We use cookies to make your experience better. To comply with the new e-Privacy directive, we need to ask for your consent to set the cookies. Learn more.
Test Voltages to 5000 V
The Metriso 5000A is suited for the non-destructive measurement of insulation resistance in electrical systems, at machines and transformers and in cables, as well as within the electrical equipment of, for example, locomotives, tram systems and ocean going vessels, with eight selectable test voltages up to 5 kV.
Voltage Measurement to 2000V
With the voltage measuring ranges, test objects can be checked for the absence of voltage in networks of up to 2 kV. This is important for insulation resistance measurement, because extraneous voltages distort measurement results.
Discharge of Capacitive Devices Under Test
Capacitive devices under test such as cables and coils, which might be discharged to test voltage, are discharged by the measuring instrument. The drop in voltage can be observed at the needle gauge.
Measurements per EN61557 Parts 1 and 2 (VDE0413)
Measuring current is equal to 1 mA at a test voltage of 100 V, 250 V, 500 V and 1000 V.
Measurement Cables with Heavy-Duty Insulation
The measurement cables with heavy-duty insulation are permanently connected for safety and technical reasons. Possible danger caused by the unintentional removal of cables is thus avoided, for example when charging occurs due to capacitive test objects.
Needle Gauge with LEDs
Three LEDs arranged within the needle gauge make reading easier. The lamp lights up which is located next to the scale, which is assigned to the selected measuring range. During the measurement sequence, the green LED indicates whether or not the battery charge is sufficient for the measurement.
Reference Conditions | |
Ambient Temperature Relative Humidity Meas. Quantity Frequency Line Voltage Waveform Battery voltage Operating position | +23 °C ±2 K 40 ... 60% 50 Hz ±10 Hz (for voltage measurements) Sine, deviation between effective and rectified value < 1% 8 V ±1% Horizontal |
Power Supply | |
Standard or Storage Battery Working Range Battery Service Life Crank Generator (optional) Nominal Voltage Nominal Power | 6 ea. 1.5 V single cell per IEC R20 (6 x D-Size) 6 V ... 10 V 7500 measurements for test voltage of 1000 V with meas. resistance of 1 MΩ, 15000 measurements for test voltage of 500 V with meas. resist. of 500 kΩ, measurement of 5 s – pause 25 s 2 to 3 r.p.s. with moderate strength, the LED Ω signals sufficient crank frequency and consequently the validity of measuring values 7.5 V (at approx. 2.5 r.p.s.) 4 W (at approx. 2.5 r.p.s.) |
Ambient Conditions | |
Operating Temperature Storage Temperature Relative Humidity Elevation | 0 °C ... + 40 °C -20 °C ... + 60 °C (without batteries) max. 75%, condensation must be avoided up to 2000 m |
Electrical Safety | |
Protection Class Test Voltage Measuring Category Nominal Voltage Open Circuit Voltage Contamination Degree | II 8.5 kV~ 1000 V CAT II or 2000 V CAT I 1000 V 5000 V 2 |
Electromagnetic Compatibility (EMC) | |
Product standard | DIN EN 61326-1:2006 |
Mechanical Design | |
Dimensions Weight Protection | W x D x H: 290 mm x 250 mm x 140 mm 3.4 kg with batteries IP 52 |
Write Your Own Review
The Metriso 5000A is ideally suited for insulation measurements of cables, motors, etc. This instrument is used for the non-destructive measurement of insulation resistance in electrical systems, machines, transformers, and cables. With its eight selectable test voltages up to 5KV, the Metriso 5000A can be used in many applications, including locomotives, tram systems, and ocean going vessels.