Fluke’s 1732/EUS Three-Phase Electrical Energy Logger delivers all the capabilities of the Fluke 1732/B and comes with three 12 inch 1,500A flexible current probes.
Click here to see the Fluke 1732/B Three-Phase Electrical Energy Logger.
Set up and sustain preventive maintenance procedures easily using the Fluke Connect® system of wireless test tools and asset management software.
- • Improve your ability to prevent or predict machine failures
- • Make confident decisions with data you can trust and track
- • Access your infrared images from anywhere, anytime with secure cloud storage
- • Connect and collaborate with your team – even when you are in different places
- • Provide more complete information to your maintenance teams
- • Generate work orders that include measurements and infrared images
- • Edit and analyze images; create and send reports from your smartphone directly from the field
Specifications | |||||
Accuracy | |||||
Parameter | Range | Resolution | Intrinsic Accuracy at Reference Conditions (% of Reading +% of Full Scale) | ||
Voltage | 1000 V | 0.1 V | ±(0.2% + 0.01%) | ||
Current: Direct input | i17xx-flex 1500 12" | 150 A | 0.1 A | ±(1% + 0.02%) | |
1500 A | 1 A | ±(1% + 0.02%) | |||
i17xx-flex 3000 24" | 300 A | 1 A | ±(1% + 0.03%) | ||
3000 A | 10 A | ±(1% + 0.03%) | |||
i17xx-flex 6000 36" | 600 A | 1 A | ±(1.5% + 0.03%) | ||
6000 A | 10 A | ±(1.5% + 0.03%) | |||
i40s-EL clamp | 4 A | 1 mA | ±(0.7% + 0.02%) | ||
40 A | 10 mA | ±(0.7% + 0.02%) | |||
Frequency | 42.5 Hz to 69 Hz | 0.01 Hz | ±(0.1%) | ||
Auxillary input | ±10 V dc | 0.1 mV | ±(0.2% + 0.02%) | ||
Voltage min/max | 1000 V | 0.1 V | ±(1% + 0.1%) | ||
Current min/max | Defined by accessory | Defined by accessory | ±(5% + 0.2%) | ||
THD on voltage | 1000% | 0.1% | ±0.5 | ||
THD on current | 1000% | 0.1% | ±0.5 | ||
Intrinsic Uncertainty ±(% of reading +% of range)¹ | |||||
Parameter | Influence quantity | iFlex1500-12 | iFlex3000-24 | iFlex6000-36 | i40S-EL |
150 A / 1500 A | 300 A / 3000 A | 600 A / 6000 A | 4 A / 40 A | ||
Active Power P | PF ≥ 0.99 | 1.2% + 0.005% | 1.2% + 0.0075% | 1.7% + 0.0075% | 1.2% + 0.005% |
Active Energy Ea | PF ≥ 0.99 | 1.2% + 0.005% | 1.2% + 0.0075% | 1.7% + 0.0075% | 1.2% + 0.005% |
Apparent power S | 0 ≤ PF ≤ 1 | 1.2% + 0.005% | 1.2% + 0.0075% | 1.7% + 0.0075% | 1.2% + 0.005% |
Apparent Energy Eap | 0 ≤ PF ≤ 1 | 1.2% + 0.005% | 1.2% + 0.0075% | 1.7% + 0.0075% | 1.2% + 0.005% |
Reactive power Q | 0 ≤ PF ≤ 1 | 2.5% of measured apparent power | |||
Reactive Energy Er | 0 ≤ PF ≤ 1 | 2.5% of measured apparent power | |||
Power Factor PF | - | ±0.025 | |||
Displacement Power Factor | - | ±0.025 | |||
DBF/cosϕ | - | ±0.025 | |||
Additional uncertainty in% of range¹ | VP-N>250 V | 0.015% | 0.0225% | 0.0225% | 0.015% |
¹Range = 1000 V x Irange Reference conditions:
|
Electrical Specifications | |||
Power Supply | |||
Voltage range | 100 V to 500 V using safety plug input when powering from the measurement circuit | ||
100 V to 240 V using standard power cord (IEC 60320 C7) | |||
Power consumption | Maximum 50 VA (max. 15 VA when powered using IEC 60320 input) | ||
Efficiency | ≥ 68.2% (in accordance with energy efficiency regulations) | ||
Maximum no-load consumption | < 0.3 W only when powered using IEC 60320 input | ||
Mains power frequency | 50/60 Hz ±15% | ||
Battery | Li-ion 3.7 V, 9.25 Wh, customer-replaceable | ||
On-battery runtime | Four hours in standard operating mode, up to 5.5 hours in power saving mode | ||
Charging time | < 6 hours | ||
Data Acquisition | |||
Resolution | 16-bit synchronous sampling | ||
Sampling frequency | 10.24 kHz at 50/60 Hz, synchronized to mains frequency | ||
Input signal frequency | 50/60 Hz (42.5 to 69 Hz) | ||
Circuit types | 1-φ, 1-φ IT, Split phase, 3-φ delta, 3-φ wye, 3-φ wye IT, 3-φ wye balanced, 3-φ Aron/Blondel (2-element delta), 3-φ delta open leg, Currents only (load studies) | ||
Data storage | Internal flash memory (not user replaceable) | ||
Memory size | Typical 10 logging sessions of 8 weeks with 1-minute intervals and 500 events¹ | ||
¹The number of possible logging sessions and logging period depends on user requirements. | |||
Basic Interval | |||
Measured parameters | Voltage, current, aux, frequency, THD V, THD A, power, power factor, fundamental power, DPF, energy | ||
Averaging interval | User selectable: 1 sec, 5 sec, 10 sec, 30 sec, 1 min, 5 min, 10 min, 15 min, 30 min | ||
Averaging time min/max values | Voltage, Current: Full cycle RMS updated every half cycle Aux, Power: 200ms | ||
Demand Interval (Energy Meter Mode) | |||
Measured parameters | Energy (Wh, varh, VAh), PF, maximum demand, cost of energy | ||
Interval | User selectable: 5 min, 10 min, 15 min, 20 min, 30 min, off | ||
Standards Compliance | |||
Power | IEEE 1459 | ||
Interfaces | |||
USB-A | File transfer via USB flash drive, firmware updates Max. current: 120 mA | ||
WiFi | File transfer and remote control via direct connection or WiFi infrastructure | ||
Bluetooth | Read auxiliary measurement data from Fluke Connect® 3000 series modules (requires 1734, or 1732 upgrade option) | ||
USB-mini | Data download device to PC | ||
Voltage Inputs | |||
Number of inputs | 4 (3 phases and neutral) | ||
Maximum input voltage | 1000 Vrms, CF 1.7 | ||
Input impedance | 10 MΩ | ||
Bandwidth (-3 dB) | 42.5 Hz - 3.5 kHz | ||
Scaling | 1:1 and variable | ||
Measurement category | 1000 V CAT III/600 V CAT IV | ||
Current Inputs | |||
Number of inputs | 3, mode selected automatically for attached sensor | ||
Input voltage | Clamp input: 500 mVrms/50 mVrms; CF 2.8 | ||
Rogowski coil input | 150 mVrms/15 mVrms at 50 Hz, 180 mVrms/18 mVrms at 60 Hz; CF 4; all at nominal probe range | ||
Range | 1 A to 150 A/10 A to 1500 A with thin flexible current probe i17XX-flex1500 12" | ||
3 A to 300 A/30 A to 3000 A with thin flexible current probe i17XX-flex3000 24" | |||
6 A to 600 A/60 A to 6000 A with thin flexible current probe i17XX-flex6000 36" | |||
40 mA to 4 A/0.4 A to 40 A with 40 A clamp i40s-EL | |||
Bandwidth (-3 dB) | 42.5 Hz - 3.5 kHz | ||
Scaling | 1:1 and variable | ||
Auxiliary Inputs | |||
Number of inputs | 2 | ||
Input range | 0 to ±10 V dc, 1reading/s | ||
Scale factor (available 2014) | Format: mx + b (gain and offset) user configurable | ||
Displayed units (available 2014) | User configurable (7 characters, for example, °C, psi, or m/s) | ||
Wireless Connection | |||
Number of inputs | 2 | ||
Supported modules | Fluke Connect® 3000 series | ||
Acquisition | 1 reading/s | ||
Environmental Specifications | |||
Operating temperature | -10 °C to +50 °C (14 °F to 122 °F) | ||
Storage temperature | -20 °C to +60 °C (-4 °F to 140 °F), with battery: -20 °C to +50 °C (-4 °F to 122 °F) | ||
Operating humidity | 10 °C to 30 °C (50 °F to 86 °F) max. 95% RH | ||
30 °C to 40 °C (86 °F to 104 °F) max. 75% RH | |||
40 °C to 50 °C (104 °F to 122 °F) max. 45% RH | |||
Operating altitude | 2000 m (up to 4000 m derate to 1000 V CAT II/600 V CAT III/300 V CAT IV) | ||
Storage altitude | 12,000m | ||
Enclosure | IP50 in accordance with EN60529 | ||
Vibration | MIL-T-28800E, Type 3, Class III, Style B | ||
Safety | IEC 61010-1 | ||
IEC Mains Input: Overvoltage Category II, Pollution Degree 2 | |||
Voltage Terminals: Overvoltage Category IV, Pollution Degree 2 | |||
IEC 61010-2-031: CAT IV 600 V / CAT III 1000 V | |||
Electromagnetic compatibility | EN 61326-1: Industrial CISPR 11: Group 1, Class A | ||
Korea (KCC): Class A Equipment (industrial broadcasting and communication equipment) | |||
USA (FCC): 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103 | |||
Temperature coefficient | 0.1 x accuracy specification/°C | ||
General Specifications | |||
Color LCD display | 4.3-inch active matrix TFT, 480 pixels x 272 pixels, resistive touch panel | ||
Warranty | Instrument and power supply: Two-years (battery not included) | ||
Accessories: one-year | |||
Calibration cycle: two-years | |||
Dimensions | Instrument: 19.8 x 16.7 x 5.5 cm (7.8 x 6.6 x 2.2 in) | ||
Power supply: 13.0 x 13.0 x 4.5 cm (5.1 x 5.1 x 1.8 in) | |||
Instrument with power supply attached: 19.8 x 16.7 x 9 cm (7.8 x 6.6 x 3.5 in) | |||
Weight | Instrument: 1.1 kg (2.5 lb) | ||
Power supply: 400 g (0.9 lb) | |||
Tamper protection | Kensington lock slot | ||
i17xx-flex 1500 12" Flexible Current Probe Specifications | |||
Measuring range | 1 to 150 A ac/10 to 1500 A ac | ||
Nondestructive current | 100 kA (50/60 Hz) | ||
Intrinsic error at reference condition* | ±0.7% of reading | ||
Accuracy 173x + iFlex | ±(1% of reading + 0.02% of range) | ||
Temperature coefficient over operating temperature range | 0.05% of reading/°C 0.09% of reading/°F | ||
Working voltage | 1000 V CAT III, 600 V CAT IV | ||
Probe cable length | 305 mm (12 in) | ||
Probe cable diameter | 7.5 mm (0.3 in) | ||
Minimum bending radius | 38 mm (1.5 in) | ||
Output cable length | 2 m (6.6 ft) | ||
Weight | 115 g | ||
Probe cable material | TPR | ||
Coupling material | POM + ABS/PC | ||
Output cable | TPR/PVC | ||
Operating temperature | -20 °C to +70 °C (-4 °F to 158 °F) temperature of conductor under test shall not exceed 80 °C (176 °F) | ||
Temperature, non-operating | -40 °C to +80 °C (-40 °F to 176 °F) | ||
Relative humidity, operating | 15% to 85% non-condensing | ||
IP rating | IEC 60529:IP50 | ||
Warranty | One-year | ||
* Reference condition:
|