The METRAHIT ENERGY is a compact, single phase Power and Power Quality meter/logger that includes multimeter functions. It is intended for measuring AC and DC voltage, and current in single-phase systems, with current being measured either directly, or via a current transformer. The METRAHIT ENERGY has a resolution of 60,000 digits and has more than 35 different measuring functions including: active power, reactive power, apparent power, power factor and energy. This powerful multimeter is extremely rugged and reliable with a housing made of impact resistant ABS.
Includes
- • MetraHit Energy
- • KS29 (3 safety measurement cables)
- • Batteries
- • Quick guide operating instructions
- • CD ROM with operating instructions
- • Rubber holster
Data Interface
Type
Optical via infrared light through the housing
Data transmission
Serial, bidirectional (not IrDa compatible)
Protocol
Device specific
Baud rate
38,400 baud
Functions
– Select/query measuring functions and parameters
– Query momentary measurement data
– Read out stored measurement data
The USB X-TRA plug-in interface adapter (see accessories) is
used for adaptation to the PC’s USB port.
Internal Measured Value Storage
Memory capacity
16 MBit for approx. 300,000 measured values with indication of date and time
Power Supply
Battery
2 each 1.5 V AA batteries, alkaline
manganese per IEC LR6 (2 each 1.2 V
NiMH rechargeable batteries also possible)
Service life
With alkaline manganese: approx. 120 hrs.
Battery indicator
Battery capacity display with battery symbol in 4 segments.
Querying of momentary battery voltage via menu function.
Power OFF function
The multimeter is switched off automatically:
– When battery voltage drops below
approx. 1.8 V
– If none of the keys or the rotary switch
are activated for an adjustable duration
of 10 to 59 min. and the multimeter is
not in the continuous operation mode
(assuming the instrument is not set to
power measurement or mains analysis)
Power pack socket
If the NA X-TRA power pack has been
plugged into the instrument, the batteries
are disconnected automatically.
Rechargeable batteries can only be
recharged externally.
Power pack voltage: 5.1 V ±0.2 V
Display
Background Illumination
LED fiber-optic background illumination is switched off approx. 1
minute after it has been activated. If necessary, automatic
deactivation of background illumination can be disabled with the
appropriate parameter setting or via the interface.
Digital
Display / char. height
7-segment characters
Main display: 13 mm
Auxiliary displays: 7.5 mm
Number of places
60,000 counts/steps
Overflow display
“OL” is displayed as of 61,000 + 1 digits
Polarity display
“–” sign is displayed if plus pole is
connected to “⊥”
Sampling rate
10 or 40 measurements per second with
the Min-Max function except for the
capacitance, frequency, duty cycle and
power measuring functions, 2000
measurements per second for fast DC
measurement
Refresh rate
V (DC, AC+DC), A, Ω,
EVENTS AC/DC, count 2 per second
Hz, °C (Pt100, Pt1000) 1 to 2 per second
°C (J, K) 0.5 per second
Acoustic Signals
For voltage Intermittent signal at above 600 V
For current Intermittent signal at above 10 A
Continuous signal at above 16 A
Fuse
Fuse link FF (UR) 10 A/1000 V AC/DC,
10 mm x 38 mm,
breaking capacity of at least 30 kA at
1000 V AC/DC,
protects the current measurement input in
the 600 μA to 10 A ranges
Electrical Safety
Per IEC 61010-1:2001/VDE 0411-1:2002
Protection class II
Measuring category CAT III CAT IV
Operating voltage 600 V 300 V
Pollution degree 2
Test voltage 5.2 kV~
Electromagnetic Compatibility (EMC)
Interference emission EN 61326-1: 2006, class B
Interference immunity EN 61326-1: 2006
EN 61326-2-1: 2006
Ambient Conditions
Accuracy Range 0 °C to +40 °C
Op. temp. range TA −10 °C to +50 °C*
Storage temp. range −25 °C to +70 °C (without batteries)
Relative humidity 40 to 75%, no condensation allowed
Elevation To 2000 m
Deployment Indoors, except within specified ambient conditions
* Exception: measurement of current > 10 to 16 A, operation at up to 40 °C
Mechanical Design
Housing Impact resistant plastic (ABS)
Dimensions 200 x 87 x 45 mm
(without rubber holster)
Weight Approx. 0.4 kg with batteries
Protection Housing: IP 52
- • Energy efficiency
- • Single phase PQ troubleshooting
- • Motor loading, testing and health
- • Branch circuit and loading
- • Neutral circuit testing