The Isolation Transmitter IsoPAQ-131P is used for isolation and conversion of 0-20 mA, 4-20 mA and 0-10 V unipolar signals.
For applications where normally one signal combination only is used, IsoPAQ-131P offers a cost-effective alternative. The high reliability and the Protective Separation are further features, which ensure a safe system operation.
COMPACT LINE is a line of very compact and cost-optimized Isolators, Transmitter Repeaters and Isolating Transmitters within the IsoPAQ family. The small dimensions - only 60 mm deep and 11.2 mm wide – and the favorable pricing allow for space saving and economic installations.
Specifications
Input
Input signal
0-20 mA
4-20 mA
0-10 V
Factory set as ordered
Input resistance
Current input Voltage input
5 Ω 1 MΩ
Overload
Current input Voltage input
≤ 200 mA ≤ 250 V
Output
Output signal
0-20 mA
4-20 mA
0-10 V
Factory set as ordered
Load
Current output Voltage output
≤ 500 Ω ≥ 2kΩ
Ripple
< 0.2 % of end value, ~ 100 kHz
General data
Transmission error
± 0.2 % of end value
Temperature coefficient 1)
± 0.02 %/K of end value
Response time
< 5 ms
Test voltage
2.5 kV, 50 Hz
Between all circuits
Working voltage 2) (Basic Insulation)
600 VAC/DC for overvoltage category II and pollution degree 2 acc. to EN 61010 part 1 between all circuits.
Protection against electrical shock 2)
Protective separation acc. to EN 61140 by reinforced insulation acc. to EN 61010 part 1 up to 300 VAC/DC for overvoltage category II and pollution degree 2 between all circuits.
Ambient temperature
Operation Transport and storage
0 to +55 °C (32 to +131 °F) -25 to +80 °C (-13 to +176 °F)
Power supply
24 VAC/DC, ± 15 %
AC 48 to 62 Hz, approx. 2 VA DC approx. 0.7 W
EMC 3)
EN 61326-1
Construction
11.2 mm (0.44 “) housing, protection class: IP20
Connection
≤ 2.5 mm2, AWG 14
Weight
Approx. 50 g
1) Average TC in specified operating temperature range 2) As far as relevant the standards and rules mentioned above are considered by development and production of our devices. In addition relevant assembly rules are to be considered by installation of our devices in other equipments. For applications with high working voltages, take measures to prevent accidental contact and make sure that there is sufficient distance or insulation between adjacent situated devices. 3) Minor deviations possible during interference