Model | | PSU | 6-200 | 12.5-120 | 20-76 | 40-38 | 60-25 | 100-15 | 150-10 | 300-5 | 400-3.8 | 600-2.6 |
Output ratings |
Rated output voltage (*1) | | V | 6 | 12.5 | 20 | 40 | 60 | 100 | 150 | 300 | 400 | 600 |
Rated output current (*2) | | A | 200 | 120 | 76 | 38 | 25 | 15 | 10 | 5 | 3.8 | 2.6 |
Rated output power | | W | 1200 | 1500 | 1520 | 1520 | 1500 | 1500 | 1500 | 1500 | 1520 | 1560 |
Ripple and noise(*5) |
CVp-p( 10 ~ 20MHz) | p-p (*6) | mV | 60 | 60 | 60 | 60 | 60 | 80 | 100 | 150 | 200 | 300 |
CVrms(5Hz ~ 1MHz) | r.m.s. (*7) | mV | 8 | 8 | 8 | 8 | 8 | 8 | 10 | 25 | 40 | 60 |
CCrms(5Hz ~ 1MHz) | r.m.s.(*12) | mA | 400 | 240 | 152 | 95 | 75 | 45 | 35 | 25 | 17 | 12 |
Load regulation |
Voltage(*4) | | mV | 2.6 | 3.25 | 4 | 6 | 8 | 12 | 17 | 32 | 42 | 62 |
Current(*11) | | mA | 45 | 29 | 20.2 | 12.6 | 10 | 8 | 7 | 6 | 5.76 | 5.52 |
Line regulation |
Voltage(*3) | | mV | 2.6 | 3.25 | 4 | 6 | 8 | 12 | 17 | 32 | 42 | 62 |
Current(*3) | | mA | 22 | 14 | 9.6 | 5.8 | 4.5 | 3.5 | 3 | 2.5 | 2.38 | 2.26 |
Analog Programming and Monitoring |
External voltage control output voltage | | | Accuracy and linearity: ±0.5% of rated output voltage. |
External voltage control output current | | | Accuracy and linearity: ±1% of rated output current. |
External resistor control output voltage | | | Accuracy and linearity: ±1% of rated output voltage. |
External resistor control output current | | | Accuracy and linearity: ±1.5% of rated output current. |
Output voltage monitor | | | Accuracy: ±1% |
Output current monitor | | | Accuracy: ±1% |
Shutdown control | | | Turns the output off with a LOW (0V to 0.5V) or short-circuit. |
Output on/off control | | | Possible logic selections: |
Turn the output on using a LOW (0V to 0.5V) or short-circuit, turn the output off using a HIGH (4.5V to 5V) or open-circuit. |
Turn the output on using a HIGH (4.5V to 5V) or open-circuit, turn the output off using a LOW (0V to 0.5V) or short-circuit |
Alarm clear control | | | Clear alarms with a LOW (0V to 0.5V) or short-circuit. |
CV/CC/ALM/PWR ON/OUT ON indicator | | | Photocoupler open collector output; Maximum voltage 30V, maximum sink current 8mA. |
Trigger out | | | Maximum low level output = 0.8V; minimum high level output = 2V; Maximum source current = 8mA. |
Trigger in | | | Maximum low level input voltage = 0.8V; minimum high level input votage = 2V, Maximum sink current = 8mA. |
Front Panel |
Display, 4 digits, Voltage accuracy | 0.1% + | mV | 12 | 25 | 40 | 80 | 120 | 200 | 300 | 600 | 800 | 1200 |
Current accuracy | 0.2% + | mA | 600 | 360 | 228 | 114 | 75 | 45 | 30 | 15 | 11.4 | 7.8 |
Indications | | | GREEN LED's: CV, CC, V, A, VSR, ISR, DLY, RMT, LAN, M1, M2, M3, RUN,OutputON |
| | | RED LED's: ALM, ERR |
Buttons | | | Lock/Local(Unlock), PROT(ALM_CLR), Function(M1), Test(M2), Set(M3), Shift, Output |
Knobs | | | Voltage, Current |
USB port | | | Type A USB connector |
Transient response time (*10) |
Transient response time | | ms | 1.5 | 1 | 1 | 1 | 1 | 1 | 2 | 2 | 2 | 2 |
Output response time |
Rise time (*8) | Rated load | ms | 80 | 80 | 80 | 80 | 80 | 150 | 150 | 150 | 200 | 250 |
| No load | ms | 80 | 80 | 80 | 80 | 80 | 150 | 150 | 150 | 200 | 250 |
Fall time(*9) | Rated load | ms | 10 | 50 | 50 | 80 | 80 | 150 | 150 | 150 | 200 | 250 |
| No load | ms | 500 | 700 | 800 | 1000 | 1100 | 1500 | 2000 | 2500 | 3000 | 4000 |
Programming and Measurements (RS-232/485, USB, LAN, GPIB) |
Output voltage programming accuracy | 0.05% + | mV | 3 | 6.25 | 10 | 20 | 30 | 50 | 75 | 150 | 200 | 300 |
Output current programming accuracy | 0.2% + | mA | 200 | 120 | 76 | 38 | 25 | 15 | 10 | 5 | 3.8 | 2.6 |
Output voltage programming resolution | | mV | 0.2 | 0.4 | 0.7 | 1.3 | 2 | 3.4 | 5.2 | 10.2 | 13.6 | 20.4 |
Output current programming resolution | | mA | 6 | 4 | 2.5 | 1.2 | 0.8 | 0.5 | 0.34 | 0.19 | 0.13 | 0.09 |
Output voltage measurement accuracy | 0.1% + | mV | 6 | 12.5 | 20 | 40 | 60 | 100 | 150 | 300 | 400 | 600 |
Output current measurement accuracy | 0.2% + | mA | 400 | 240 | 152 | 76 | 50 | 30 | 20 | 10 | 7.6 | 5.2 |
Output voltage measurement resolution | | mV | 0.2 | 0.4 | 0.7 | 1.3 | 2 | 3.4 | 5.2 | 10.2 | 13.6 | 20.4 |
Output current measurement resolution | | mA | 6 | 4 | 2.5 | 1.2 | 0.8 | 0.5 | 0.34 | 0.19 | 0.13 | 0.09 |
Temperature coefficience |
Voltage | | ppm/℃ | 100ppm/℃ after a 30 minute warm-up |
Current | | ppm/℃ | 100ppm/℃ after a 30 minute warm-up |
Remote sense compensation voltage(single wire) |
voltage | | V | 1 | 1 | 1 | 2 | 3 | 5 | 5 | 5 | 5 | 5 |
Protection Function |
Over voltage protection(OVP) | Setting range | V | 0.6 - 6.6 | 1.25 - 13.75 | 2 - 22 | 4 - 44 | 5 - 66 | 5 - 110 | 5 - 165 | 5 - 330 | 5 - 440 | 5 - 660 |
| Setting accuracy | mV | 60 | 125 | 200 | 400 | 600 | 1000 | 1500 | 3000 | 4000 | 6000 |
Over current protection(OCP) | Setting range | A | 5 - 220 | 5 - 132 | 5 - 83.6 | 3.8 - 41.8 | 2.5 - 27.5 | 1.5 - 16.5 | 1 - 11 | 0.5 - 5.5 | 0.38 - 4.18 | 0.26 - 2.86 |
| Setting accuracy | mA | 4000 | 2400 | 1520 | 760 | 500 | 300 | 200 | 100 | 76 | 52 |
Under voltage limit(UVL) | Setting range | | 0 - 6.3 | 0 - 13.12 | 0 - 21 | 0 - 42 | 0 - 63 | 0 - 105 | 0 - 157.5 | 0 - 315 | 0 - 420 | 0 - 630 |
Over temperature protection(OHP) | Operation | | Turn the output off. |
Incorrect sensing connection protection (SENSE) | Operation | | Turn the output off. |
Low AC input protection (AC-FAIL) | Operation | | Turn the output off. |
Shutdown (SD) | Operation | | Turn the output off. |
Power limit (POWER LIMIT) | Operation | | Over power limit. |
| Value (fixed) | | Approx. 105% of rated output power |
Interface Capabilities |
USB | | | TypeA: Host, TypeB: Slave, Speed: 1.1/2.0, USB Class: CDC(Communications Device Class) |
LAN | | | MAC Address, DNS IP Address, User Password, Gateway IP Address, Instrument IP Address, Subnet Mask |
RS-232 / RS-485 | | | Complies with the EIA232D / EIA485 Specifications |
GPIB (Factory Option) | | | SCPI - 1993, IEEE 488.2 compliant interface |
Isolated Analog Control Interface (Factory Option) |
Voltage Control | | | Using 0-5V or 0-10V signals for programming and measurement |
Current Control | | | Using 4-20mA current signals for programming and measurement |
Environmental Conditions |
Operating temperature | | | 0˚C to 50˚C |
Storage temperature | | | -25˚C to 70˚C |
Operating humidity | | | 20% to 85% RH; No condensation |
Storage humidity | | | 90% RH or less; No condensation |
Altitude | | | Maximum2000m |
Input Characteristics |
Nominal input rating | | | 100Vac to 240Vac, 50Hz to 60Hz, single phase |
Input voltage range | | | 85Vac ~ 265Vac |
Input frequency range | | | 47Hz ~ 63Hz |
Maximum input current | 100Vac / 200Vac | A | 21 / 11 |
Inrush current | | | Less than50A. |
Maximum input power | | VA | 2000 |
Power factor | 100Vac / 200Vac | | 0.99 / 0.98 |
Efficiency (*13) | 100Vac / 200Vac | % | 77 / 79 | 82 / 85 | 83 / 86 | 84 / 87 | 84 / 87 | 84 / 87 | 84 / 87 | 84 / 87 | 84 / 87 | 84 / 87 |
Hold-up time | | | 20ms or greater |
General |
Weight | main unit only | kg | Less than8.7kg |
Dimensions | (W×H×D) | mm^3 | 423×43.6×447.2 |
Cooling | | | Forced air cooling by internal fan. |
EMC | | | Complies with the European EMC directive 89/336/EEC for Class A test and measurement products. |
Safety | | | Complies with the European Low Voltage Directive 73/23/EEC and carries the CE-marking. |
Withstand voltage | | | AC to Chassis : 1500Vac / 1min |
AC to Output terminal : 3000Vac / 1min |
Vout≦150V |
Output terminal to Chassis : 1000Vdc / 1min |
150<Vout≦600 |
Output terminal to Chassis : 1500Vdc / 1min |
Insulation resistances | | | Chassis and output terminal; chassis and AC input; AC input and output terminal: 100MΩ or more (DC 1000V) |