We use cookies to make your experience better. To comply with the new e-Privacy directive, we need to ask for your consent to set the cookies. Learn more.
DENT Instruments’ CT-SCM-0200 Standard Medium Split Core Current Transformer is tactfully configured for 200 Amp loads and crafted with a 1.25” window size. The CT can be installed over already present electrical power lines, making installation easier and worry free by eliminating the stress of possible service disruption or line disconnection.
The CT-SCM-0200 produces 333mV at full scale and provides linear output voltage directly relational to the input current. Even more, the CT is shunted for safety, compared to other commercially available CTs.
The CT-SCM-0200 is compatible with both the ELITEpro and PowerScout series from DENT Instruments.
Window Size | 1.25” (3.20 cm) |
Current Range | 4 - 260A AC |
Output | 333 mV at rated current |
Ratio Error | <1% at rated current (typical) |
Phase Error | <2° at rated current (typical) |
ELECTRICAL | |
Output | 333 mV at rated current |
Wire Polarity | White = Hi, positive (+) Black = Low, negative (‐) |
Frequency Range | 50 to 400 Hz |
MECHANICAL | |
Case Material | Epoxy encapsulated housing |
Leads | 2.7 M (8’), twisted pair, 20 AWG |
Operating Temperature | –20° to 55°C (-4° to 131°F) |
SAFETY | |
Working Voltage | 600 VAC Category III |
Dielectric Strength | 5000 VAC around case 600V rated leads |
Safety Standards | Conforms to: UL STD 61010-1 EN 60044-1 Certified to: CAN/CSA STD C22.2 No. 61010-1 |