Vaisala HMD62 2-Wire Humidity and Temperature Transmitter for Duct Mounting

SKU
HMD62
Manufacturer:
Vaisala
Vaisala

Key Features:

  • Measurement accuracy up to ±1.5 %RH and ±0.1 °C (±0.18 °F)
  • Analog output transmitter model options: HMD62 (RH and T) and TMD62 (T-only)
  • All common humidity parameters available, including RH, dew point, enthalpy, and wet bulb temperature
  • 4 … 20 mA analog output
  • Resistant to chemicals and dust
  • IP66-rated body
  • Traceable calibration certificate
  • Easy field adjustment and output configuration with quick access to transmitter electronics also when installed
  • Compatible with Vaisala Insight PC software
Product Options:
$572.00

Secured and trusted checkout with

The Vaisala HMD62 is designed for light industrial applications and demanding HVAC applications such as museums, cleanrooms, and laboratories. The HMD62 transmitter uses floating 4 … 20 mA loop powered output. The HMD62 replaces the popular HMD60U and HMD60Y transmitters.

Relative Humidity Measurement Performance

Humidity sensorVaisala HUMICAP R2
Measurement range0 ... 100 %RH
Stability±2.5 %RH over 2 years
Accuracy at 0 … +40 °C (+32 … +104 °F) (Incl. Non-Linearity, Hysteresis and Repeatability)
0...90%RH±1.5%RH
90...100%RH±2.5%RH
Accuracy at +40 … +80 °C (+104 … +176 °F) and -40 ... 0 °C (-40 ... +32 °F)
(Incl. Non-Linearity, Hysteresis and Repeatability)
0 … 90 %RH±2.5%RH
90 … 100 %RH±3.5%RH
Factory calibration uncertainty±1.0 %RH
Start-up and Response Time
Start-up time at +20 °C (+68 °F)8 s
Response time (T63) at +20 °C (+68 °F)15 s
Calculated Humidity Parameters (Default Analog Output Scale)
Dew point-40 ... +80 °C (-40 ... +176 °F)
Dew point / frost point-40 ... +80 °C (-40 ... +176 °F)
Absolute humidity0 … 300 g/m3 (0 … 131.1 gr/ft3)
Wet bulb temperature-40 ... +80 °C (-40 ... +176 °F)
Enthalpy-40 … 1600 kJ/kg (-9.5 ... 695.6 Btu/lb)
Mixing ratio0 … 600 g/kg (0 … 4200 gr/lb)

 

Temperature Measurement Performance

Measurement range-40 ... +80 °C (-40 ... +176 °F)
Default analog output scale-20 … +80 °C (-4 … +176 °F)
Accuracy at +20 °C (+68 °F)±0.1 °C (0.18 °F)
Temperature dependence±0.005°C/°C
Factory calibration uncertainty±0.1 °C (0.18 °F)
Response time (T63) with free convection8 min

 

Operating Environment

Operating temperature, electronics-40 ... +60 °C (-40 ... +140 °F)
Operating temperature, probe-40 ... +80 °C (-40 ... +176 °F)
Storage temperature range-40 ... +80 °C (-40 ... +176 °F)
Maximum flow speed50 m/s with sintered filter
Electromagnetic compatibilityEN61326-1, Industrial Environment

 

Mechanical Specification

Housing materialCast aluminium
Probe materialStainless steel
IP ratingIP66 (NEMA 4X)
Weight511 g (18 oz)

 

Inputs and Outputs

Power supply input10 ... 35 VDC (RL = 0 Ω)
20 ... 35 VDC (RL = 600 Ω)
Analog outputs• TMD62: 1 x T output 4 ... 20 mA
• HMD62: 1 x RH output 4 … 20 mA,
1 x T output 4 ... 20 mA
• Calculated output parameters
for HMD62 include Td, Tdf, A, X,
Tw, and H.
Service portM8 4-pin male connector:
• MI70 hand-held indicator (requires
cable 219980SP)
• Vaisala Insight PC software 1)
(requires USB cable 219690)
Screw terminal wire size0.5 ... 2.5 mm2
1) Vaisala Insight software for Windows available at www.vaisala.com/insight.
Write Your Own Review
Only registered users can write reviews. Please Sign in or create an account

Products In This Series

As low as

Now $442.00