The new Fluke 1555 and redesigned Fluke 1550C insulation resistance testers, offer digital insulation testing up to 10kV, making them ideal for testing a wide range of high voltage equipment including switchgear, motors, generators and cables. Fluke insulation resistance testerscan now conduct the entire range of test voltages specified in IEEE 43-2000 with a best in class, 3 year warranty and CAT IV 600 V safety rating. With measurement storage and PC interface, the 1555 and 1550C are perfect tools for preventative or predictive maintenance programs designed to identify potential equipment failures before they occur.
Specifications
Insulation resistance measurement - Fluke 1550C and Fluke 1555
Test voltage (dc)
Range (dc)
Accuracy (± reading)
250 V
< 200 kΩ 200 kΩ to 5 GΩ 5 GΩ to 50 GΩ > 50 GΩ
unspecified 5 % 20 % unspecified
500 V
200 kΩ 200 kΩ to 10 GΩ 10 GΩ to 100 GΩ > 100 GΩ
unspecified 5 % 20 % unspecified
1000 V
< 200 kΩ 200 kΩ to 20 GΩ 20 GΩ to 200 GΩ > 200 GΩ
unspecified 5 % 20 % unspecified
2500 V
< 200 kΩ 200 kΩ to 50 GΩ 50 GΩ to 500 GΩ > 500 GΩ
unspecified 5 % 20 % unspecified
5000 V
< 200 kΩ 200 kΩ to 100 GΩ 100 GΩ to 1 TΩ > 1 TΩ
unspecified 5 % 20 % unspecified
10000 V (Model 1555 only)
< 200 kΩ 200 kΩ to 200 GΩ 10 GΩ to 2 TΩ > 2 TΩ
unspecified 5 % 20 % unspecified
Bar graph range
0 to 1 TΩ
Insulation test voltage accuracy
-0 %, +10 % at 1 mA load current
Induced ac mains current rejection
2 mA maximum
Charging rate for capacitive load
5 seconds per μF
Discharge rate for capacitive load
1.5 s/μF
Leakage current measurement
Range: 1 nA to 2 mA
Accuracy: ± (5 % + 2 nA)
Capacitance measurement
Range: 0.01 uF to 15.00 μF
Accuracy: ± (15 % rdg + 0.03 μF)
Timer
Range: 0 to 99 minutes
Resolution Accuracy: Setting: 1 minute Indication: 1 second
Live circuit warning
Warning Range: 30 V to 660 V ac/dc, 50/60 Hz
Voltage Accuracy: ± (15 % + 2 V)
General specifications
Display
75 mm x 105 mm
Power
12 V lead-acid rechargeable battery, Yuasa NP2.8-12
Charger Input (AC)
Charger Input (AC) 85 V to 250 V ac 50/60 HZ 20 VA
This Class II (double insulated) instrument is supplied with a Class 1 (grounded) power cord. The protective earth terminal (ground pin) is not connected internally. The extra pin is for added plug retention only.
Dimensions
170 mm x 242 mm x 330 mm (6.7 in x 9.5 in x 13 in)
Weight
3.6 kg (7.94 lb)
Temperature (operating)
-20 ºC to 50 ºC (-4 ºF to 122 ºF)
Temperature (storage)
-20 ºC to 65 ºC (-4 ºF to 149 ºF)
Humidity
80 % to 31 ºC decreasing linearly to 50 % at 50 ºC
Altitude
2000 m
Enclosure sealing
IP40
Input overload protection
1000 V ac
Electromagnetic compatibility
EN 61326
Certifications
Safety compliance
CAT III 1000 V, CAT IV 600 V
Pollution degree
2
The tester’s accuracy is specified for one year after calibration at operating temperatures of 0 °C to 35 °C. For operating temperatures outside the range (-20 °C to 0 °C and 35 °C to 50 °C), add ± .25 % per °C, except on the 20 % bands add ± 1 % per °C.