'AS3' Series Current Operated Switches from NK Technologies provide the same dependable indication of status offered by the AS1, but with the added benefit of increased setpoint accuracy. A choice of three, jumper-selectable input ranges allows the AS3 to be tailored to an application, providing more precise control through improved setpoint resolution. Self-powering, isolated solid-state outputs, 1-6A, 6-40A and 40-200A input ranges and a choice of split- or solid-core enclosures are standard.
Power Supply | None—Self-powered | ||
Output | Isolated solid-state relay; shared common (CCDC) | ||
Output Rating | • 1.0 A @ 240 VAC (Standard AC Units) • 0.15 A @ 30 VDC (Standard DC & Multi-pole Units) • 15 A @ 120 VAC, 10 A @ 240 VAC (-15 Option) | ||
Off-state Leakage | • NOAC: <10 μA • NCAC: 2.5 mA • AADC: <10 μA | • NODC: <10 μA • NCDC: 1.4 mA • CCDC: 0.3 mA (NC Terminal) | |
Response Time | 40–120 ms | ||
Setpoint Range | • Solid-core: 1–6, 6–40 & 40–175 A • Split-core: 1.75–6, 6–40 & 40–200 A | ||
Hysteresis | Low: 0.15 A, Mid: 0.3 A, High: 0.9 A | ||
Overload | Range | 6 Sec | 1 Sec |
• 1–6 A • 6–40 A • 40–175 A | • 400 A • 500 A • 800 A | • 600 A • 800 A • 1200 A | |
Isolation Voltage | UL listed to 1270 VAC, tested to 5000 VAC | ||
Frequency Range | 6–100 Hz | ||
Sensing Aperture | • -FF Case: 0.55” (14 mm) dia. • -FT Case: 0.74” (19 mm) dia. • -SP Case: 0.85” (21.6 mm) sq. | ||
Case | UL94 V0 Flammability Rated | ||
Environmental | -4 to 122°F (-20 to 50°C) 0–95% RH, non-condensing | ||
Listings | UL 508 Industrial Control Equipment (USA & Canada)*, CE |
* UL listing for -FF and -SP models only.