We use cookies to make your experience better. To comply with the new e-Privacy directive, we need to ask for your consent to set the cookies. Learn more.
Offering all the features and functionalities of the DET3TD, Megger’s DET3TC 3-Terminal Ground Resistance Tester has the added capability for ART (Attached Rod Technique) Testing.
Click here to view Megger’s DET3TD 3-Terminal Ground Resistance Tester.
Resistance range: | 0.01 to 2000 Ω autoranging |
Resistance accuracy: | |
2P measurements | 2% ±3 digits |
3P measurements | 2% ±3 digits |
ART measurements | 5% ±3 digits |
Maximum probe resistance | |
Rp limit: | 100kΩ (50V output voltage) |
Rc limit: | 100kΩ (50V output voltage) |
Limits reduced to 50kΩ for 25V output voltage Limits reduced to 5kΩ for 0.01 Ω resolution on 18 Ω range | |
Earth voltage range: | 0 – 100 V |
Earth voltage accuracy: | 2% ±2 V |
2- and 3-wire test: | Yes |
ART (Attached Rod Technique): | DET3TC |
Ground current range (with current measuring clamp): | 0.5 mA to 19.9 A |
Ground current accuracy: | 5% ±3 digits |
Display: | LCD |
Test frequency: | 128 Hz |
Test voltage: | 25 V or 50 V, user selectable (factory setting 50 V) |
Test current: | 450 mA or 4.5 mA |
Noise rejection: | 40V pk to pk |
Noise check: | Automatic |
C spike check: | Automatic |
Battery type: | 8 1.5 V AA cells |
Battery life: | 3 hours, 700 consecutive tests |
Safety: | EN61010-1 CAT IV 100 V |
Terminals: | 4 mm plug type (test leads) |
Ingress protection: | IP54 |
EMC: | Meets the requirements of EN61326-1:1998 for use in heavy industrial areas |
Dimensions: | 8 x 5.7 x 3.2 in. (203 x 148 x 78 mm) |
Weight: | 2.2 lb (1 kg) |
Operating temperature range: | -5º to +131º F (-15º to +55º C) |
Storage temperature range: | -40º to +158º F (-40º to +70º C) |
Humidity: | 95% RH non-condensing at 104º F (40º C) |