Input Input: 4-20 mA Accuracy: ±0.02% of span ±1 count, Square root and programmable exponent: 10-100% FS Voltage Drop: Without Backlight: 1.5 V maximum, With backlight: 4.5 V maximum Equivalent Resistance: With backlight off: 75 Ω @ 20 mA, With backlight on: 225 Ω @ 20 mA Input Overload: Over current protection to 1 A maximum Temperature Drift: 25 PPM/°C from -40 to 75°C ambient Function: PV1: Linear, square root, or programmable exponent PV2: Linear or Round Horizontal Tank Low-Flow Cutoff: 0.0 to 999,999.9 HART Transparency: Analog input will not interfere with existing HART communications on the wired 4-20 mA signal Display Display: Dual-line LCD with backlight. Both lines 14-segment alphanumeric. Top: 0.7" (17.8 mm), Bottom: 0.4" (10.2 mm). Display may be programmed to turn red and flash a user-defined message on alarm condition. Backlight: Powered by 4-20 mA loop. Intensity varies with signal level PD6602 & PD6606: Top line: 5 digits (-9999 to 99999) or 5 characters (all capital & most lower case letters) Bottom line: 8 digits (-9,999,999 to 99,999,999; separated by commas) or 8 characters (all capital & most lower case letters) Bargraph: None PD6603 & PD6607: Top line: -99FT 11IN 15/16 to 999FT 11IN 15/16 Bottom line: 8 digits (-9,999,999 to 99,999,999; separated by commas) or 8 characters (all capital & most lower case letters) Bargraph: 20 segments, numeric percent indication at top PD6604 & PD6608: Top line: 5 digits (-9999 to 99999) or 5 characters (all capital & most lower case letters) Bottom line: 8 digits (-9,999,999 to 99,999,999; separated by commas) or 8 characters (all capital & most lower case letters) Bargraph: 20 segments, numeric percent indication at top Decimal Point & Commas: Top line: Up to four decimal places Bottom line: Up to seven decimal places and commas to indicate 1000s (ie 88,987,628) Dual-Scale Feature: The input can be displayed in different scales on the top and bottom lines. For instance, the top line could display the input in height and the bottom line could display that same input in volume. Alarm Indication: Red backlight, flashing display, alarm symbol (!). Symbols are not available on bargraph models. Alarm Message: On or Off; user programmable, 8 characters maximum. Displayed every 10 seconds for 1 second on bottom line. Display Update Rate: Ambient > -10°C: 1 update/second Ambient -20 C: 1 update/2 seconds From -20°C to -40°C the update rate slows down 1 second for every -2°C (e.g. at -24°C, 1 update/4 seconds). Overrange: Top: 99999; Bottom: 99,999,999 (flashing) Underrange: Top: -9999; Bottom: -9,999,999 (flashing) General Environmental: Operating temperature range: -40 to 75°C for safe area products -40 to 70°C for hazardous area products Storage temperature range: -40 to 85°C Relative humidity: 0 to 90% non-condensing. Printed circuit boards are conformally coated. Programming Method: Front panel & Free PC-based USB programming software Enclosure & Materials: Enclosure: 1/8 DIN, IP65, NEMA 4X front panel, high impact plastic, NORYL® polyphenylene ether & polystyrene blend (PPE PS) resin, UL 94V-0, Color: gray, Gasket: silicone rubber, Faceplate: LEXAN® polycarbonate (PC) film, Buttons: silicone rubber Noise Filter: Averages the input signal over a period of time between 1 and 16 seconds to dampen the effects of a noisy signal that causes a jumpy display. Recalibration: Recalibration is recommended at least every 12 months. Max/Min Display: Max/min readings reached by the process are stored until reset by the user or until power to the meter is turned off. Tare: Zeros out display Password: Programmable password restricts modification of programmed settings. Non-Volatile Memory: All programmed settings are stored in nonvolatile memory for a minimum of ten years if power is lost. Normal Mode Rejection: 64 dB at 50/60 Hz Connections: Removable screw terminals accept 12 to 22 AWG wire. DI Digital Input Contacts: 2.1 VDC on contact. Connect normally open contacts across DI+ and DI DI Digital Input Logic Levels: Logic High: 2.4 to 30 VDC (max) Logic Low: 0 to 0.9 VDC Tightening Torque: Screw terminal connectors: 4.5 lb-in (0.5 Nm) Mounting screws: 8.0 lb-in max. (0.9 Nm) Overall Dimensions: 4.68"x 2.45"x 3.79" (119 mm x 62 mm x 96 mm) (W x H x D) Weight: 8.7 oz (247g) with option board Warranty: 3 years parts and labor Common Open Collector & Relay (Alarm) Specifications High or Low Alarm: User programmable for high or low alarm Alarm Deadband: 0-100% FS, user programmable On & Off Time Delay: 0 to 9,999 seconds Fail-Safe Operation: Independent for each open collector and relay Alarm Operation: Automatic, Automatic with manual override, Latching (manual reset anytime), Latching with reset after cleared (manual reset only after alarm has cleared) Alarm Indication: Red backlight, flashing display, alarm symbol (!); (symbols not available on bargraph models) Alarm Message: On or Off; User programmable, 8 characters maximum. Displayed every 10 seconds for 1 second on bottom line Alarm Acknowledge: Front panel ACK button or external digital input resets output and screen indication Auto Initialization: When power is applied to the meter, open collectors and relays will reflect the state of the input to the meter Timer Output: One-shot or Continuous Off Time Delay: 1 sec to 99:59:59 (hrs:min:sec) On Time: 1 sec to 99:59:59 (hrs:min:sec) Stopwatch: Output turns on when started and off when stopped Open Collector Outputs Rating: Two NPN, Isolated open collector, 30 VDC @ 150 mA max Output Assignment: Pulse, Alarm, Timer, Stopwatch on/off, or Disable Pulse Output Source: PV (PV1, PV2) or Test Frequency Pulse Output Factor: 0.000001 to 999,999.9 Pulse Width: 0.5 ms @ 1 kHz; 500 ms @ 1 Hz; 50% duty cycle Pulse Output Frequency: 1,000 Hz maximum Quadrature Pulse Output: Available for Output 2 (90° behind Output 1) Alarm Output Source: Assign to PV (PV1, PV2) or Digital Input Solid State Relays Rating: Resistive Load: 250 VAC/DC @ 1 A Inductive Load: 75 VA @ 0.6 A, 250 VAC/DC max (Safe Area only) Noise Suppression: Metal oxide varistors across outputs Relay Assignment: Pump Alternation, Alarm, Timer, Stopwatch on/off, or Disable Alarm Output Source: Assign to PV (PV1, PV2) or Digital Input Pump Alternation: Relays will alternate with each pump cycle and alternation can be based on elapsed time. Pump alternation time can be programed for: 0 to 999:59 (hrs:min) Relay (Pump) Runtime: Meter will keep track of how long each relay (pump) has operated and display this information Relay (Pump) Cycles: Meter will keep track of how many times the relays (pumps) have cycled and display this information 4-20 mA Transmitter Output Accuracy: ±0.05% FS ±0.001mA Output Source: PV1, PV2, re-transmit; reverse scaling allowed Scaling Range: 1.00 to 23.0 mA Disable: High impedance state, less than 1 mA Calibration: Factory calibrated 4.00 to 20.00 mA Underrange: 1.0 mA, 3.5 mA, or 3.8 mA (If input < 3.5 mA), or Off; user selectable Overrange: 20.5 mA, 20.8 mA, or 23.0 mA (If input > 20.5 mA), or Off; user selectable Isolation: 500 V input-to-output Temperature Drift: 0.5 μA/°C max from -40 to 75°C ambient External Loop Power Supply: 7.0 VDC to 30.0 VDC maximum Output Loop Resistance: 10-750 Ω @ 24 VDC; 100-1100 Ω @ 30 VDC |