INOR APAQ-H Analog Adjustable 2-Wire Transmitters - DISCONTINUED

SKU
70APH
Manufacturer:
Inor Transmitter
Inor Transmitter

Key Features:

This Product is DISCONTINUED
Please see the INOR APAQ C130 as a Recommended Replacements

  • Rangeable with solder pads and potentiometers
  • Temperature linear output for Pt100 (APAQ-HRF/-HRFX)
  • mV linear output for T/C (APAQ-HCF/-HCFX)
  • Consistent sensor break function
  • Easy wiring, large center hole
  • Moulded electronics for high protection

Secured and trusted checkout with

APAQ-H is a family of multirange 2-wire temperature transmitters for Pt100 or Thermocouple input.

Designed for highest reliability and excellent industrial performance. The ”low profile” housing is extremely durable and facilitates easy connections and adjustments.

 

Configuration

  • No PC Programmable
  • Bridging Solder Pads
  •                          

    Specifications : APAQ-HRF/-HRFX

    Input
    Pt100 (α = 0.00385), 3-wire connectionAdjustable to specific ranges within:
    -50 to +550 °C / -60 to +1120 °F
    Sensor current~1.1 mA
    Max. sensor wire resistance15 Ω / wire
    Monitoring
    Sensor break detection, selectableUpscale ~25 mA, downscale ~3 mA
    Adjustments
    Zero-50 to +50 °C / -60 to +120 °F
    Span, selectable50 to 500 °C / 100 to 1000 °F
    Span, fine adjustment±10 % (± 5% for 600 / 800 / 1000 °F)
    Output
    Current4 - 20 mA
    LinearityTemperature linear
    Current limitation~ 25 mA
    Permissible loadAPAQ-HRF700 Ω @ 24 VDC, 25 mA
     APAQ-HRFX620 Ω @ 24 VDC, 25 mA
    Temperature
    Ambient, storage-40 to +100 °C / -40 to +212°F
    Ambient, operatingAPAQ-HRF-40 to +85 °C / -40 to +185 °F
     APAQ-HRFXATEX:T4 /+85 °C, T5 /+55 °C, T6 /+40 °C; FM: T4/+80 °C
    General data
    Response time 10-90%≤ 0.2 s
    Humidity (non-condensing)0 to 95 %RH
    Intrinsic safetyAPAQ-HRFXATEX: II 1 G EEx ia IIB T4, T5, T6
    FM: Class I, Div.1, Group A-D
    Power supply, polarity protected
    Supply voltageAPAQ-HRF6.5 to 32 VDC
     APAQ-HRFX8.5 to 30 VDC
    Permissible ripple4 Vp-p @ 50/60 Hz
    Accuracy
    Linearity±0.1 % of span
    Calibration±0.1 % of span
    Temperature influence±0.6 % of span/25 °C, ±0.7 % of span/50 °F
    Sensor wire influence±0.005 °C/Ω / ±0.009 °F/Ω 1)
    RFI influence,0.15-1000MHz, 10 V or V/m±0.2 % of span (typical)
    Supply voltage influence±0.02 % of span/V
    Supply ripple influence, 50/60 Hz, 4 Vp-p±0.05 % of span
    Long term stability±0.1 % of span/year
    Housing
    Material / Flammability(UL)Zinc alloy + ABS / V0
    MountingDIN B-head or larger
    Connection, single/stranded wires≤2.5 mm2, AWG 14
    Weight40 g
    Protection, housing with cover/terminalsIP 20 / IP 10

    1) Per wire, with equal resistance

     

    Specifications : APAQ-HCF/-HCFX

    Input
    ThermocouplesSelectable, type J, L, T, K and N with
    ranges within -5 to +55 mV
    Input impedance>5 MΩ
    Max. sensor wire resistance500 Ω (total loop)
    Monitoring
    Sensor break detection, selectableUpscale ~25 mA, downscale ~3 mA
    Adjustments
    Zero±10 % of span
    Span, selectable10 to 50 mV
    Span, fine adjustment±10 %
    Output
    Current4 - 20 mA
    LinearityVoltage linear
    Current limitation~ 25 mA
    Permissible loadAPAQ-HCF700 Ω @ 24 VDC, 25 mA
     APAQ-HCFX620 Ω @ 24 VDC, 25 mA
    Temperature
    Ambient, storage-40 to +100 °C / -40 to +212°F
    Ambient, operatingAPAQ-HCF-40 to +85 °C / -40 to +185 °F
     APAQ-HCFXATEX:T4 /+85 °C, T5 /+55 °C, T6 /+40 °C; FM: T4/+80 °C
    General data
    Response time 10-90%≤ 0.2 s
    Humidity (non-condensing)0 to 95 %RH
    Intrinsic safetyAPAQ-HCFXATEX: II 1 G Ex ia IIB T4, T5, T6
    FM: Class I, Div.1, Group A-D
    Power supply, polarity protected
    Supply voltageAPAQ-HCF6.5 to 32 VDC
     APAQ-HCFX8.5 to 30 VDC
    Permissible ripple4 Vp-p @ 50/60 Hz
    Accuracy
    Linearity (mA output to mV input)±0.1 % of mV span
    Calibration±0.1 % of span
    Cold Junction Compensation (CJC)±1.0 °C /±1.8 °F
    Temperature influence±0.6 % of span/25 °C, ±0.7 % of span/50 °F
    Temperature influence CJC±1.25 °C/25 °C, ±2.5 °F/50 °F 1)
    Sensor wire influence0.4 μV/Ω
    RFI influence,0.15-1000MHz, 10 V or V/m±0.2 % of span (typical)
    Supply voltage influence±0.02 % of span/V
    Supply ripple influence, 50/60 Hz, 4 Vp-p±0.05 % of span
    Long term stability±0.1 % of span/year
    Housing
    Material / Flammability(UL)Zinc alloy + ABS / V0
    MountingDIN B-head or larger
    Connection, single/stranded wires≤2.5 mm2, AWG 14
    Weight40 g
    Protection, housing with cover/terminalsIP 20 / IP 10

     1) ±2.5 °C/25 °C, ±5.0 °F/50 °F for type T

    Write Your Own Review
    Only registered users can write reviews. Please Sign in or create an account