NK Technologies ASXP Series AC Current Operated Switches with Time Delay

SKU
ASXP
Manufacturer:
NK Technologies
NK Technologies

Key Features:

    Fixed Start-up/Delay Timer
  • Trip timer set to 2 seconds to eliminate nuisance alarms due to start-up inrush or temporary overcurrent conditions
    Choice of N.O./N.C. Electro-mechanical Relay Output
  • Contact rating of 10A@240VAC provides adequate switching capacity for use in most motor control systems
    Improved Ease of Installation and Use
  • Eliminates need for separate time delay relay Choice of 24VAC/DC or 120VAC supply models LED provides indication of trip point contact status Setpoint adjustable from 1-50A
    Industrial Grade Performance
  • 0.5% accuracy, precise time delay setpoint, constant hysteresis, linear response and low frequency capability
    Agency Approved
  • UL, CE approvals pending
Product Options:
$180.00

Secured and trusted checkout with

NK Technologies ASXP Series AC Current Operated Switches with Time Delay, SmartLED, 1 - 50 A Adjustable Setpoint Range

The 'ASXP' from NK Technologies is a powered version of our popular current switch with integral time delay series. A fixed two-second delay upon trip minimizes nuisance alarms during start-up and operation in motor or heater status applications.  For use with 24VAC/DC or 120VAC supplies, this high performance product offers OEM-caliber accuracy, precision tolerances, low hysteresis and low (non-sinusoidal) frequency operation. Available with status LED and solid-core enclosure as standard.

Power Supply24 VAC/DC or 120 VAC,
(±10%), 2 VA max.
OutputElectromechanical SPDT relay, auto reset
Output Rating1 A, up to 120 VAC
Trip Point Range• ASXP1: 1–20 A
• ASXP2: 20–50 A
• ASXP3: 50–80 A
Time Delay2.0 sec (fixed on startup)
0–15 sec (adjustable after startup)
Max. Inrush
Current
500 A (5 second duration)
Hysteresis5% (constant)
Isolation VoltageTested to 5 KVAC
Frequency Range40–100 Hz
Sensing Aperture0.75” (19.1 mm) dia.
CaseUL94 V0 Flammability Rated
Environmental-4 to 122°F (-20 to 50°C)
0–95% RH, non-condensing
ListingsDesigned to meet UL508 requirements
Write Your Own Review
Only registered users can write reviews. Please Sign in or create an account

Motor Protection

  • Serves as an electronic proof-of-operation; detects current draw changes in motors when they encounter problems such as pumps running dry or pending bearing failure. Non-intrusive, less expensive to install than differential pressure flow sensors or thermal switches. Much quicker response time than Class 10 overload relays
  • High Inrush or Temporary Overload Current

  • Start-up/delay timer provides 2 second delay to avoid nuisance tripping from high inrush or short overload conditions