We use cookies to make your experience better. To comply with the new e-Privacy directive, we need to ask for your consent to set the cookies. Learn more.
The UEI DL419 1000A AC/DC True RMS Clamp Meter features LRA Inrush current measurement, Data hold, Min/Max, Relative/DC A Zero mode, High contrast backlit display, Auto/ Manual ranging, Magnetic mount, Bargraph, Auto power off, and a 2-Year limited warranty.
AC Volts Measurement
Range | Resolution | Accuracy | Overload Protection |
400mV | 0.1mV |
± (2.0% + 5 digits) |
1000V RMS |
4V | 1mV | ||
40V | 10mV | ||
400V | 100mV | ||
1000V | 1V |
True RMS: 45Hz to 400Hz
DC Volts Measurement
Range | Resolution | Accuracy | Overload Protection |
400mV | 0.1mV |
|
1000V |
4V | 1mV | ||
40V | 10mV | ||
400V | 100mV | ||
1000V | 1V | ± (0.8% + 10 digits) |
True RMS: 45Hz to 400Hz
Resistance: < 40MΩ
Range | Resolution | Accuracy | Overload Protection |
400Ω | 0.1Ω |
± (1.0% + 4 digits) |
600V RMS |
4kΩ | 1Ω | ||
40kΩ | 10Ω | ||
400kΩ | 100Ω | ||
4MΩ | 1kΩ | ||
40MΩ | 10kΩ | ± (2.0% + 4 digits) |
Capacitance (MFD)
Range | Resolution | Accuracy | Overload Protection |
40.00nF | 0.01nF |
± (3.5% + 6 digits) |
600V RMS |
400.0nF | 0.1nF | ||
4.000uF | 0.001μF | ||
40.00uF | 0.01μF | ||
400.0uF | 0.1μF | ||
2000uF | 1μF |
Continuity
Overload Protection | Open Circuit Voltage |
600V RMS | < 0.44V |
Threshold Approx : < 40Ω
DC Low Amps Measurement -Test lead input
Range | Resolution | Accuracy | Overload Protection |
400μA | 0.1μA | ± (1.2% + 3 digits) | 2000μA / 600V RMS |
2000μA | 1μA |
True RMS: 45Hz to 400Hz (Crest factor < 3 : 1 )
AC Low Amps Measurement -Test lead input
Range | Resolution | Accuracy | Overload Protection |
400μA | 0.1μA | ± (2.0% + 5 digits) | 2000μA / 600V RMS |
2000μA | 1μA | ± (1.5% + 5 digits) |
True RMS: 45Hz to 400Hz (Crest factor < 3 : 1 )
Diode Test
Overload Protection | Range | Test Current | Open Circuit Voltage |
600V RMS | 2.0V | Appx. 0.25mA | < 1.6V DC |
DC Amps Measurement
Range | Resolution | Accuracy | Overload Protection |
40A | 0.01A | ± (2.5% + 15 digits) |
1000V RMS |
400A | 0.1A | ± (1.5% + 8 digits | |
1000A | 1A | ± (1.5% + 8 digits) |
True RMS: 45Hz to 400Hz
AC Amps Measurement
Range | Resolution | Accuracy | Overload Protection |
40A | 0.01A | ± (2.9% + 15 digits) |
1000V RMS |
400A | 0.1A | ± (1.9% + 8 digits) | |
1000A | 1A | ± (1.9% + 8 digits) |
True RMS: 45Hz to 400Hz
Write Your Own Review
- Measure linear electrical loads
- Control voltage or system board voltage checks
- Circuit continuity or specified resistance
- Motor run or start faults
- Quick check of live wires
- Diode test malfunctions/ unbroken paths
- Motor inrush