +/- 7.2 °F
                 535 to 1800 °C +/- 2.1 °C       1000 to 3300 °F +/- 3.8 °F
U              0 to 100 °C +/- 0.9 °C              32 to 212 °F +/- 1.6 °F
R              0 to 260 °C +/- 3.0 °C              32 to 500 °F +/- 5.4 °F    
                 260 to 650 °C +/- 1.4 °C          500 to 1200 °F +/- 2.5 °F
                 650 to 1760 °C +/- 1.0 °C        1200 to 3200 °F +/- 1.9 °F
C              0 to 180 °C +/- 2.5 °C               32 to 360 °F +/- 2.5 °F
                 180 to 1200 °C +/- 0.8 °C         360 to 2220 °F +/- 1.5 °F
                 1200 to 2315 °C +/- 3.6 °C       2220 to 4199 °F +/- 6.5 °F
L               -200 to 0 °C +/- 1.1 °C              -328 to 32 °F +/- 2.0 °F
                 0 to 890 °C +/- 0.7 °C                32 to 1650 °F +/- 1.2 °F  

Note: Field calibration improves accuracy to better than +/- 2 °F and up to 
+/- 0.5°F and ensures compliance with AMS2750D measurement accuracy
requirements for Nadcap accredited suppliers.                   

RTD
Base Accuracy: 0.2% or 0.5 °C (1 °F). Resolution: 0.1 °C
2 or 3 wire connection. Cable compensation to +50 ohm. Open and short circuit detection.


Type                               Range °C                        Range °F
100 ohm Plt. 385            -220 to 850 °C                -364 to 1560 °F
100 ohm Plt. 392            -180 to 820 °C                -292 to 1500 °F
200 ohm Plt. 385            -220 to 400 °C                -364 to 750 °F
200 ohm Plt. 392            -180 to 400 °C                -292 to 750 °F
1000 ohm Plt. 385          -200 to 200 °C                -328 to 392 °F
500 ohm Plt. 385            -220 to 850 °C                -364 to 1562 °F
50 ohm Plt. 385              -200 to 850 °C                -328 to 1562 °F
50 ohm Plt. 392              -200 to 1100 °C              -436 to 2012 °F

100 ohm Ni.                    -70 to 300 °C                  -94 to 570 °F
120 ohm Ni.                    -70 to 300 °C                  -94 to 570 °F
1000 ohm Ni.                  -60 to 209 °C                  -76 to 408 °F
10 ohm Cu.                     -70 to 170 °C                  -94 to 338 °F*
50 ohm Cu.426               -50 to 200 °C                  -58 to 392 °F
50 ohm Cu. 428              -200 to 200 °C                -328 to 392 °F
100 ohm Cu. 426            -50 to 200 °C                  -58 to 392 °F
100 ohm Cu. 428            -200 to 200 °C                -328 to 392 °F
100 JIS                           -200 to 649 °C                -328 to 1200 °F
*0.5% +/- 0.5 °C


Frequency inputs (2 or 4 channels)
Range: 0 to 5,000Hz all channels, 0 to 10,000Hz 1 channel (on channels 1, 6, 7 and 12 only)
Accuracy: 0.005% +/- 1 digit

Recording
Recording Rates: User programmable from 10 samples per second to 1 sample every 24 hours
Data Format: Proprietary encrypted format, User file naming
Data Storage Capacity: Data stored in non-volatile RAM and recorded automatically to:
                Removable media types:
                        CompactFlash™ or USB drive to 16 GB
                Internal media type:
                        SD card (secure digital) to 16 GB
File Types: Data files, alarm and event files, configuration files, language files, multiple files of different names on a single disk.

Display
Type: Color LED back-lit Active Matrix TFT Liquid Crystal Display
Size: 5.6 inch diagonal, Resolution: 320 (W) x 240 (H) pixels
Interface: Resistive analog touch screen control
Display Builder: Allows user to create custom displays
Display Modes: Graphic trending (vertical or horizontal), Bar Graphs (vertical or horizontal), Digital Meter (large or small), Alphanumeric Alarm and Event log
Virtual Chart Speed: Programmable from 0.5 inch/hour to 600 inches/hour (10 mm/hr to 10,000 mm/hr)
Display Windows: Time/Date, Graphics (bars, large digital, trends) Disk Status, System Status, Menu Button Bar, Unit Identification, Alarms/Events

Communications
Network: 10/100 Base T Ethernet per 802.3, RJ45 connection standard
Servers: Web server supports http and ftp protocols, OPC server, Modbus over Ethernet server
Serial: Isolated RS485/RS232 Modbus Interface (option)

Power
Requirements: 100 to 240 Vac, 50/60Hz. 35 VA max. Optional 24 Vdc +/-15%
Power Fail Protection: Programmed parameters stored in non-volatile memory. Clock battery backed. Internal battery backup provides orderly shutdown and the ability to survive brownouts and short blackouts (<20 seconds)
Power Output: Optional isolated 24Vdc @ 100mA output

Input/Output
Digital I/O: 6 or 12 relay outputs, Form A (normally open SPST contacts) rated at 200 Vdc @ 0.5A Max, 2 digital control inputs +5 to +12Vdc @ 20mA (optional), Control inputs may be used for record start/stop, alarm acknowledge and channel reset functions

Safety and Environmental
Operating Range: 0 °C to 50 °C, 10% to 80% RH non-condensing
Protection: IP65 when mounted in panel
Safety: Meets the requirements of EN61010-1 when installed in accordance with the instructions in the manual.
EMC: Meets the requirements of EN61326:2003 and CE directive 89/336/EEC.

Weight: Approximately 7 lbs. (3.17 kg) - weight will vary depending on options installed

Write Your Own Review
Only registered users can write reviews. Please Sign in or create an account