Technicians that work in high voltage dc environments, such as solar arrays, wind power, electric railways, data centers battery banks for uninterruptible power supplies, the Fluke 393 FC true-rms clamp meter with iFlex is the meter to use. The Fluke 393 FC can measure up to 1500 V dc, 1000 V ac, and up to 999.9 A dc or ac through the clamp jaw. With the included iFlex flexible current probe the ac current measures up to 2500 amps.
Includes:
- • Fluke 393 FC CAT III 1500 V TRMS clamp meter
- • Test leads, CAT III 1500 V rated, right angle plugs, with safety caps
- • iFlex 18 inch flexible current probe
- • TPAK magnetic hanging strap
- • Premium carrying case
- • 3-year warranty
Set up and sustain preventive maintenance procedures easily using the Fluke Connect® system of wireless test tools and asset management software.
- • Improve your ability to prevent or predict machine failures
- • Make confident decisions with data you can trust and track
- • Access your infrared images from anywhere, anytime with secure cloud storage
- • Connect and collaborate with your team – even when you are in different places
- • Provide more complete information to your maintenance teams
- • Generate work orders that include measurements and infrared images
- • Edit and analyze images; create and send reports from your smartphone directly from the field
Specifications: | |||
General | |||
Maximum voltage between any Terminal and Earth Ground | |||
AC | 1000 V | ||
DC | 1500 V | ||
Batteries | 2 AA IEC LR6 alkaline | ||
Display | Dual display with backlight | ||
Automatic Power Off | 20 minutes | ||
Electrical | |||
Accuracy | |||
Accuracy is specified for 1 year after calibration, at operating temperatures of 18 °C to 28 °C, relative humidity at 0 % to 75 %. Accuracy specifications take the form of: ±([% of Reading] + [Number of Least Significant Digits]). | |||
Temperature Coefficients | Add 0.1 x specified accuracy for each °C > 28 °C or < 18 °C | ||
AC Current: Jaw | |||
Range | 999.9 A | ||
Resolution | 0.1 A | ||
Accuracy | 2 % + 5 digits (10 Hz to 100 Hz) | ||
2.5 % + 5 digits (100 Hz to 500 Hz) | |||
Crest Factor (50/60 Hz) | 2.5 @600.0 A | ||
3.0 @500.0 A | |||
1.42 @999.9 A | |||
Add 2 % for C.F. >2 | |||
AC Current: Flexible Current Probe | |||
Range | 999.9 A | ||
2500 A | |||
Resolution | 0.1 A (≤999.9 A) | ||
1 A (≤2500 A) | |||
Accuracy | 3 % RD + 5 digits (10 Hz to 500 Hz) | ||
Crest Factor (50/60Hz) | 2.5 @1400 A | ||
3.0 @1100 A | |||
1.42@2500 A | |||
Add 2 % for C.F. >2 | |||
Position Sensitivity | |||
Distance from Optimum | i2500-10 Flex | i2500-18 Flex | Error |
A | 0.5 in (12.7 mm) | 1.4 in (35.6 mm) | ±0.5 % |
B | 0.8 in (20.3 mm) | 2.0 in (50.8 mm) | ±1.0 % |
C | 1.4 in (35.6 mm) | 2.5 in (63.5 mm) | ±2.0 % |
Measurement uncertainty assumes centralized primary conductor at optimum position, no external electrical or magnetic field, and within operating temperature range. | |||
DC Current | |||
Range | 999.9 A | ||
Resolution | 0.1 A | ||
Accuracy | 2 % RD + 5 digits[1] | ||
[1] When using the ZERO (B) function to compensate for offsets. | |||
AC Voltage | |||
Range | 600.0 V | ||
1000 V | |||
Resolution | 0.1 V (≤600.0 V) | ||
1 V (≤1000 V) | |||
Accuracy | 1 % RD + 5 digits (20 Hz to 500 Hz) | ||
DC Voltage | |||
Range | 600.0 V | ||
1500 V | |||
Resolution | 0.1 V (≤600.0 V) | ||
1 V (≤1500 V) | |||
Accuracy | 1 % RD + 5 digits | ||
mV dc | |||
Range | 500.0 mV | ||
Resolution | 0.1 mV | ||
Accuracy | 1 % RD + 5 digits | ||
Amps Frequency: Jaw | |||
Range | 5.0 Hz to 500.0 Hz | ||
Resolution | 0.1 Hz | ||
Accuracy | 0.5 % RD + 5 digits | ||
Trigger Level | 5 Hz to 10 Hz, ≥10 A | ||
10 Hz to 100 Hz, ≥5 A | |||
100 Hz to 500 Hz, ≥10 A | |||
Amps Frequency: Flexible Current Probe | |||
Range | 5.0 Hz to 500.0 Hz | ||
Resolution | 0.1 Hz | ||
Accuracy | 0.5 % RD + 5 digits | ||
Trigger Level | 5 Hz to 20 Hz, ≥25 A | ||
20 Hz to 100 Hz, ≥20 A | |||
100 Hz to 500 Hz, ≥25 A | |||
Voltage Frequency | |||
Range | 5.0 Hz to 500.0 Hz | ||
Resolution | 0.1 Hz | ||
Accuracy | 0.5 % RD + 5 digits | ||
Trigger Level | 5 Hz to 20 Hz, ≥5 V | ||
20 Hz to 100 Hz, ≥5 V | |||
100 Hz to 500 Hz, ≥10 V | |||
DC Power | |||
Range | 600.0 kVA (600.0 V dc range) | ||
1500 kVA (1500 V dc range) | |||
Resolution | 0.1 kVA | ||
1 kVA | |||
Accuracy | 2 % RD + 2.0 kVA | ||
2 % RD + 20 kVA | |||
Resistance | |||
Range | 600.0 Ω | ||
6000 Ω | |||
60.00 kΩ | |||
Resolution | 0.1 Ω (≤600.0 Ω) | ||
1 Ω (≤6000 Ω) | |||
0.01 kΩ (≤60.00 kΩ) | |||
Accuracy | 1 % RD + 5 digits | ||
Capacitance | |||
Range | 100.0 μF | ||
1000 μF | |||
Resolution | 0.1 μF (≤100.0 μF) | ||
1 μF (≤1000 μF) | |||
Accuracy | 1 % RD + 5 digits | ||
Inrush Trigger Level | 5 A | ||
Mechanical | |||
Size (L x W x H) | 281 mm x 84 mm x 49 mm | ||
Weight (with batteries) | 520 g | ||
Jaw Opening | 34 mm | ||
Flexible Current Probe Diameter | 7.5 mm | ||
Flexible Current Probe Cable Length | |||
(head to electronics connector) | 1.8 m | ||
Environmental | |||
Operating Temperature | -10 °C to 50 °C | ||
Storage Temperature | -40 °C to 60 °C | ||
Operating Humidity | Non condensing (<10°C) | ||
≤90 % RH (at 10 °C to 30 °C) | |||
≤75 % RH (at 30 °C to 40 °C) | |||
≤45 % RH (at 40 °C to 50 °C) | |||
Operating Altitude | 2000 m | ||
Storage Altitude | 12 000 m | ||
Ingress Protection (IP) Rating | IEC 60529: IP54 non-operating | ||
Electromagnetic Compatibility (EMC) | |||
International | IEC 61326-1: Portable, Electromagnetic Environment, IEC 61326-2-2 CISPR 11: Group 1, Class A | ||
Group 1: Equipment has intentionally generated and/or uses conductively-coupled radio frequency energy that is necessary for the internal function of the equipment itself. | |||
Class A: Equipment is suitable for use in all establishments other than domestic and those directly connected to a low-voltage power supply network that supplies buildings used for domestic purposes. There may be potential difficulties in ensuring electromagnetic compatibility in other environments due to conducted and radiated disturbances. | |||
Caution: This equipment is not intended for use in residential environments and may not provide adequate protection to radio reception in such environments. | |||
Korea (KCC) | Class A equipment (Industrial Broadcast & Communications Equipment) | ||
Class A: Equipment meets requirements for industrial electromagnetic wave equipment and the seller or user should take notice of it. This equipment is intended for use in business environments and not to be used in homes. | |||
USA (FCC) | 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103. | ||
Safety | |||
General | IEC 61010-1, Pollution Degree 2 | ||
Measurement | IEC 61010-2-032: CAT III 1500 V / CAT IV 600 V | ||
IEC 61010-2-033: CAT III 1500 V / CAT IV 600 V | |||
Wireless Radio | |||
Radio frequency certification | FCC ID: T68-FBLE, IC: 6627A-FBLE | ||
Wireless Radio Frequency Range | 2400 MHz to 2483.5 MHz | ||
Output Power | <100 mW | ||
SIMPLIFIED EU DECLARATION OF CONFORMITY | |||
Hereby, Fluke declares that the radio equipment contained in this Product is in compliance with Directive 2014/53/EU. |