Fluke Networks 26500090 TS90 Cable Fault Finder with BNC to Alligator Clips

SKU
26500090
Manufacturer:
Fluke Networks
Fluke Networks

Key Features:

  • Works on any two or more conductor cable up to 2,500 feet (762 meters)
  • Instantly measures distance to open or any fault from one end of any cable pair
  • Patented SmartTone® tone generator positively identifies pair
  • Measures cable distance on spool
  • Measures constantly while 'on'
  • Displays distance reading rather than waveform
  • Large LED screen
  • High voltage detection
  • Moisture proof
  • One-button operation
  • Additional line cord options available for coaxial cable (F-connectors) and other applications
Product Options:
$320.99

Secured and trusted checkout with

The Fluke Networks 26500090 TS90 is an easy-to-use cable fault locator, cable and wire manager, and tone generator. The TS90 lets you easily find the distance to opens or shorts on electrical wire, telephone wire, security wire and coax. The TS90 has SmartTone technology that gives you 5 distinct tones to use for exact wire and pair identification, even in proximity to current-bearing cable.

General Specifications
Power of operation4 AA alkaline batteries, provide 50 hours
Reverse Battery ProtectionNo damage to the tester will occur if the batteries are installed backwards.
Input Protection250 V rms ac, continuous or intermittent
MoistureIf the tester is exposed to water, some may get inside, but it will suffer NO DAMAGE. See the moisture notes in the Maintenance section.
Impedance Range35 Ω to 330 Ω with auto-compensation within this range. Cables with an impedance outside this range will not be properly tested and may produce erratic or incorrect readings.
Maximum Length2500 feet on most cable types, and 500 feet on very lossy cables. The tester will feet on very lossy cables. The tester will display –Err if the cable is too long to be correctly measured.
Representative Maximum
Cable Length
2500 feet: CAT-5 Twisted Pair
2000 feet: 12/2 ac Wire
1000 feet: RG-6/U TV Coax
500 feet (150 meters): RG-174/U Coax
Minimum LengthNo minimum length. Minimum non-zero reading is 2 feet.
Length Accuracy±2 feet for cables less than 10 feet ±5 feet for cables longer than 10 feet and shorter than 200 feet ±3 % and ±5 feet for cables longer than 200 feet
High Voltage DetectionAn ac voltage of more than 5 V rms will trigger the High Voltage Warning.
Measurement RateMaximum of 4 complete measurements per second, decreasing to 2 seconds per measurement based on cable size and uniformity.
VOPAdjustable from -20- to -99-, retained during power off. Default to -66- when batteries are changed.
Measurement TechnologyTime Domain Reflectometry (TDR) with 50 Ω drive impedance, 6 V maximum pulse height.
Low BatteryIndicator flashes when battery voltagefalls below 4.1 V
Tone InjectionApproximately 1 kHz at an amplitude of 80 % of battery voltage. Variable frequency and cadence. Tone characteristic is changed as cable condition changes to “normal-open” from any other condition.
Cable TypeVirtually all two or more conductor cables
Temperature Range Operating Storage32 °F to 131 °F (0 °C to 55 °C) -40 °F to 158 °F (-40 °C to 70 °C)
Humidity Operating Storage0 % to 80 % 0 % to 100 %
Weight1 lb with batteries and clip leads
Operating Altitude10,000 ft max
Certifications and ComplianceConformité Européenne. Conforms to relevant European Union directives. CAN/CSA-C22.2 No. 60950-1-03 CAN/CSA-C22.2 No. 1010.1-92 CSA-C22.2 No. 1010.1B-97, UL/ANSI 3111-1

 