Ashcroft DXLdp Low Differential Pressure Transmitter

SKU
DXLdp
Manufacturer:
Ashcroft
Ashcroft

Key Features:

  • The exclusive patent pending Ashcroft® SpoolCal™ actuator provides in-place system calibration without disturbing process tubes
  • Front access test jacks provide on-line signal reference without removing wiring
  • LED range status indicators for instant troubleshooting information
  • DIN Rail Mount – dramatically reduces installation and calibration costs
  • CE standard with all outputs
  • On-board voltage regulation allows use of lower cost, non-precise, unregulated power supply
Product Options:
$513.46

Secured and trusted checkout with

The Ashcroft Si-Glas sensor now enables precise measurement and control of very low pressure. Although the ultra-thin silicon diaphragm deflects only a micron, the sensor is 100 times more sensitive to pressure than available silicon piezoresistive pressure sensors. The Si-Glas sensor is composed of only sputtered metals and glass molecularly bonded to silicon. There are no epoxies or other organics in the sensor to contribute to drift or mechanical degradation over time. The glass-clad silicon diaphragm withstands extreme overpressure as well as severe shock and vibration.

                                        

PERFORMANCE SPECIFICATIONS
Ref. Temperature: 70°F ±2°F (21°C ±1°C)
Accuracy Class (of Span)
Three Options: ±0.25%, ±0.5%, ±1.0%
Includes non-linearity (Terminal Point Method), hysteresis,
non-repeatability, zero offset and span setting errors.
Note: Caibration report included with 0.25% and 0.5% units.
Stability – Max. Change (Span/year): ±0.25%
Standard Ranges (Inches W.C.)
Unidirectional Ranges:
Differential or Gauge
0/0.10      0/1.00      0/ 3.00      0/20.00
0/0.25      0/1.50      0/ 5.00      0/25.00
0/0.50      0/2.00      0/10.00     0/50.00
0/0.75      0/2.50      0/15.00
Bidirectional Ranges:
Compound
±0.05      ±0.50      ±2.00      ± 5.00
±0.10      ±0.75      ±2.50      ±10.00
±0.25      ±1.00      ±3.00      ±25.00
Custom Ranges: Special range calibration,
(XCL) – Consult factory
Standard Response Time: 250m sec
(Consult factory for optional damping times)
ENVIRONMENTAL SPECIFICATIONS
Temperature Limits:
Storage:   –40 to 180°F
Operating: –20 to 160°F
(10-95% R.H. noncondensing)
Compensated Range: +35 to 135°F
Thermal Coefficients:
ZERO      ±0.02% Span/°F
SPAN      ±0.02% Span/°F
FUNCTIONAL SPECIFICATIONS
Overpressure Limits:
Proof                                   15 psid
Burst                                   25 psid
Max. Static Line Pressure: 25 psi
Mounting Position Effect:
0.5˝ W.C. and higher            0.1% Span/g
Below 0.5˝ W.C.                  0.25% Span/g
Note: Mounting Position Effect easily corrected with zero potentiometer.
ELECTRICAL SPECIFICATIONS
Output Signal:         Power:
4-20mA (2 wire)        12-36 Vdc
1-5 Vdc                    12-36 Vdc
1-6 Vdc                    12-36 Vdc
0-5 Vdc                    12-36 Vdc
0-10 Vdc                   12-36 Vdc
Output signal is independent of power
supply changes: 12-36 Vdc range without effect on
output signal
Reverse Wiring Protected
Zero and Span Potentiometers:
Front accessible, non-interactive
Zero:      ±5%F.S.
Span:     ±3%F.S.
Supply Current: < 10mA for voltage
Warm-up Time: 5 sec. max. to meet stated specifications from initial power-up

PHYSICAL SPECIFICATIONS
Pressure Connections: 1⁄8 NPT Female
Weight: 4.5 oz., NEMA 1 Case
MATERIALS:
Enclosure: Glass-filled polycarbonate (UL94-V-1)
Media: Clean, dry and non-corrosive gas (consult
factory for use on other media).
NOT FOR USE ON LIQUIDS
Mounting: DIN rail types EN50022, 35 & 45
OPTIONS
• Option XDL:
LED for quick process diagnostics:
Zero Pressure.........Center Amber LED
In Range ± .............Adjacent Green LED’s
Out of Range ± ......Adjacent Red LED’s
Includes: front access test jacks for on-line data
access without disturbing wiring
• Option XNL: Front access jacks without LED’s
• Option XPV: Available on pressure ranges up to
50IW maximum, SpoolCal™ process valve actuator
provides in-place system calibration without disturbing
process tubes. From Off position the removable
SpoolCal™ actuator tool provides the following functions:
- A 90 degree clockwise rotation puts the DXLdp in
the CAL mode isolating it from the process and
allowing direct external pressure input
- A 90 degree counter clockwise rotation puts the
DXLdp in the MONITOR mode to tee the process
pressure to the DXLdp sensor and out, providing
external measurement or recording capabilities.
Includes SpoolCal™ actuator tool with 7˝ silicon
tubing (as shown in front photo). (Refer to
Ashcroft® ATE series calibrator for data collection
and instrumentation)
• Option X21: 2:1 turn down, 0.25% accuracy is
maintained on initialized range
• Option XCL: Special range calibration
• Option XX1: Fast response (10msec)
• Option XX2: Slow response (1sec)

Write Your Own Review
Only registered users can write reviews. Please Sign in or create an account
  • High reliability:
    HVAC
    Bio-pharm
    Bio-tech
    Room pressurization and control