INOR IsoPAQ-131P Basic Isolation Transmitter

SKU
70ISC131
Manufacturer:
Inor Transmitter
Inor Transmitter

Key Features:

  • 3-port isolation
  • Protection against erroneous measurements due to parasitic voltages or ground loops
  • Fixed ranges
  • Ready to use without any settings
  • Universal power supply for 24 VAC/DC
  • Increased flexibility in industrial applications
  • Compact DIN-rail mounting
  • 11.2 mm (0.44”) housing combined with very low self heating allows for high density mounting. With a depth of only 60 mm, compact standard boxes can be used
  • Protective Separation
  • The design and high isolation level (2.5 kV) provides protection for service personnel and downstream devices against impermissibly high voltage
  • Excellent reliability
  • Low self heating thanks to high-efficiency power supply provides long-term reliability and stability
Product Options:
$250.00

Secured and trusted checkout with

The Isolation Transmitter IsoPAQ-131P is used for isolation and conversion of 0-20 mA, 4-20 mA and 0-10 V unipolar signals.

For applications where normally one signal combination only is used, IsoPAQ-131P offers a cost-effective alternative.
The high reliability and the Protective Separation are further features, which ensure a safe system operation.

COMPACT LINE is a line of very compact and cost-optimized Isolators, Transmitter Repeaters and Isolating Transmitters within the IsoPAQ family.  The small dimensions - only 60 mm deep and 11.2 mm wide – and the favorable pricing allow for space saving and economic installations.

Input
Input signal0-20 mA4-20 mA0-10 VFactory set as ordered
Input resistanceCurrent input
Voltage input
5 Ω
1 MΩ
OverloadCurrent input
Voltage input
≤ 200 mA
≤ 250 V
Output
Output signal0-20 mA4-20 mA0-10 VFactory set as ordered
LoadCurrent output
Voltage output
≤ 500 Ω
≥ 2kΩ
Ripple< 0.2 % of end value, ~ 100 kHz
General data
Transmission error± 0.2 % of end value
Temperature coefficient 1)± 0.02 %/K of end value
Response time< 5 ms
Test voltage2.5 kV, 50 HzBetween all circuits
Working voltage 2) (Basic Insulation)600 VAC/DC for overvoltage category II and pollution degree 2 acc. to EN 61010 part 1 between all circuits.
Protection against electrical
shock 2)
Protective separation acc. to EN 61140 by reinforced insulation acc. to EN 61010 part 1 up to 300 VAC/DC for overvoltage category II and pollution degree 2 between all circuits.
Ambient temperatureOperation
Transport and storage
0 to +55 °C (32 to +131 °F)
-25 to +80 °C (-13 to +176 °F)
Power supply24 VAC/DC, ± 15 %AC 48 to 62 Hz, approx. 2 VA
DC approx. 0.7 W
EMC 3)EN 61326-1
Construction11.2 mm (0.44 “) housing, protection class: IP20
Connection≤ 2.5 mm2, AWG 14
WeightApprox. 50 g

 

1) Average TC in specified operating temperature range
2) As far as relevant the standards and rules mentioned above are considered by development and production of our devices. In addition relevant assembly rules are to be considered by installation of our devices in other equipments. For applications with high working voltages, take measures to prevent accidental contact and make sure that there is sufficient distance or insulation between adjacent situated devices.
3) Minor deviations possible during interference

Write Your Own Review