We use cookies to make your experience better. To comply with the new e-Privacy directive, we need to ask for your consent to set the cookies. Learn more.
Like other tools that you have come to expect from Fluke, the 1587 is rugged, reliable and easy to use. Whether you work on motors, generators, cables or switch-gear, the Fluke 1587 Insulation Multimeter is ideally suited to help you with your tasks.
Specifications | ||
Voltage DC | Maximum voltage | 1000 V |
Accuracy | ±(0.09% + 2) | |
Maximum resolution | 0.001 V | |
Voltage AC | Maximum voltage | 1000 V |
Accuracy | ±(2% + 3) | |
AC bandwidth | 5 kHz1 | |
1. with low pass filter; 3 db @ 800 Hz | ||
Maximum resolution | 0.1 mV | |
Current DC | Maximum amps | 400 mA |
Amps accuracy | ±(0.2% + 2) | |
Maximum resolution | 0.01 mA | |
Current AC | Maximum amps | 400 mA |
Amps accuracy | ±(1.5% + 2)2 | |
2. 1 kHz bandwidth | ||
Maximum resolution | 0.01 mA | |
Resistance | Maximum resistance | 50 MΩ |
Accuracy | ±(0.9% + 2) | |
Maximum resolution | 0.1 Ω | |
Capacitance | Maximum capacitance | 9,999 µF |
Accuracy | ±(1.2% + 2) | |
Maximum resolution | 1 nF | |
Frequency | Maximum frequency | 100 kHz |
Accuracy | ±(0.1% + 1) | |
Maximum resolution | 0.01 Hz | |
Temperature Measurement | -40.0°C to 537°C | |
-40.0°F to 998°F excluding probe | ||
Diode test | Range/Resolution | 6 V / 1 mV |
Accuracy | ±(2% + 1) | |
Insulation Test | ||
Minimum test current @ 1kΩ/V | 1 mA | |
Test Voltages | 50, 100, 250, 500, 1000 V | |
Maximum resistance per test voltage | 50 V | |
100 V | ||
250 V | ||
500 V | ||
1000 V | 2 GΩ | |
Maximum resolution per test voltage | 50 V | 0.01 MΩ |
100 V | 0.01 MΩ | |
250 V | 0.1 MΩ | |
500 V | 0.1 MΩ | |
1000 V | 0.1 MΩ | |
Accuracy per test voltage | 50 V | ±(3% + 5) |
100 V | ±(3% + 5) | |
250 V | ±(1.5% + 5) | |
500 V | ±(1.5% + 5) | |
1000 V | ±(1.5% + 5) to 600 MΩ, ±(10% + 3) above 600 MΩ | |
Environmental Specifications | ||
Operating temperature | –20°C to +55°C | |
Storage temperature | -40°C to +60°C | |
Humidity (without condensation) | 0% - 95% (10°C – 30°C) 0% - 75% (30°C – 40°C) 0% - 40% (40°C – 55°C) | |
Operating altitude | 2000 m | |
Safety Specifications | ||
Overvoltage category | Complies with ANSI/ISA 82.02.01 (61010-1) 2004, CAN/CSA-C22.2 NO. 61010-1-04, and IEC/EN 61010-1 2nd Edition for measurement CAT III 1000 V and CAT IV 600 V | |
Agency approvals | 2000 m CAT III 1000 V, CAT IV 600 V; 3000 m CAT II 1000 V, CAT III 600 V | |
Mechanical and General Specifications | ||
Size | 203 x 100 x 50 mm (with holster) | |
Weight | 624 g | |
Warranty | 3 years | |
Battery life alkaline | Meter use | 1000 hours |
Insulation test u6se | Meter can perform at least 1000 insulation tests with fresh alkaline batteries at room temperature. These are standard tests of 1000 V into 1 MΩ with a duty cycle of 5 seconds on and 25 seconds off. | |
IP rating | IP40 |
Fluke 1587 Insulation Multimeter Includes:
- Remote probe
- Test leads
- Alligator clips
- Hard case
- Four AA alkaline batteries
- Quick Reference Guide
- CD Rom with Manual
- K-type thermocouple
Write Your Own Review