We use cookies to make your experience better. To comply with the new e-Privacy directive, we need to ask for your consent to set the cookies. Learn more.
Don’t break the loop on 4-20 mA signal measurements and save time.
Do these troubleshooting time wasters sound familiar?
The Fluke 772 can eliminate many of the above time wasters. Use the Fluke 772 to source and simulate 4-20mA loops signals as well as measuring loop signals without interupting your process.
How the Fluke 772 makes like easier:
Milliamp Clamp Features | Application | How it saves Time & Money |
Measure mA signals for PLC and control system analog I/O without breaking the loop | Measures low level DC current | Correlate process indication with real physical value |
Measure output signals from transmitters without breaking the loop | Maintain and troubleshoot process and automation equipment without breaking the loop | No disruption to the process |
Detachable clamp with extention cable | Measurements in tight locations | Enables measurements in difficult situations |
Source, simulate, and measure mA signals in circuit (break the loop) | Confirm non-contact measurement. Have the next tool in hand for troubleshooting (source simulate) | Eliminates the need to return to the shop to get a loop calibrator for troubleshooting after finding a bad signal with non-contact measurement |
Loop power supply | Power a transmitter | Substitute testing of the installed 24V loop power supply. Power a transmitter and measure its mA output for troubleshooting |
Dual backlit display with both mA measurement and percent of 4 to 20 mA span | Clear measurement presentation | Allows quick measurement evaluation |
Measurement Spotlight | Illuminates hard to see wires in dark enclosures | Measurement process is easier and quicker |
Measure up to 99.9 mA range non-contact | Wide range of measurements | Measures 10 to 50 mA signals in older control systems |
Automatic power off | After 15 minutes and 2 minute automatic off for backlight and spotlight | Saves battery life |
Fluke 772 Environmental Specifications:
Diameter of measurable conductor | 0.177" or 4.5 mm max |
Operating Temperature | -10 to 50 °C |
Storage Temperature | -25 to 60 °C |
Operating Humidity | <90% @ <30°C, <75% @ 30 to 55°C |
Operating Altitude | 0 to 2000m |
IP Rating | IP 40 |
Size | 44 x 70 x 246 mm (2 7/8 x 5 3/4 x 11 5/8 in) |
Weight | 410 g (14.4 oz) |
Vibration | Random 2 g, 5 to 500 Hz |
Shock | 1 meter drop test (except the jaw) |
EMI/RFI | Meets EN61326-1 Note: For current measurement w/JAW, add 1 mA to specification for EMC field strengths of 1V/m up to 3V/m. |
Temperature Coefficient | 0.01% °C |
Power, Battery Life | (4) AA 1.5V Alkaline, IEC LR6, 12 hours in mA source into 500 ohms |
Warranty | Three years for electronics One year for cable & clamp assembly |
Fluke 772 Functional Specifications:
mA Measurement (Measured by clamp) | Resolution and Range: 0 to 20.99 mA Accuracy: 0.2% + 2 counts Resolution and Range: 21.0 mA to 100.0 mA Accuracy: 1% + 5 counts |
mA Measurement (Measured in series with test jacks) | Resolution and Range: 0 to 24.00 mA Accuracy: 0.2% + 2 counts |
mA Source (Maximum mA Drive: 24 mA into 1,000 ohms) | Resolution and Range: 0 to 24.00 mA Accuracy: 0.2% + 2 counts |
mA Simulate (Maximum voltage 50 V dc) | Resolution and Range: 0 to 24.00 mA Accuracy: 0.2% + 2 counts |
|
Fluke 772 Includes:
|
Manuals