Measure essential electrical parameters in 3 phase 4 wire and 3 phase 3 wire networks with Simpson’s new Amik A200 3-Phase Digital Power Meter. The Amik A200 measures import export energy, AC voltage, frequency, AC current, active, reactive, apparent power and more with accuracy and efficiency. More still, the meter has a 1/4 DIN (96 x 96mm) construction, 3 line 0.56” red LED display and is UL certified.
*Note: A three-phase, terminal style current transformer must be used with the Simpson Amik A200 Digital Power Meter.
Reference Conditions For Accuracy | |
Reference Temperature | 23°C +/- 2°C |
Input Waveform | Sinusoidal (distortion factor 0.005) |
Input Frequency | 50 or 60 Hz +/-2% |
Auxiliary Supply Voltage | Rated Value +/-1% |
Auxiliary Supply Frequency | Rated Value +/-1% |
Voltage Range | 20... 100% of Nominal Value. |
Current Range | 10... 100% of Nominal Value. |
Power | Cos phi / sin phi = 1 for Active / Reactive Power & Energy. 10... 100% of Nominal Current & 20... 100% of Nominal Voltage. |
Power Factor / Phase Angle | 40... 100% of Nominal Current & 20... 100% of Nominal Voltage. |
Accuracy | |
Voltage | ± 1% of Nominal Value. |
Current | ± 1% of Nominal Value. |
Frequency | 0.5% of mid frequency |
Active Power | ± 1% of Nominal Value. |
Re-Active Power | ± 1% of Nominal Value |
Apparent Power | ± 1% of Nominal Value. |
Active Energy | ± 1% |
Reactive Energy | ± 1% |
Apparent Energy | ± 1% |
Power Factor | 2% of Unity |
Phase Angle | 2% of range |
Input Voltage | |
Nominal Input Voltage (AC RMS) | Phase –Neutral 290V L-N , Line-Line 500V L-L |
Max Continuous Input Voltage | 120% of rated value |
Nominal Input Voltage Burden | < 0.3 VA approx. per phase (For external auxiliary meter) |
System PT Secondary Values | 100VLL to 500VLL programmable on site. |
System PT Primary Values | 100VLL to 692kVLL programmable on site. |
Input Current | |
Nominal Input Current | 5A / 1A AC RMS |
System CT Secondary Values | 1A & 5A programmable on site |
System CT Primary Values | From 1A up to 9999A (for 1 or 5 Amp ) |
Max Continuous Input Current | 120% of rated value |
Nominal Input Current Burden | < 0.2 VA approx. per phase |
Auxiliary Supply | |
External Aux | 40 V – 300V AC-DC (± 5 % ) |
Frequency Range | 45 to 65 Hz |
VA Burden | < 4 VA Approx. |
Overload Withstand | |
Voltage | 2 x rated value for 1 second, repeated 10 times at 10 second intervals |
Current | 20x rated value for 1 second, repeated 5 times at 5 min intervals |
Operating Measuring Ranges | |
Voltage Range with External Aux | 10… 120% of rated value |
Voltage Range with Self Power | 80… 120% of rated value |
Current Range | 10 … 120% of rated value |
Frequency | 45…65 Hz |
Power Factor | 0.5 Lead ... 1 ... 0.5 Lag |
Influence of Variations | |
Temperature Coefficient | 0.025%/°C for Voltage 0.05%/°C for Current |
Display Update Rate | |
Response Time to Step Input | 1 sec approx. |
Enclosure | |
Front | IP 50 |
Back | IP 20 |
Environmental | |
Operating Temperature | -20° to +70°C |
Storage Temperature | -30°C to +80°C |
Relative Humidity | 0 to 95% non condensing |
Warm Up Time | Minimum 3 minute |
Shock | 15g in 3 planes |
Vibration | 10... 55 Hz, 0.15mm amplitude |
Safety | |
Pollution Degree | 2 |
Installation Category | III |
High Voltage Test | 4.7 kV DC, for 1 minute between Aux. and measuring inputs |
Applicable Standards | |
EMC | IEC 61326-1: 2005 |
Safety | IEC 61010-1-2001 , Permanently connected use |
IP for Water & Dust | IEC60529 |
Dimensions and Weight | |
Bezel Size | 96 mm x 96 mm DIN 43 718 |
Panel Cut-Out | 92 +0.8 mm x 92 + 0.8 mm |
Overall Depth | 55 mm (without output options) |
Panel Thickness | 1 - 3 mm for self clicking, 1 – 6 mm for swivel screws |
Weight | 320 gm. Approx (with output options).. |