Simpson Gima G300 Digital Power Meter - DISCONTINUED

SKU
G300
Manufacturer:
Simpson
Simpson

Key Features:

This Product is DISCONTINUED

  • Measure phase amps, phase volts, line volts, per phase PK, per phase kW, 3 phase Pf, 3 phase kW, frequency, current demand, voltage demand, peak current demand, peak voltage demand, kWh, per phase kvar, 3 phase kvar, capacitive kvarh, inductive kvarh, total kvarh and kW demand
  • Software detection and correction of wiring mistakes makes installation easy
  • 1/4 DIN (96 x 96 mm bezel, 92 x 92 mm cutout) needs just 2.8” (71 mm) behind the panel
  • Expansive backlit LCD display for better viewing
  • 4 keys select all parameters
Call For Price

Secured and trusted checkout with

Equipped with all the features and functions of the G200, Simpson’s Gima G300 Digital Power Meter also preforms per phase kvar, 3 phase kvar, capacitive kvarh, inductive kvarh, total kvarh and kW demand measurements.


 Click here to see Simpson’s Gima G200 Digital Power Meter. 


*Note: A three-phase terminal style current transformer must be used with the G300 Digital Power Meter.


*Note: For models with Modbus Communication options please call for assistance.

 

 

Input

System

3-phase, 3 or 4 wire unbalanced load

Voltages

120/208, 120/240, 277/480, 63/110

Measurement Range

20% to 120%

Current

5 amp from external CTs Fully Isolated

Measurement Range

5% to 120%

Operating Frequency

45 to 65 Hz

Harmonics

Up to the 30th harmonic

Input Loading

Voltage

Less than 0.1VA per phase

Current

Less than 0.1VA per phase

Overload

Voltage

x2 for 2 seconds max

Current

x40 for .5 second max

Auxiliary Supply

Standard

115V±15% 45-65Hz

Optional

230V±15% 45-65Hz

Display

Custom backlit supertwist LCD 3 lines of .47”

General

(12mm) digits plus .15” (3.8mm) legends

Update Rate

Once/Second

Environmental

Temperature

14°F to 149°F (-10°C to 65°C) operating

Humidity

<75% RH non-condensing

Programming

CT Primary

5amp to 6500 amp

VT Primary

60v to 50,000v

Pulse Outputs

2

Function

Output No.1

Wh 

Output No. 2

Total varh 

Pulse Length

100ms to 20 seconds

Isolation

2.2KV (50V Output No. 1 to Output No. 2)

Scaling

Settable 1, 10 or 100 pulse output rate

Mechanical

Bezel

3.79” x 3.79” (w/ .29” lip)

Depth

3.35”

Panel Cutout

3.62” x 3.62”

Weight

14 oz.

 

 

Accuracy

Parameter

Spec Range

Spec

Phase Current

5% to 120% lb

±0.2% lb (1% *Rdg) ±1 Digit

Neutral Current

5% to 120% lb

±0.6% lb (2% *Rdg) ±1 Digit

Phase Voltage

20% to 120% Vb

±0.2% Vb (1% *Rdg) ±1 Digit

Voltage LL

20% to 120% Vb

±0.3% Vb (1% *Rdg) ±1 Digit

Phase Watts

5% to 120% FS

±0.4% FS (1% *Rdg) ±1 Digit

Phase VA

5% to 120% FS

±0.6% FS (1.5% *Rdg) ±1 Digit

Phase var

5% to 120% FS

±0.8% FS (2% *Rdg) ±1 Digit

Phase PF

 

Rdg) ±1 Digit Phase PF ±

System Watts

5% to 120% FS

±0.6% FS (1% *Rdg) ±1 Digit

System VA

5% to 120% FS

±1% FS (1.5% *Rdg) ±1 Digit

System var

5% to 120% FS

±1.5% FS (2% *Rdg) ±1 Digit

System PF

 

±0.2 Degrees

Frequency

45Hz to 65Hz

±.05 Hz

 

Note: *Rdg = Reading

Write Your Own Review
Only registered users can write reviews. Please Sign in or create an account