Accuenergy Acuvim IIBN BACnet Power Meter

SKU
Acuvim IIBN
Manufacturer:
Accuenergy
Accuenergy

Key Features:

  • Revenue grade version available ← Please Call
  • Built-in BACnet-IP Protocol for integration with BAS and other monitoring and control systems
  • BTL Listed for Smart Sensor (B-SS) and BACnet Smart Actuator (B-SA)
  • Built-in mobile-friendly web server for real-time meter reading and configuration
  • Secure access to meter via HTTPs encrypted webpage
Product Options:
$345.00

Secured and trusted checkout with

The Accuenergy Acuvim IIBN energy meter is equipped with a built-in BACnet communication module specifically crafted to monitor and collect real-time revenue-grade electrical data for building control and automation applications. The meter shows multiple energy parameters such as voltage, ampere, power factor, harmonic distortions, energy and demand data making it perfect for three-phase, two-phase and single-phase systems to track energy consumption and trends.

METERING
Parameters
AccuracyResolutionRange
Voltage0.2%0.1V10V~1000kV
Current0.2%0.1mA5mA~50000A
Power0.2%1W-9999MW~9999MW
Reactive Power0.2%1var-9999Mvar~9999Mvar
Apparent Power0.2%1VA0~9999MVA
Power Demand0.2%1W-9999MW~9999MW
Reactive Power Demand0.2%1var-9999Mvar~9999Mvar
Apparent Power Demand0.2%1VA0~9999MVA
Power Factor0.2%0.001-1.000~1.000
Frequency0.02%0.01Hz45.00~65.00Hz
(50 or 60Hz type)
300.00Hz~500.00Hz (400Hz type)
EnergyPrimary0.2%0.1kWh0-99999999.9kWh
Secondary0.2%0.001kWh0-999999.999kWh
Reactive EnergyPrimary0.2%0.1kvarh0-99999999.9kvarh
Secondary0.2%0.001kvarh0-999999.999kvarh
Apparent EnergyPrimary0.2%0.1kVAh0-99999999.9kVAh
Secondary0.2%0.001kVAh0-999999.999kVAh

 

INPUT
Current Inputs (Each Channel)
Nominal Current①5A, ②1A, ③1A(333mV), ④1A(100mV Rope-CT), ⑤1A(80mA/100mA/200mA)
Metering Range①0~10A, ②0~2A, ③0~1.2A,④0~1.2A, ⑤0~1.2A
Pickup Current①5mA, ②1mA, ③5mA, ④5mA, ⑤5mA
Withstand20Arms Continuous, 0.1% of Nominal
100Arms for 1 second, Non-Recurring
Burden0.05VA (Typical) @ 5Arms
Accuracy0.2% Full Scale
Voltage Inputs (Each Channel)
Nominal Full Scale400Vac L-N, 690Vac L-L (+20%)
Withstand1500Vac Continuous
2500Vac, 50/60Hz for 1 Minute
Input Impedance2Mohm per Phase
Metering Frequency45Hz~65Hz, 300Hz ~ 500Hz
Pickup Voltage10Vac
Accuracy0.2% Full Scale
Energy Accuracy
ActiveClass 0.2s (According to IEC 62053-22)
Class 0.2s (According to ANSI C12.20)
ReactiveClass 2 (According to IEC 62053-23)
Harmonic Resolution
 63rd Harmonic (50Hz or 60Hz type)
15th Harmonic (400Hz type)

 

STANDARD COMPLIANCE
Measurement StandardIEC 62053-22; ANSI C12.20
Environmental StandardIEC 60068-2
Safety StandardIEC 61010-1, UL 61010-1, IEC 61557-12
EMC StandardIEC 61000-4/-2-3-4-5-6-8-11, CISPR 22,
IEC 61000-3-2, IEC 61000-6-2/4
Outlines StandardDIN 43700, ANSI C39.1

 

CONTROL POWER
UniversalAC or DC
AC/DC Control Power
Operating Range100~415Vac, 50/60Hz; 100~300Vdc
Burden5W
Frequency50/60Hz
Withstand3250Vac, 50/60Hz for 1 minute
Installation Category III (Distribution)

 

OPERATING ENVIRONMENT
Operation Temperature- 25°C to 70°C
Storage Temperature- 40°C to 85°C
Relative Humidity5% to 95% Non-Condensing

 

Write Your Own Review
Only registered users can write reviews. Please Sign in or create an account
  • • Tenant Sub Metering
  • • Data Center Monitoring
  • • Building Automation
  • • Industrial Facility Metering
  • • Commercial Building Metering