Vaisala HMW112 Humidity and Temperature Transmitter for Wall Mounting in HVAC Applications

SKU
HMW112
Manufacturer:
Vaisala
Vaisala

Key Features:

  • Accurate humidity and temperature transmitters for measurements in HVAC applications
  • Outdoor transmitter with professional-grade radiation shield
  • Proven HUMICAP 180R sensor for superior long-term stability
  • ±2 %RH accuracy
  • 3-point NIST traceable calibration (certificate included)
  • On-site calibration with HM70 Hand-Held Meter or PC connection
  • Current output (4 … 20 mA)
  • Default output parameters are relative humidity and temperature. Dew point temperature, wet bulb temperature, and enthalpy outputs selectable with a PC connection.
Product Options:
$306.00

Secured and trusted checkout with

Essential for HVAC applications where water is present, Vaisala has introduced their HMW112 Wall Mounted Analog Humidity and Temperature Transmitter. The HMW112 has an IP65 certified enclosure, safeguarding the sensor and electronics from possible water splashes.

The HMW112’s HUMICAP 180R sensor has excellent long-term stability, thus reducing maintenance needs during the lifetime of the transmitter. More still, users can field-calibrate the transmitter with an HM70 Hand-Held Humidity and Temperature Meter or PC connection for utmost efficiency. With an RH accuracy of +/-2%RH, Vaisala’s HMW112 Humidity and Temperature Transmitter is outfitted for an array of requirements in HVAC applications.

Note - Analog outputs are preset at the factory to:
Channel 1: 4 ... 20 mA = 0 ... 100% RH
Channel 2: 4 ... 20 mA = -40 ... +60 °C (-40 ... +140 °F) T

Performance
RELATIVE HUMIDITY
Measurement range0 ... 100 %RH
Accuracy
   Temperature range+10 ... +30 °C (+50 ... +86 °F)
     0 ... 90 %RH±2 %RH
     90 ... 100 %RH±3 %RH
   Temperature range-20 ... +10 °C, +30 ... +60 °C
(-4 ... +50 °F, +86 ... +140 °F)
     0 … 90 %RH±3 %RH
     90 … 100 %RH±4 %RH
   Temperature range-40 ... -20 °C (-40 ... -4 °F)
     0 ... 100%RH±4 %RH
Stability in typical HVAC applications±0.5 %RH/year
Humidity sensorVaisala HUMICAP® 180R
TEMPERATURE
Measurement range-40 ... +60 °C (-40 ... +140 °F)
Accuracy
   At +20 °C (+68 °F)±0.2 °C (±0.36 °F)
Temperature dependence±0.01 °C/°C
Temperature sensorPt1000 RTD Class F0.1 IEC 60751
CALCULATED PARAMETERS
Measurement range for dew
point temperature and wet bulb
temperature


-40 ... +60 °C (-40 ... +140 °F)
Measurement range for
enthalpy

-40 ... 460 kJ/kg (-10 ... +190 BTU/lb)
Accuracy of the calculated parameters should be
calculated at the actual condition based on the RH
and temperature specification.
 
Accuracy at 20°C (68°F) and 80%RH: 
   Dew point±0.7 °C (1.2 °F)
   Wet bulb temperature±0.5 °C (0.9 °F)
   Enthalpy±1.6kJ/kg (0.7 BTU/lb)
Factory calibration uncertainty at 20 °C
(+68 °F)

±1.5%RH/±0.2 °C
 
Operating Environment (All Models)
Operating temperature range-40 ... +60 °C (-40 ... +140 °F)
Operating humidity range0 ... 100 %RH
Maximum wind/flow speed30 m/s
Storage temperature-40 ... +60 °C (-40 ... +140 °F)
Electromagnetic complianceEN61326-1, Industrial Environment
 
Mechanics
Max wire size1.5 mm2 (AWG 16)
Standard housing colorWhite (RAL9003)
Housing materialPC + 10%GF (UL-V0 approved)
 
Inputs and Outputs
Analog output4 ... 20 mA, loop powered
Loop resistance0 ... 600 Ω
Supply voltage20 ... 28VDC at 600 Ω load
10 ... 28VDC at 0 Ω load
Data input for RDP100 RemoteRS485
Panel DisplayVaisala proprietary protocol



Write Your Own Review
Only registered users can write reviews. Please Sign in or create an account