We use cookies to make your experience better. To comply with the new e-Privacy directive, we need to ask for your consent to set the cookies. Learn more.
The AEMC Model 8333 power analyzer is simple to use and it allows technicians to perform diagnostics and power quality work on single-phase or three-phase systems. The Model 8333 has 2 GB of memory that allows users to store up to 12 screen shots, up to 51 captured transients that contain 4 cycles for each active input, and 4,000 alarm events from up to 10 different parameters.
Available Models:
Model 8333 [AEMC Part No. 2136.10] PowerPad® III Model 8333 (No Probes)
Model 8333 [AEMC Part No. 2136.11] PowerPad® III Model 8333 w/3 193-24-BK (6500 Amp) AmpFlex Current Sensors
Model 8333 [AEMC Part No. 2136.12] PowerPad® III Model 8333 w/3 MN193-BK (100/5 Amp) Current Probes
MODEL | 8333 |
Input Terminals | 4 voltage / 3 current |
Inputs | 3 voltage / 3 current |
Voltage (TRMS AC+DC) | Phase-to-Phase: 2000V; Phase-to-Neutral: 1000V |
Voltage Ratio | up to 500kV |
Current (TRMS AC+DC) | MN Clamp: 0.005A to 6A/2A or 0 to 240A SR Clamp: 3A to 1200Aac MR Clamp: 10 to 1000Aac/10 to 1400Adc SL261 Clamp: 100mA to 10A/1 to 100A AmpFlex® or MiniFlex® Clamps: 100mA to 10000Aac Current Ratio: 10mA to 60kA J93: 50 to 3500Aac, 50 to 5000Adc |
Frequency (Hz) | 40 to 70Hz |
Distribution Systems | 1P 2W, 1P 3W, 2P 2W, 2P 3W, 2P 4W, 3P 3W, 3P 4W, 3p 5W, Split-Phase 2W & 3W, 2 ½ Element & Aron meters |
Power Values | W, VA, var, VAD, PF, DPF, cos ϕ, tan ϕ |
Energy Values | Wh, varh, VAh, VADh |
Harmonics | 1st to 50th, Direction, Sequence; THD: 0 to 50, Phase |
Transients | up to 51 |
Flicker | Pst |
Unbalance | Yes |
Record Mode | Yes |
Trend Mode | Records up to 29 variables for several days to several years depending on selected storage rate |
Alarm Mode | 10 types; 4096 recorded; 2 sessions |
Waveform Mode | Calculated: AN (RMS, DC, CF, PK+/-) and FK |
Peak | Yes |
Phasor Display | Automatic |
Display | Color ¼ VGA TFT screen (320 x 240) diagonal 148mm |
Snapshots | 12 |
Sampling Frequency | 256 samples/cycle for trend recording |
Data Storage | 2GB card for trend + 4MB partitioned for snapshot, transients and alarms |
Other Measurements | kW, kvar, PF, DPF, kWh, kvarh, kVAh, Factor K, Flicker |
Electrical Safety | IEC 61010, 1000V CAT III / 600V CAT IV |
Protection | IP53 - non operating |
Languages | more than 26 |
Communication Interface | USB |
Battery Life | 10 hrs in non - Record Mode with display on; 25 hrs in Record Mode with display off |
Power Source | 9.6V NiMH rechargeable battery pack (included) External AC supply: 110/230Vac ±20% (50/60Hz) |
Dimensions / Weight | 9.8 x 7.8 x 2.6" (240 x 180 x 55mm) / 4.3 lbs (1.95kg) |
* Registration must take place within 30 days of purchase
- Verification of transmission and distribution systems
- In-plant troubleshooting of power panels and individual machinery power usages
- Monitor pad mount transformers and phase unbalances
- Determine harmonic problems
- Determine transformer K-Factor
- Measure energy usage (kVAh, VARh, kWh)