AEMC Model MN375 AC Current Probe (10A / 100mV/A / Lead)

SKU
2115.41
Manufacturer:
AEMC
AEMC

Key Features:

  • Small, compact size
  • Measurement range of 100mA to 240AAC
  • Large jaw opening accommodated conductors up to 250kcmil
  • Designed for DMMs, loggers, recorders and oscilloscopes
  • Available with mA or mV output signals
  • Conforms to EN 61010, 600V Cat. III
Product Options:
$275.00

Secured and trusted checkout with

The MN375 is a compact AC current probe. It is designed to meet the most stringent demands in industry and electrical contracting. The Model MN375 meets EN 61010, 600V Cat. III safety standards and is CE marked and UL approved. The Model MN375 has a 0.78" (20mm) jaw opening and will accommodate conductors up to 250MCM. The unique hooked jaw design facilitates clamping and hooking into conductors. Polycarbonate materials and ultrasonic welding are used throughout to ensure ruggedness and overall lasting reliability. The Model MN375 is a high performance models and uses a nickel core to improve accuracy and phase shift on the low end of the measurement range. The Model MN375 is an excellent probe to be used in power and low level current measurement application.
ELECTRICAL
Nominal Range10A
Measurement Range0.1 to 10A
Transformation RatioVoltage output
Output Signal100mV/A (1V @ 10A)

Accuracy (10A Range)

0.1 to 1A
1 to 10A
Adjusted to

 

1% of Reading ± 2mV
1% of Reading ± 1.5mV
<0.5° @ 0.25A

Phase Shift (10A Range)

0.1 to 1A
1 to 5A
5 to 10A

 

Not Specified
≤1° @ 60Hz
≤1.5° @ 60Hz

Overload
Frequency Range40 to 3kHz
Limit Operating
20A permanently
Crest Factor
Working/Common
Mode Voltage
600Vrms
Output Termination5 ft Lead
MECHANICAL
Operating Temperature14° to 131°F (-10° to 55°C)
Storage Temperature-40° to 158°F (-40° to 70°C)
Operating Relative
Humidity
10 to 35°C 85% RH (without roll-off above 35°C)
Jaw Opening0.83" (21mm)
Maximum Conductor
Size
0.78" (20mm)
Dimensions5.47 x 2.00 x 1.18" (139 x 51 x 30mm)
Weight6.5 oz (180g)
Polycarbonate MaterialPolycarbonate with fiberglass charge, UL94 V0
SAFETY
ElectricalEN 61010-2-32
UL ApprovalYes – Canada and United States
Double InsulationYes
CE MarkYes

 

Note: Reference conditions: 20 to 26°C, 20 to 75% RH, external magnetic field <40A/m, 48 to 65Hz sine wave, distortion factor less than 1%, no DC component, no external current carrying conductor, test sample centered. Load impedance >1MΩ

Write Your Own Review
Only registered users can write reviews. Please Sign in or create an account
  • Measuring in breaker panels
  • Industrial loads
  • HVAC
  • Residential and commercial sites
  • 5A secondary current transformers (CTs) monitoring
  • Data logging and recording