We use cookies to make your experience better. To comply with the new e-Privacy directive, we need to ask for your consent to set the cookies. Learn more.
Meet all measurement and metering demands with Simpson’s Gima G100 Digital Power Meter. As part of the Gima series, the G100 delivers continuous, rapid precision measurements, regardless of harmonics and waverform disruptions. More still, users can employ the instrument as a single-phase meter or three-phase meter.
The meter suits a variety of applications with its capacity for measuring parameters like, phase amps, phase volts, line volts, per phase PK, per phase kW, 3 phase Pf, 3 phase kW, frequency, current demand, voltage demand, peak current demand and peak voltage demand.
*Note: A three-phase terminal style current transformer must be used with the G100 Digital Power Meter.
*Note: For models with Modbus Communication options please call for assistance.
Input | |
System | 3-phase, 3 or 4 wire unbalanced load |
Voltages | 120/208, 120/240, 277/480, 63/110 |
Measurement Range | 20% to 120% |
Current | 5 amp from external CTs Fully Isolated |
Measurement Range | 5% to 120% |
Operating Frequency | 45 to 65 Hz |
Harmonics | Up to the 30th harmonic |
Input Loading | |
Voltage | Less than 0.1VA per phase |
Current | Less than 0.1VA per phase |
Overload | |
Voltage | x2 for 2 seconds max |
Current | x40 for .5 second max |
Auxiliary Supply | |
Standard | 115V±15% 45-65Hz |
Optional | 230V±15% 45-65Hz |
Display | Custom backlit supertwist LCD 3 lines of .47” |
General | (12mm) digits plus .15” (3.8mm) legends |
Update Rate | Once/Second |
Environmental | |
Temperature | 14°F to 149°F (-10°C to 65°C) operating |
Humidity | <75% RH non-condensing |
Programming | |
CT Primary | 5amp to 6500 amp |
VT Primary | 60v to 50,000v |
Pulse Outputs | 2 |
Function | |
Pulse Length | 100ms to 20 seconds |
Isolation | 2.2KV (50V Output No. 1 to Output No. 2) |
Scaling | Settable 1, 10 or 100 pulse output rate |
Mechanical | |
Bezel | 3.79” x 3.79” (w/ .29” lip) |
Depth | 3.35” |
Panel Cutout | 3.62” x 3.62” |
Weight | 14 oz. |
Accuracy | ||
Parameter | Spec Range | Spec |
Phase Current | 5% to 120% lb | ±0.2% lb (1% *Rdg) ±1 Digit |
Neutral Current | 5% to 120% lb | ±0.6% lb (2% *Rdg) ±1 Digit |
Phase Voltage | 20% to 120% Vb | ±0.2% Vb (1% *Rdg) ±1 Digit |
Voltage LL | 20% to 120% Vb | ±0.3% Vb (1% *Rdg) ±1 Digit |
Phase Watts | 5% to 120% FS | ±0.4% FS (1% *Rdg) ±1 Digit |
Phase VA | 5% to 120% FS | ±0.6% FS (1.5% *Rdg) ±1 Digit |
Phase var | 5% to 120% FS | ±0.8% FS (2% *Rdg) ±1 Digit |
Phase PF |
| Rdg) ±1 Digit Phase PF ± |
System Watts | 5% to 120% FS | ±0.6% FS (1% *Rdg) ±1 Digit |
System VA | 5% to 120% FS | ±1% FS (1.5% *Rdg) ±1 Digit |
System var | 5% to 120% FS | ±1.5% FS (2% *Rdg) ±1 Digit |
System PF |
| ±0.2 Degrees |
Frequency | 45Hz to 65Hz | ±.05 Hz |
Note: *Rdg = Reading