Simpson Amik 300 LCD Touchscreen Digital Power Meter

SKU
A300
Manufacturer:
Simpson
Simpson

Key Features:

  • True RMS measurement
  • Onsite programmable
  • Low back depth
  • Phase reversal indication
  • Graphical LCD touch screen
Product Options:
$552.50

Secured and trusted checkout with

The Simpson Amik 300 (A300) is a compact multifunction meter with a graphical LCD touch screen display. The A300 is capable of measuring electric parameters like AC current, voltage, frequency, active energy import and active energy export, current demand, kW demand, kVA demand, and max current demand, max kW demand and max kVA demand.
Reference conditions for Accuracy
Reference temperature23°C +/- 2°C
Input waveformSinusoidal (distortion factor 0.005)
Input frequency50 or 60 Hz ±2%
Auxiliary supply voltageRated Value ±1%
Auxiliary supply frequencyRated Value ±1%
Voltage Range50... 100% of Nominal Value.
60... 100% of Nominal Value for THD
Current Range10... 100% of Nominal Value.
20... 100% of Nominal Value for THD
PowerCos phi / sin phi = 1 for Active / Reactive Power & Energy
10... 100% of Nominal Current & 50... 100% of Nominal Voltage
Power Factor / Phase Angle40... 100% of Nominal Current &
50... 100% of Nominal Voltage

 

Accuracy
Voltage±0.5% of range
Current±0.5% of range
Frequency±0.15% of mid frequency
Active Power±0.5% of range
Re-Active Power±0.5% of range
Apparent Power±0.5% of range
Active energy (kWh)±0.5% of range
Re Active energy (kVArh)±0.5% of range
Apparent energy (kVAh)±0.5% of range
Accuracy of Analog Output1% of Output end value
Power Factor±1% of Unity
Angle±1% of range
Total Harmonic Distortion±1%

 

Input Voltage
Nominal input voltage
(AC RMS)
Phase –Neutral 63.5 / 133 / 239.6/ 254 VL-N
Line-Line 110/230/415/ 440 VL-L
System PT primary values100VLL to 692kVLL programmable on site
Max continuous input voltage120% of rated value

 

Input Current
Nominal input current5A AC RMS
System CT secondary values1A & 5A programmable on site
System CT primary valuesFrom 1A up to 9999A
(for 1 or 5 Amp)
Max continuous input current120% of rated value

 

Auxiliary Supply
AC/DC Auxiliary Supply100V… 250 VAC DC +/- 10%
DC Auxiliary Supply12…..48 VDC +/- 10%
AC Auxiliary supply frequency range45 to 66 Hz

 

Overload Withstand
Voltage2 x rated value for 1 second,
repeated 10 times at 10 second intervals
Current20x rated value for 1 second,
repeated 5 times at 5 min

 

Operating Measuring Ranges
Voltage5… 120% of rated value
Current5 … 120% of rated value
Frequency40…70 Hz
Power Factor0.5 Lag ... 1... 0.8 Lead

 

Influence of Variations
Temperature coefficient0.025%/°C for Voltage (50... 120% of rated value) and
0.05%/°C for Current (10... 120% of rated value)

 

Environmental
Operating temperature-20 to +70°C
Storage temperature-30 to +80°C
Relative humidity0... 95% non condensing
Warm up timeMinimum 3 minute
Shock15g in 3 planes
Vibration10... 55 Hz, 0.15mm amplitude

 

Display update rate
Response time to step input1 sec approx.
 
Applicable Standards
EMCIEC 61326
ImmunityIEC 61000-4-3. 10V/m min –
Level 3 industrial low level
SafetyIEC 61010-1-2001 , Permanently connected use
IP for water & dustIEC60529
Pollution degree2
Installation categoryIII
High Voltage Test2.2 kV AC, 50Hz for 1 minute between all electrical circuits
 
VA Burden
Nominal input voltage burden< 0.2 VA approx. per phase
Nominal input current burden< 0.6 VA approx. per phase
Auxillary Supply burden
For VAC Aux.

< 6.5 VA approx.
For DC Aux.< 3 W approx.

 

PT Secondary Ranges for Various Input Voltage
Input VoltagePT Secondary Settable Range
110V L-L (63.5V L-N)100V – 120V L-L (57V – 69V L-N)
230V L-L (133V L-N)121V – 239V L-L (70V – 139V L-N)
415V L-L (239.6V L-N)240V – 480V L-L (140V – 277V L-N)

 

Ampere Hour
Default pulse rate divisorCT secondary = 1A Max pulse rate 3600 pulses/Ah *
CT secondary = 5A Max pulse rate 720 pulses/Ah
Other Pulse rate
Divisors (applicable only when Energy on MODBUS (RS-485) is in W)
10CT secondary = 1A Max pulse rate 3600 pulses/10Ah *
CT secondary = 5A Max pulse rate 720 pulses/10Ah
100CT secondary = 1A Max pulse rate 3600 pulses/100Ah *
CT secondary = 5A Max pulse rate 720 pulses/100Ah
1000CT secondary = 1A Max pulse rate 3600 pulses/1000Ah *
CT secondary = 5A Max pulse rate 720 pulses/1000Ah
Pulse duration60 ms, 100 ms or 200 ms
*No. of Pulses = Maximum Pulses
                      CT Ratio
Where, CT Ratio = (CT primary/ CT Secondary)
Write Your Own Review
Only registered users can write reviews. Please Sign in or create an account

Products In This Series

As low as