AEMC Model MN307 AC Current Probe (12A / 100mV/A AC / Lead)

SKU
2116.23
Manufacturer:
AEMC
AEMC

Key Features:

  • Small, compact size
  • Large jaw opening accommodated conductors up to 250kcmil
  • Designed for DMMs, loggers, recorders and oscilloscopes
  • Conforms to EN 61010, 600V CAT III
Product Options:
$250.00

Secured and trusted checkout with

MN307 is designed for low AC current measurements up to 10A, it offers a higher voltage output of 100mV per Amp (1VAC @ 10AAC) for enhanced sensitivity at lower levels, while offering a high crest factor at full range. The MN307 has an integral 5 ft (1.5m) lead terminated by shrouded banana plugs.
Electrical
Nominal Range10A
Measurement Range0.01 to 12A
Transformation RatioVoltage output
Output Signal100mV/A (1V @ 10A)
Accuracy (10A Range) 
0.1 to 0.5A≤2.5% of Reading ± 0.1mV
0.5 to 1A≤2.5% of Reading
1 to 12A≤1.0% of Reading
Phase Shift (10A Range) 
0.01 to 0.1ANot Specified
0.1 to 1A≤5.0°
1 to 5A≤3.0°
5 to 12A≤2.5°
Overload12A for Continuous
Frequency Range40 to 10kHz
Limit Operating
Conditions
200A permanently to 3kHz;
Derating above 3kHz: 200A x (1/0.333F), F in kHz
Crest Factor3 @ 10Arms with an error (due to CF) of 3%
Working/Common
Mode Voltage
600Vrms
Output Termination5 ft Lead
Mechanical
Operating Temperature14° to 131°F (-10° to 55°C)
Storage Temperature-40° to 158°F (-40° to 70°C)
Operating Relative
Humidity
10 to 35°C 85% RH (without roll-off above 35°C)
Jaw Opening0.83" (21mm)
Maximum Conductor Size0.78" (20mm)
Dimensions5.47 x 2.00 x 1.18" (139 x 51 x 30mm)
Weight6.5 oz (180g)
Polycarbonate MaterialPolycarbonate with fiberglass charge, UL94 V0
Safety
ElectricalEN 61010-2-32
UL ApprovalYes – Canada and United States
Double InsulationYes
CE MarkYes

Note: Reference conditions: 20 to 26°C, 20 to 75% RH, external magnetic field <40A/m, 48 to 65Hz sine wave, distortion factor less than 1%, no DC component, no external current carrying conductor, test sample centered. Load impedance >1mΩ

Write Your Own Review
Only registered users can write reviews. Please Sign in or create an account
  • Measuring in breaker panels
  • Industrial loads
  • HVAC
  • Residential and commercial sites
  • 5A secondary current transformers (CTs) monitoring