We use cookies to make your experience better. To comply with the new e-Privacy directive, we need to ask for your consent to set the cookies. Learn more.
Dranetz Power Xplorer PX5 include capture of low-medium-high freq. transients through peak,waveshape,rms duration and adaptive high-speed sampling,as well as power measurements to clearly characterize voltage harmonics,non-sinusoidal & unbalanced systems. The Power Xplorer integrates the most advanced feature set available in a power monitoring instrument, with an easy-to-navigate, color graphical user interface. With high-speed sampling and data capture (1 microsecond/channel), this 8-channel workhorse simultaneously captures and characterizes thousands of parameters, using a range of standard and customizable operating modes. The unique measurement capabilities of the Power Xplorer include capture of low-medium-high frequency transients through peak, waveshape, rms duration and adaptive high-speed sampling, as well as power measurements to clearly characterize voltage harmonics, non-sinusoidal and unbalanced systems.
Measured Parameters
- • (4) differential inputs, 1-600 Vrms, AC/DC, 0.1% rdg + 0.05% FS, 256 samples/cycle, 16 bit ADC
- • (4) inputs with CTs 0.1-6000 Arms CT-dependent, AC/DC, 0.1%rdg + CTs, 256 samples/cycle, 16 bit ADC
- • 1 MHz High Speed Sampling, 14 bit ADC, 1% FS
- • Frequency Range, 10m Hz resolution, 15-20 Hz, 45-65 Hz, or 350-450 Hz
- • Phase Lock Loop - Generator tracking
- • Phase Lock Loop - Standard PQ mode
Monitoring/Compliance
- • IEEE 1159
- • IEC 61000-4-30 Class A
- • EN50160 Quality of Supply
- • Current Inrush / Energization
- • Voltage Fault recording
- • Long Term Monitoring
- • Continuous Data Logging w/min/max/avg
Power Quality Triggers
- • Cycle-by-cycle analysis
- • 256 samples/cycle; 1/2 cycle RMS steps (1)
- • L-L, L-N, N-G RMS Variations: Sags/swells/interruptions)
- • RMS Recordings V&I (32 pre-fault, 10K post-fault cycles)
- • Waveshape Recordings (2/6/2 cycles)
- • Low and Medium Frequent Transients - V&I
- • High Frequency Transients - V&I, 3% FS trigger (1)
- • Harmonics Summary Parameters
- • Cross trigger V & I channels
- • RMS Event Characterization (IEEE or IEC)
- • Transient Event Characterization (1)
Distortion/Power/Energy
- • W, VA, VAR, TPF, DPF, Demand, Energy, etc.
- • IEEE 1459 Parameters of distorted and unbalanced
- • Harmonics/Interharmonics per IEC 1000-4-7
- • THD/Harmonic Spectrum (V,I,W) to 63rd
- • TID /Interharmonic Spectrum (V,I) to 63rd
- • Flicker per IEC 1000-4-15 (Pst,Plt,Sliding Plt)
- • Crest Factor, K Factor, Transformer Derating Factor, Telephone Interference Factor
- • Unbalance (max. rms deviation) & sequencing components
- • 5 User Spec Harmonics or Signaling Frequency
- • Vector/Arithmetic/Coincident Parameters
Available Languages
-
• English, French, Italian, German, Spanish, Swedish
General Specifications
- • Size (HxWxD): 12" x 2.5" x 8" (30cm x 6.4cm x 20.3 cm)
- • Weight: 4.2 pounds (1.9 kg)
- • Operating Temperature: 0 -50 (32 to 122 )
- • Storage Temperature: -20 to 55 (4 to 131 F)
- • Humidity: 10 to 90% non-condensing
- • System Time Clock-Crystal controlled-1 second resolution
- • Charger /Battery Eliminator: 90-264 VAC 47-63 Hz
- • Display: LCD color touch screen
- • Memory options (must have one): 256M removable compact flashcard
- Fast Transient Capture
- Power Quality Surveys and Diagnostics
- Capacitor Switching Events
- Load Distortion and Imbalance
- Flicker
- Compliance Monitoring
- Harmonics