Fluke’s PQ400 Electrical Measurement Window allows the connection of three phase measurement equipment to energized panels, eliminating the need to open the panel door, or wear supplemental personal protective equipment (PPE). The PQ400 provides access to crucial power quality and energy data, all while diminishing testing time and assisting in maintaining user safety.
The Fluke PQ400 is loaded with features functions and benefits:
• Decrease the possibility of arc-flash and electrocution, while improving the safety of employees
• Reduce maintenance costs and diminish downtime by making critical power quality and energy measurements without opening the panel door, enabling logging and monitoring at any time—without disrupting operations
• Lessen work permit requirements and processes by limiting the risks associated with taking measurements on open panels, saving time and effort
• Increase measurement efficiency and lessen the need for arc-flash PPE1, saving time, increasing efficiency and increasing operator comfort
Specifications
Voltage
Input
Number of inputs
5 (A/L1, B/L2, C/L3, N, and earth/ground)
Wire gauge
Solid/flexible: 0.25 mm² to 1.5 mm² (AWG 24 to AWG 16)
Voltage
Max. 1000 V
Fuse
2 A 1000 V 1.5 A²s, 10 kA IR (A/L1, B/L2, C/L3, N)
Output
Connectors
5x 4 mm safety terminals, 3x red for A/L1, B/L2, C/L3, 1x black for N, 1x green for earth/ground
Load current
Max. 1 A rms
Current
Input/output
Connectors
5x 4-pin circular compatible with Fluke 354x FC, 173x, and 174x power and power quality loggers (these loggers can all be power from the measured voltage up to 500V)v
General specifications
Maximum voltage between any voltage terminal and earth ground
1000 V
Maximum voltage between any current terminal and earth ground
30 V
Safety
General
IEC 61010-1: pollution degree 2
Measurement
IEC 61010-2-030: CAT IV 600 V / CAT III 1000 V
Dimensions
Outside
148 mm x 187 mm x 23 mm (W x H x D) (148 mm x 370 mm x 19 mm with cover opened)
Inside
140 mm x 158 mm x Di (W x H x D) Di = 58 – thickness of panel door in mm
Supported electrical enclosures
Enclosure
UL 50/NEMA environmental type 1 (Type 12 when PQ400 cover is closed)
Panel thickness
Max. 3.5 mm (10 gauge)
Environment
Operating/storage temperature
-25 °C to 60 °C (-13 °F to 140 °F)
Humidity
10 % to 90 % in dependency of temperature according to IEC 60721-3-3 Class 3K6 (modified):-25 °C to 35 °C: 10 % to 90 %, 50°C: max. 35 %, 60°C: max. 23 %
Altitude
Operating
2,000 m (up to 4000 m derate to CAT II 1000 V, CAT III 600 V, CAT IV 300 V)
Storage
12,000 m
Ingress protection
Rating
IEC 60529: IP67 with cover closed, IP50 with cover opened and all connectors attached
Vibration
IEC 60068-2-6 , MIL-PRF28800F: Random vibration class 2
Weight
2.1 kg (4.6 lb)