We use cookies to make your experience better. To comply with the new e-Privacy directive, we need to ask for your consent to set the cookies. Learn more.
Megger’s DLRO10X 1006-600 Digital Low Resistance Ohmmeter offers all the benefits of their DLRO10 1006-598, plus several new efficient features.
In addition to the measurement modes of the DLRO10 1006-598, the DLRO10X 1006-600 has an Unidirectional Measurement Mode which applies a current in only one direction, inhibiting any standing emfs to be negated, speeding up the measurement process. Not only are the forward and reverse measurements shown, the DLRO10X 1006-600 presents the average of the two measurements on the vast backlit LCD display.
Users can manually select the test current with the ohmmeter’s menu system, controlled by a two-axis paddle. Likewise, users can download in real time or take advantage of the onboard storage for up to 700 sets of results.
No requirement for the additional features? Click here to view Megger’s DLRO10 1006-598 Digital Low Resistance Ohmmeter.
Measurement mode | DLRO 10: Manual, Auto, Continuous, Inductive DLRO 10X: Manual, Auto, Continuous, Inductive, Undirectional |
Measurement control | DLRO 10: Fully Automatic DLRO 10X: Fully Automatic/Manual |
Measurement speed | <3s for forward and reverse current and to display average |
Display Measurement | DLRO10: 4 1/2 digit seven segment LED DLRO10X: Large colour display |
Range and safety | DLRO10 LED indications |
Test method | Single cycle reversing d.c. ratiometric measurement - average result display. |
Test current accuracy | ±10% |
Test current stability | <10 ppm per second |
Lead resistance | Maximum 100 mΩ total for 10 A operation irrespective of battery condition. |
Voltmeter input impedance | >200 kΩ |
Noise rejection | Less than 1% ±20 digits additional error with 100 mV peak 50/60 Hz. on the potential leads. Warning will show if hum or noise exceeds this level. |
Data transfer | DLRO10X: Real Time or from storage via RS232 |
Data storage | DLRO10X: 700 tests |
Memo field | DLRO10X: Up to 200 characters per test via integral alphanumeric keypad |
Battery type | 5.2 lithium ion rechargeable |
Battery life | Typical 1300 x 10 A tests before recharge |
Battery charge time | Via external 90 V - 260 V 50/60 Hz charger from 12 to 15 V dc supply Standard: 2.5 hours to 90% capacity, 4 hours to fully charged Slow Charge: +10 °C to + 45 °C (50 °F to 113 °F) |
Operating temperature range and humidity | +5 °C to +45 °C (41 °F to 113 °F) at full accuracy -10 °C to +50 °C (14 °F to 122 °F) at reduced accuracy <90% RH @ 40 °C (104 °F) non-condensing |
Storage temperature range and humidity | -30 °C to +70 °C (50 °F to 113 °F) <90% RH @ 40 °C (104 °F) non-condensing |
Temperature co-efficient | <0.01% per °C, over range 5 °C to 40 °C (<0.0006% per °F from 41 °F to 104 °F) |
Maximum altitude | 2000m (6562 ft) to full safety specifications |
Safety | In accordance with IEC61010-1, CAT III 600 V - only when DH6 leads are used. |
EMC | IP65 case closed, IP54 battery operation In accordance with IEC61326-1 (Heavy industrial) |
Dimensions | 220 x 100 x 237 mm |
Weight | 2.6 kg including battery |
* The accuracy stated assumes forward and reverse measurements. Inductive mode or undirectional mode will introduce an undefined error if an external EMF is present. |
- • Resistive Components Quality Control
- • Switch and Contact Breaker Resistance
- • Transformer and Motor Winding Resistance
- • Busbar and Cable Joints
- • Metal Alloys, Welds and Fuse Resistance
- • Rails and Pipe Bonds
- • Static Control Circuits
- • Integrity of Welded Joints
- • Inter-Cell Connections on Battery Systems
- • Graphite Electrodes
- • Aircraft Frame Bonds