We use cookies to make your experience better. To comply with the new e-Privacy directive, we need to ask for your consent to set the cookies. Learn more.
Megger’s MIT410/2 1004-735 Insulation Tester offers all the capabilities of the MIT400/2 1006-719, with serval added features and functions.
The MIT410/2 1004-735 provides test voltages of 50V, 100V, 250V, 500V and 1000V and functions for Polarization Index (PI) and Dielectric Absorption Ratio (DAR). Likewise, the tester can perform frequency measurements from 15 to 400 Hz. The MIT410/2 1004-735 is outfitted with Pass/Fail on limit alarms and supplied with a switched probe for a total value.
All quoted accuracies are at +20 °C. | |||
Insulation: | |||
Test voltage | |||
Nominal: MIT400/2 | 250 V, 500 V, 1000 V | ||
MIT410/2, 420/2, 430/2 | 50 V, 100 V, 250 V, 500 V, 1000 V | ||
Insulation accuracy | |||
50 Volts. | 10 GΩ | ± 2% | ± 2 digits ± 4.0% per GΩ |
100 Volts. | 20 GΩ | ± 2% | ± 2 digits ± 2.0% per GΩ |
250 Volts. | 50 GΩ | ± 2% | ± 2 digits ± 0.8% per GΩ |
500 Volts. | 100 GΩ | ± 2% | ± 2 digits ± 0.4% per GΩ |
1000 Volts | 200 GΩ | ± 2% | ± 2 digits ± 0.2% per GΩ |
Service Error: BS EN 61557-2 (2007). | |||
50V, ± 2.0% ± 2d, 100 kΩ - 900 kΩ ± 10.5% | |||
100V, ± 2.0% ± 2d, 100 kΩ - 900 kΩ ± 10.3% | |||
250V, ± 2.0% ± 2d, 100 kΩ - 900 kΩ ± 10.3% | |||
500V, ± 2.0% ± 2d, 100 kΩ - 900 kΩ ± 10.3% | |||
1000V, ± 2.0% ± 2d, 100 kΩ - 900 kΩ ± 11.5% | |||
Display range | Analogue: 1 GΩ full scale | ||
Resolution | 0.1 kΩ | ||
Short circuit/charge current | 2 mA +0% -50% to EN 61557-2 (2007) | ||
Open circuit voltage insulation | -0% +2% ± 2V | ||
Test current | 1 mA at min. pass value of insulation to a maximum of 2 mA max. | ||
Leakage (not MIT400/2) | 10% ±3 digits | ||
Voltage | 3% ±3 digits ±0.5% of rated voltage | ||
Timer control (not MIT400/2) | 60 second countdown timer | ||
Note | Above specifications only apply when high quality silicone leads are being used. | ||
Continuity: | |||
Continuity measurement | 0.01 Ω to 1000 kΩ | ||
Continuity accuracy | ± 3% ± 2 digits (0 to 100 Ω ) ±5% ±2 digits (100 to 500kΩ) (500kΩ to 1MΩ unspecified) Service Error: BS EN 61557-4 (2007) - ± 2.0%, 0.1 Ω - 2 Ω ± 6.8% | ||
Open circuit voltage | 5 V ± 1 V | ||
Test current | 200 mA (–0 mA +20 mA) (0.01 Ω to 4 Ω) | ||
Polarity (not MIT400/2) | Single polarity (Default) / Dual polarity (configurable on setup). | ||
Lead resistance | Null up to 9.00 Ω | ||
Voltage: | |||
Voltage range | AC: 10 mV to 600 V TRMS sinusoidal (15 Hz to 400 Hz) DC: 0 to 600 V | ||
Volt range accuracy | AC: ±2% ±1 digit DC: ±2% ±2 digit Service Error: BS EN 61557-1 (2007) - ± 2.0% ± 2d, 0 V – 300 V AC/DC ± 5.1% | ||
Waveform | Unspecified range: 0 – 10 mV (15 to 400 Hz) For non-sinusoidal waveforms additional specifications apply Non-sinusoidal waveforms: ±3% ± 2 digits >100 mV to 600 V TRMS ±8% ± 2 digits 10 mV to 100 mV TRMS | ||
Frequency: (not MIT400/2) | |||
Frequency measurement range | 15 Hz - 400 Hz | ||
Frequency measurement accuracy | ±0.5% ± 1digit (100 Hz to 400 Hz unspecified) | ||
Capacitance measurement: | MIT420/2, MIT430/2 | ||
MIT420/2, MIT430/2 Capacitance measurement | 1 nF to 10 μF | ||
Capacitance measurement accuracy | ± 5.0% ± 2 digits (0.1 nF – 1 nF unspecified) | ||
Storage: | |||
Result storage (MIT420/2 and MIT430/2): | |||
Storage capacity | >1000 test results | ||
Data download (MIT430/2 only) | Bluetooth® wireless Bluetooth® Class II | ||
Range | up to 10 m | ||
Power supply | 6 x 1.5 V cells type IEC LR6 (AA, MN1500, HP7, AM3 R6HP) Alkaline 6 x 1.2 V NiMH rechargeable cells may be used | ||
Battery life | 3000 insulation tests with duty cycle of 5 sec ON /55 sec OFF @ 1000 V into 1 MΩ | ||
Charger (Optional): | 12-15 V dc (accessory interface) | ||
Dimensions | Instrument 228 mm x 108 mm x 63 mm (9.00 in x 4.25 in x 2.32 in) | ||
Weight | 600 g (MIT400/2), (1.32 lb) | ||
Weight (instrument and case) | 1.75 kg (3.86 lb) | ||
Fuse | Use only 1 x 500 mA (FF) 1000 V 32 x 6 mm ceramic fuse of high breaking capacity HBC 30 kA minimum. Glass fuses MUST NOT be fitted. | ||
Safety protection | The instruments meet EN 61010-1 (1995) to 600 V phase to earth, Category IV. Refer to safety warnings supplied. | ||
EMC | In accordance with IEC 61326 including amendment No.1 | ||
Temperature co-efficient | <0,1% per °C up to 1 GΩ <0.1% per °C per GΩ above 1 GΩ | ||
Environmental: | |||
Operating temperature range and humidity | -10 to +55 °C 90% RH at 40 °C max. | ||
Storage temperature range | -25 to +70 °C | ||
Calibration temperature | +20 °C | ||
Maximum altitude | 2000 m | ||
IP rating | IP 54 | ||
The Bluetooth® word mark and logos are registered trademarks owned by Bluetooth SIG, Inc and is used under licence. |
Write Your Own Review
- • Battery Powered Traction and Lifting Equipment
- • Commercial Avionics
- • Cable Testing
- • Military Land, Marine and Air Communications
- • Component Testing
- • Manufacturing/Production Line Goods
- • Electrostatic Measurement
- • Motoring Testing
- • ESD
- • Panel Building
Products In This Series