We use cookies to make your experience better. To comply with the new e-Privacy directive, we need to ask for your consent to set the cookies. Learn more.
AEMC is introducing their 8436 (2136.43) PowerPad III three-phase power quality analyzer. Technicians and engineers can measure and perform diagnostics and power quality work on 1, 2 or even 3 phase networks. The 8436 comes with 5 voltage and 4 current inputs and can record up to 2GB of trend data on a memory card. More still, further internal memory is utilized for the storage of alarms, snapshot data and transients. That surplus of memory allows users to store up to 50 screen snapshots, up to 210 captured transients that encompass 4 cycles for each active input and >16,000 alarm events from up to 40 different parameters! Inrush current can also be captured and stored. Users can record trend data for days to months!
The analyzer is user friendly and built with a durable shock resistant design, all while still compact. It is IEC 61000-4-30 Class B and safety rated to 600V CAT IV. When used with the flexible sensor Ampflex 196A it has an IP67 rating.
AEMC has loaded the 8436 with a variety of useful accessories. Each analyzer comes with an extra-large tool bag, five 10 ft black voltage leads with alligator clips, accessory pouch, 5 ft USB cable, NiMH battery, SD-Card, twelve color-coded input ID markers, 110V US power cord, quick start guide, and a USB stick containing DataView® software and user manual.
Inputs | 4 Voltage / 4 Current | ||||
Sample Rate | 256 per Cycle | 12.8kHz at 50Hz | 15.36kHz at 60Hz | ||
Specification | Range | Measurement Range | Resolution | Accuracy (Typical) | |
Volt | |||||
Vrms (AC + DC) | 1000V P to N 2000V P to P | 2 to 1000V | 0.1V | ±0.5% Rdg + 200mV | |
Vpk | 1414V | 2 to 1000V | 0.1V | ±3% Rdg + 2V | |
Vrms Half Cycle | 1000V P to N 2000V P to P | 2 to 1000V | 0.1V | ±0.8% Rdg + 1V | |
Amps (accuracy excluding clamp accuracy) | |||||
Amps (AC + DC) | SR193 & MR193 MN193 5A MN193 100A | 1 to 1000A 5mA to 5A 100mA to 100A | 0.1A 1mA 10mA | ±0.5% Rdg + 200mA ±0.5% Rdg + 2mA ±0.5% Rdg + 20mA | |
AmpFlex& MiniFlex | Range 100A Range 6500A Range 10kA | 100mA to 100A 10 to 6500A 10A to 10kA | 10mA 0.1A & 1A 1A | ±0.5% Rdg + 30mA ±0.5% Rdg + 3A ±0.5% Rdg + 3A | |
Apk | SR193 & MR193 MN193 5A MN193 100A | 1 to 1414A 5mA to 7.017A 100mA to 141.4A | 0.1A 1mA 10mA | ±1% Rdg + 2A ±1% Rdg + 20mA ±1% Rdg + 200mA | |
Apk AmpFlex & MiniFlex | Range 100A Range 6500A Range 10kA | 100mA to 100A 10 to 6500A 10A to 10kA | 1A 0.1A & 1A 1A | ±3% Rdg + 600mA ±3% Rdg + 5A ±3% Rdg + 5A | |
A Half Cycle | SR193 &MR193 MN193 5A MN193 100A | 1 to 1200A 5mA to 6A 100mA to 120A | 0.1A 1mA 10mA | ±1% Rdg + 1A ±1% Rdg + 10mA ±1% Rdg + 100mA | |
Frequency | 40 to 70Hz | 0.01 | ±0.01Hz | ||
Power | |||||
Watts (VA, var) P-Q-S | Probes: AmpFlex, MiniFlex | 10mW to 10MW 10mW to 10MW | 4 digits min 4 digits min | ±1% Rdg ±1.5% Rdg | |
Power Factor (Cos Φ/DPF) | -1.000 to 1.000 | 0.001 | ±1° for Φ, +5 cts for cos Φ | ||
Energy | |||||
kWh (kVAh, kvarh) P-Q-S | 1mWh to 9,999,999MWh (MVAh, Mvarh) | ±1% Rdg | |||
Harmonics | DC, 1 to 50 | ||||
Volts & Amp % | f r Absolute V Absolute A THD | 0.0 to 1500% 0.0 to 100% 0.0 to 1000V 0.0 to 1000A 0.0 to 999.9% | 0.1% 0.1% 0.1V 0.1A 0.1% | ±2.5% Rdg + 5cts ±2.5% Rdg + 5cts ±2.5% Rdg + 1V ±2% Rdg + 1A ±2.5% Rdg + 5cts | |
Phase Angle | -179° to +180° | 1° | ±1.5° +1°x(n/12.5) | ||
Also display Energy loss, Flicker, Plt (2H), Pst (10min), Unbalance V% & A% | |||||
General Features | |||||
Programmable Alarm | Up to 40 types: up to 16,362 recorded max | ||||
Transient Capture | Up to 210 | ||||
Snapshot | Up to 50 (screen BMP + all channels data) | ||||
Interface | Isolated USB, SD card, and Dataview software for real time data, configuration, and reporting included | ||||
Memory | SD card (SDHC compliant, not formatted) standard, for trend Data, Internal memory for In-Rush, transients and alarms | ||||
Display | Color TFT 320 x 240 (1/4 OFT) with graphic representation of system parameters and measurements | ||||
Real-Time Clock | Time and date stamp for Trend mode, Transient display, System Monitor and event capture | ||||
Power Supply | External from 110V to 1000V DC to 440Hz | ||||
Charging Time | 6 hours approx. | ||||
Battery Backup | Rechargeable 9.6V NiMH 4000mA battery pack | ||||
Battery Life | ≥10hrs when display ON | ||||
Dimensions (L x W x H) | 10.6 x 9.85 x 7.09” (270 x 250 x 180mm) | ||||
Weight | 8.16 lbs (3.7kg) | ||||
Altitude Operating | 2000m (6560ft) | ||||
Operating Temperature | 32° to 122°F (0° to 50°C) | ||||
Storage Temperature | -4° to 122°F (-20° to 50°C) | ||||
IP Rating | IP67 per IEC 60529 when housing close and A196 sensor used | ||||
Safety | IEC/EN 61010-1 (1000V CAT III-600V CAT IV), IEC 1326-1 C E |