Input: 4-20 mA @ 30 VDC maximum Display: 1.0" (25.4 mm) LCD, 3½ digits; 1999 Accuracy: ±0.1% FS ±1 count Approvals: FM Approved & CSA Certified as intrinsically safe with entity, for use in Class I, II, III, Division 1, Groups A, B, C, D, E, F, & G; T-code = T4; hazardous locations. Non-incendive for use in Class I, II, III, Division 2, Groups A, B, C, D, F, & G. Entity Parameters: Vmax= 30 V, Imax = 175 mA, Ci= 0 µF, Li = 0 µH, Pi = 1.3 W FM Approved: Intrinsically Safe, Class I Zone 0 Decimal Point: User selectable Calibration: Two-step; non-interacting zero and span Calibration Range: 4 mA input: -1000 to +1000; 20 mA input: between 20 and 2000 counts > 4 mA display Display Update Rate: 2.5/second Maximum Input Current: 30 mA Maximum Voltage Drop: 1 V @ 20 mA Operating Temperature: PD686: -40 to 85°C for Canadian installations -40 to 40°C. Storage Temperature: -40 to 85°C Relative Humidity: 0 to 90% non-condensing Enclosure: Impact-resistant glass filled polycarbonate body, color: gray; impact-resistant clear polycarbonate cover; NEMA 4X, IP67 Connections: Removable screw terminals accept 12 to 26 AWG Conduit Hole: One ½" conduit hole provided; refer to Ordering Information to specify conduit hole location; request models with rear conduit hole (-X) for panel mounting applications. Weight: 12 oz (340 g) Warranty: 2 years parts & labor