We use cookies to make your experience better. To comply with the new e-Privacy directive, we need to ask for your consent to set the cookies. Learn more.
The Megger DET2/3 is a durable and compact automatic earth (ground) test instrument crafted to measure earth electrode resistance and soil resistivity. It is ideal for use on large or more complex earth systems, which include communications earth systems and difficult test environments, it can be used to test in accordance with BS 7430 (earthing / grounding), BS-EN-62305 (Lightning Protection), BS-EN-50122-1 (Railway Applications), and IEEE Standard 81.
Test frequency, test current and filtering can be effortlessly adjusted so that adverse conditions, which can affect the test, can be diminished. The DET2/3 boasts a vast band of test current frequencies, with a resolution of 0.5 Hz, that can be used to eliminate errors caused by noise in the earth.
With its microprocessor controlled system it offers a flexible and ‘user-friendly’ approach to earth tests by the provision of superior error detection abilities and full test information shown on a vivid color display. The DET2/3 can provide a live trace of its measurements, which graphically presents the amount of noise from the system under test - a useful diagnostic tool for the expert earth (ground) test engineer.
The DET2/3 also includes an automatic frequency selection feature that scans for frequencies with the lowest noise level and then runs a test at that frequency. The selected test current frequency, test current level and the increased filtering option are stored in memory for use in subsequent tests.
2, 3 and 4 pole resistance measurements | |
Range | 0.001 Ω to 20.00 kΩ auto range |
Display | 4-digit display |
Accuracy | ±0.5 % of reading ±2 digits at 23 °C ±2 °C |
Operational uncertainty | ±2 % of reading, ±2 digits (meets IEC61557 operational uncertainty requirement with readings over 10 mΩ) when spike resistances are below 100 Ω ±5% of reading ±2 digits ±10 mΩ (meets IEC61557 operational uncertainty requirement with readings over 10 mΩ) |
Test standards | BS 7430 (Grounding) BS 62305 (Lightning) BS50122 (Railway) IEEE Standard 81 |
Test frequency | 10 Hz to 200 Hz in steps of 0.5 Hz |
Test current | 50 mA max. |
Maximum output voltage | Less than 50 V rms |
Maximum interference | Up to 50 V pk to pk |
3 and 4 pole ART (selective) resistance measurements | |
Range | 0.01 Ω to 10.00 kΩ auto range |
Accuracy | ±5 % of reading ±3 digits at 23 °C ±2 °C |
Stakeless resistance measurement | |
Range | 0.01 Ω to 200 Ω |
Accuracy | ±7 % accuracy, ±3 digits |
Leakage current | |
Range | 0.00 A to 2.00 A |
Accuracy | ±5% (±3 digits) |
Instrument specifications | |
Display | 4 .3 inch QWVGA, daylight viewable backlit color |
Operating temperature and humidity | +14 to +104 °F (-10 to +40 °C) 90 % RH max at +104 °F (+40 °C) |
Storage temperature | -4 to + 140 °F (-20 to +60 °C) |
IP rating | IP54 operational (lid open), IP65 storage (lid closed) |
Measurement rating | CAT IV 300 V |
Power supply | Internal Li-ion battery or external 12-18 V, 65 W, DC supply |
Battery life | Up to 10 hrs use |
Battery charging time | Fast recharge to 50%, 3 hrs for 100% |
Safety | Meets IEC 61010 |
EMC | Meets IEC 61326 |
Dimensions | L12.4 x W 11.2 x H 7.1 in. (L 315 x W 285 x H 181 mm) |
Weight | 9.9 lb (4.5 kg) |
Data download | To PC through USB 2.0 |
Data storage | On board 500 record storage providing 900,000 data points downloadable as *.txt |
USB type A | Data download to USB drive |
USB type B | Data download to PC |
Secondary measurement display | Noise, voltage and current |
Resistivity calculation | Wenner: PE = 2 π a RW Schlumberger: PE = π b (b+a) R a |
Test modes | Internally set 2P, 3P, ART (Selective), 4P, Stakeless (clamp) modes |
Aux inputs | MCC1010, MVC1010 |
RoHS compliant | Yes |