Designed for maximum user versatility, GF Signet is offering their 3-8900 Multi-Parameter Controller. The field commissioned 3-8900 is equipped with users-specified combination of inputs, outputs, and relays using modular boards into the base unit that are effortless to install. Users can configure the controller by choosing either two, four or six input channels as well as power module with universal AC line voltage or 12 to 24 VDC.
The 3-8900 allows for longer cables to be run and easy wiring with little noise interference. The advanced relay logic enables users to choose up to three measurement sources to trigger one relay. Derived measurements include difference, sum, ratio, percent recovery, percent rejection, percent passage and BTU.
Standards:
General | ||||
Compatibility | Modular (completely field-commissionable) | |||
No. of Input Channels | 2, 4, or 6 | |||
Compatible Sensors | See System Overview | |||
Input Signal Types | Digital (S3L) | Serial ASCII, TTL level 9600 bps | ||
Frequency | 0.5% of reading | |||
Measurement Types | Flow, pH, ORP, Conductivity/Resistivity, Pressure, Temperature, Level, or 3rd party devices with a 4 to 20 mA output | |||
Derived Measurements | Sum, difference, ratio, % recovery, % reject, % passage, power (BTU) | |||
No. of Relays Supported | Available: 2, 4, 6 or 8 (8 dry-contact or 4 solid state and 4 dry- contact) | |||
No. of Analog Outputs | Available in pairs: 2 or 4 (active and/or passive 4 to 20 mA); and/or 2 (0 to 5/10 VDC) | |||
Enclosure and Display | ||||
Enclosure Rating | NEMA 4X/IP65 (front face only) | |||
Case Material | PBT | |||
Panel Gasket | Silicone Sponge | |||
Window | Self-healing polyurethane-coated polycarbonate | |||
Keypad | 4-buttons, highly tactile and audible injection-molded silicone rubber seal | |||
Display | Alphanumeric 2 x 16 back-lit LCD | |||
Update Rate | 1 second | |||
Accuracy | Sensor dependent | |||
LCD Contrast | 4 settings | |||
Languages Available | English, French, Spanish, German, Italian and Portuguese | |||
Display Ranges (see sensor specifications for actual measurement limits) | ||||
pH | -2.00 to 15.00 pH | |||
pH Temperature | -40 °C to 150 °C | -40 °F to 302 °F | ||
ORP | -9999 to +9999 mV | |||
Flow Rate | 0.0000 to 999999 units per second, minute, hour or day | |||
Totalizer | 0.00 to 99999999 units | |||
Conductivity | 0.0000 to 999999 μS, mS, PPM & PPB (TDS), kΩ, MΩ | |||
Conductivity Temperature | -99.9 °C to 250 °C | -148 °F to 482 °F | ||
Temperature | -99.9 °C to 999.9 °C | -148 °F to 999.9 °F | ||
Pressure | -99.99 to 9999 psi, kPa, bar | |||
Level | -99999 to 99999 m, cm, ft, in., % | |||
Volume | -99999 to 999999 m3, ft3, in3, cm3, gal, L, kg, lb, % | |||
Other (4 to 20 mA) | -99999 to 999999 user selectable units | |||
Environmental | ||||
Ambient Operating Temperature | ||||
Backlit LCD | -10 °C to 55 °C | 14 °F to 131 °F | ||
Storage Temperature | -15 °C to 80 °C | 5 °F to 176 °F | ||
Relative Humidity | 0 to 95%, non-condensing | |||
Maximum Altitude | 2,000 m (6,560 ft) | |||
4,000 m (13,123 ft); use only DC power supply and, if applicable, solid state relays to maintain UL safety standard up to this altitude | ||||
Electrical | ||||
Power Requirements (AC or DC via Power Modules) | ||||
Universal AC | 100 to 240 VAC ±10%, regulated 50-60 Hz, 24 VA max. | |||
DC | 12 to 24 VDC, ±10%, regulated recommended, 7 Watts max. | |||
Output Power to Sensors | 5 VDC up to 40 mA total | |||
Terminal type | Screw-clamp, removable via plug-in modules | |||
Analog Outputs (via I/O Modules and Output Modules) All analog outputs are freely assignable to any channel. | ||||
4 to 20 mA Output | Endpoints are adjustable and reversible | |||
Minimum Default | 4.0 mA; user adjustable from 3.8 to 5.0 mA | |||
Maximum Default | 20.00 mA; user adjustable from 19.0 to 21.0 mA | |||
Test Mode | Produces an adjustable 4 to 20 mA signal for functional verification of each output circuit | |||
Isolation | Up to 48 VAC/DC | |||
Error Condition | 22.1 mA (default state when output source not configured) | |||
Update Rate | 100 ms | |||
Accuracy | ±32 μA over entire operating temperature range | |||
Passive 4 to 20 mA (External Power required) | ||||
Voltage | 12 to 24 VDC, ±10%, regulated | |||
Max. Impedance | 250 Ω @ 12 VDC | 500 Ω @ 18 VDC | 750 Ω @ 24 VDC | |
Active 4 to 20 mA (Internally Loop Powered) | ||||
Max. Impedance | 750 Ω | |||
0 to 5/10 VDC Output | Endpoints are adjustable and reversible | |||
Output Range | 0 to 5 VDC or 0 to 10 VDC, software selectable | |||
Minimum Default | 0 VDC; user programmable from 0 to 0.5 VDC | |||
Maximum Default | 5 VDC; user programmable from 4.5 to 5.5 VDC, or 9.5 to 10.5 VDC | |||
Output Load | 10 kΩ minimum | |||
Test Mode | Produces an adjustable signal for functional verification of each output circuit | |||
Isolation | Up to 48 VAC/DC | |||
Error Condition | 0 VDC (default state when output source not configured) | |||
Update Rate | 100 mS | |||
Accuracy | ±20 mV over entire operating temperature range | |||
Resolution | 5 mV | |||
Power Supply Rejection | 0.5 mV/V | |||
Relay Modules All relays are freely assignable to any channel. | ||||
Internal relay modes of operation | Off , Low, High, Window, Proportional Pulse, Pulse Width Modulation, USP, Volumetric, Pulse, Totalizer Volume, Advanced, % Rejection, % Recovery, % Passage | |||
External relay modes of operation | Off , Low, High, Window, USP, Totalizer Volume, Advanced, % Rejection, % Recovery, % Passage | |||
Hysteresis | User adjustable | |||
Time Delay | 0 to 6400 seconds | |||
Advanced Relay | Use “AND/OR” logic along with relay sources to trigger a relay. High/Low modes available for each of the 3 sources | |||
Solid State Relays | Non-mechanical switches | |||
Normally Open/Closed Operation | Software selectable | |||
Maximum Voltage Rating | 30 VDC or 42 VAC p-p | |||
Current Rating | 50 mA DC or 50 mA AC RMS | |||
On-state Impedance | 30 Ω or less | |||
Off-state Leakage | 400 nA or less, AC or DC | |||
Isolation | Up to 48 VAC/DC | |||
Transient Protection | Embedded, up to 48 V over-voltage | |||
Dry-contact Relays | Mechanical contacts | |||
Type | SPDT | |||
Form | C | |||
Maximum Pulse Rate | 600 pulses/min. (volumetric pulse & PWM modes) | |||
400 pulses/min. (prop. pulse mode) | ||||
Maximum Voltage Rating | 30 VDC or 250 VAC | |||
Current Rating | 5 A | |||
Shipping Weight | ||||
Base Unit | 1.00 kg | 2.25 lb | ||
Power Module | 0.12 kg | 0.25 lb | ||
I/O Module | 0.12 kg | 0.25 lb | ||
Output Module | 0.12 kg | 0.25 lb | ||
Relay Module | 0.12 kg | 0.25 lb | ||
Standards and Approvals | ||||
CE, UL, FCC | ||||
RoHS compliant, China RoHS | ||||
Manufactured under ISO 9001 for Quality and ISO 14001 for Environmental Management and OHSAS 18001 for Occupational Health and Safety |