AEMC Model MN261 24/240 AC Amp Current Probe

SKU
2115.82
Manufacturer:
AEMC
AEMC

Key Features:

  • Small, compact size
  • Large jaw opening accommodates conductors up to 250kcmil
  • Designed for DMMs, loggers, recorders and oscilloscopes
  • Conforms to EN 61010, 600V CAT III
Product Options:
$252.00

Secured and trusted checkout with

The MN261 is a high sensitivity probe with voltage outputs (100mV/A and 10mV/A) and combine two switch-selectable ranges of 20A and 200A, thus permitting accurate measurements at low and high levels. The MN261 is designed for oscilloscopes and other BNC terminated instruments. It has two performing ranges (20A, 200A) both voltage output (100mV/A and 10mV/A) and 40Hz to 10kHz response.
ELECTRICAL
Nominal Range20A & 200A
Measurement Range0.1 to 24A, 0.5 to 240A
Transformation RatioVoltage output
Output Signal20A: 100mV/A,
200A: 10mV/A
Accuracy (20A Range)1% of Reading ± 50mV
Phase Shift (20A Range)Not Specified
Overload (20A Range)24A for 10 min ON, 30 min OFF
Accuracy (200A Range) 
0.5 to 10A3.0% of Reading ± 5mV
10 to 40A2.5% of Reading ± 5mV
40 to 100A2.0% of Reading ± 5mV
100 to 240A1.0% of Reading ± 5mV
Phase Shift (200A Range) 
0.5 to 10ANot Specified
10 to 40A≤5.0°
40 to 100A≤3.0°
100 to 240A≤2.5°
Overload (200A Range)240A for 10 min ON, 30 min OFF
Frequency Range40 to 10kHz
Limit Operating
Conditions
200A permanently to 1kHz; Derating above 3kHz: 200A x (1/0.333F), F in kHz
Crest Factor3 @ 200Arms with an error (due to CF) of 4%
Working/Common
Mode Voltage
600Vrms
Output Termination6 ft BNC
MECHANICAL
Operating Temperature14° to 131°F (-10° to 55°C)
Storage Temperature-40° to 158°F (-40° to 70°C)
Operating Relative
Humidity
10 to 35°C 85% RH (without roll-off above 35°C)
Jaw Opening0.83” (21mm)
Maximum Conductor Size0.78” (20mm)
Dimensions5.47 x 2.00 x 1.18” (139 x 51 x 30mm)
Weight6.5 oz (180g)
Polycarbonate MaterialPolycarbonate with fiberglass charge, UL94 V0
SAFETY
ElectricalEN 61010-2-32
UL ApprovalYes – Canada and United States
Double InsulationYes
CE MarkYes

 

Note: Reference conditions: 20 to 26°C, 20 to 75% RH, external magnetic field <40A/m, 48 to 65Hz sine wave, distortion factor less than 1%, no DC component, no external current carrying conductor, test sample centered. Load impedance >1Ω

Write Your Own Review
Only registered users can write reviews. Please Sign in or create an account
  • Measuring in breaker panels
  • Industrial loads
  • HVAC
  • Residential and commercial sites
  • 5A secondary current transformers (CTs) monitoring