Measurement Characteristics | Input | Item | | Range | Rating Voltage | | 600 Vrms | Rating Current | | 20 Arms | Impedance(50/60Hz) | Voltage | 2.4 MΩ | Current | 5mA~200mA:500 mΩ | Current | 0.5A~20A:5 mΩ | Maximum Voltage | | 700 Vrms | Maximum Current | | 25 Arms | Maximum Common Mode Voltage | | 300 V | Low Pass Filter | Cutoff frequency | 500 Hz | Parameters | Item Measurement | | Symbol | Voltage | Vdc, Vrms, V+pk, V-pk | Current | Idc, Irms, I+pk, I-pk | Power | P, P+pk, P-pk, VA, Var | Crest Factor | CFV, CFI | Power Factor | PF | Frequency | VHz, IHz | Angle | Deg | Total Harmonic Distortion | THDV, THDI | Integration | Time, WP, WP+, WP-, q, q+, q- | Display Digits | | 5 digits | Frequency Bandwidth | | DC, 45Hz~6kHz | Average | | 1, 2, 4, 8, 16, 32, 64 | PT Rate | | 1 ~ 9999.999 | CT Rate | | 1 ~ 9999.999 | Display Mode | Standard | 8 measurement Item | Simple | 4 measurement Item | Voltage | Item | | Range | Range | CF=3 | 15V, 30V, 60V, 150V, 300V, 600V | CF=6 | 7.5V, 15V, 30V, 75V, 150V, 300V | Crest Factor | | 3 or 6 (selectable) | Accuracy | Effective Range | 1% ~ 105% of range | DC | ±(0.2% of reading+0.2% of range) | 45Hz ≦f ≦66Hz | ±(0.1% of reading+0.1% of range) | 66Hz < f ≦1kHz | ±(0.1% of reading+0.2% of range) | 1kHz < f ≦6kHz | ±3% of reading | Filter(ON) | Add 0.3% of reading@45Hz ~ 66Hz | Temperature Effect | 5-18゚C / 28-40゚C | Add ±0.03% of reading/゚C | Residual Noise | | 0.5% of range | Current | Item | | Range | Measurement | CF=3 | 5mA, 10mA, 20mA, 50mA, 100mA, 200mA, 1A, 2A, 5A, 10A, 20A | CF=6 | 2.5mA, 5mA, 10mA, 25mA, 50mA, 100mA, 0.5A, 1A, 2.5A, 5A, 10A | Crest Factor | | 3 or 6 (selectable) | Accuracy | Effective Range | 1% ~ 105% of range | DC | ±(0.2% of reading+0.2% of range) | 45Hz≦f ≦66Hz | ±(0.1% of reading+0.1% of range) | 66Hz < f ≦1kHz | ±(0.1% of reading+0.2% of range) | 1kHz < f ≦6kHz | ±3% of reading | Filter(ON) | Add 0.3% of reading@45Hz ~ 66Hz | Temperature Effect | 5-18゚C/28-40゚C | Add ±0.03% of reading/゚C | Residual Noise | | 0.5% of range | Power | Item | | Range | Measurement | Filter(ON) | 30.000 Hz~9.9999 kHz | Filter(OFF) | 30.000 Hz~499.99 Hz | Parameter | | Voltage, Current | Effective Range | | 10%~105% of voltage input | Accuracy | | ±0.06% of reading | Frequency | Item | | Range | Measurement | Filter(ON) | 30.000 Hz~9.9999 kHz | Filter(OFF) | 30.000 Hz~499.99 Hz | Parameter | | Voltage, Current | Effective Range | | 10%~105% of voltage input | Accuracy | | ±0.06% of reading | Integration | Item | | Range | Intergration | Accuracy | ±(voltage or current accuracy+0.1% of reading) | Time | Range | 0 hour 00 min ~ 9999 hour 59 min | Accuracy | ±0.01%±1second | | General Information | Display | 4” TFT LCD | Standard Interface | RS-232C, USB device, LAN | Power Source | AC 100~240 V, 50-60Hz | Power Consumption | Max. 25VA | Dimension & Weight | 270(W) x 110(H) x 350(D) mm, Aapprox. 2.9kg |
|