Avoid damaging connected appliances during insulation tests with Fluke’s 1664 FC Installation Tester. The 1664 FC uses Fluke’s own patented Insulation PreTest which prevents tests from being performed with appliances that are connected to the system during the testing process, reducing incidents of accidental damage.
The Fluke 1664 FC is part of Fluke’s family of wireless test tools. Now, data communication and analysis is easy and more efficient. Readings and data can be communicated to team members in the field from most smartphones. The Fluke Connect software is compatible with the iPhone models 4S and higher running iOS 8.0 or higher, iPad Air and iPad Mini (2nd generation) in an iPhone frame on iPad and iPod Touch (5th generation), HTC One and One M8 running Android 4.4.x or higher, LG G3 and Nexus 5 running Android 4.4.x or higher, Samsung Galaxy S4 running Android 4.3.x or higher, Samsung Galaxy S5 running Android 4.4.x or higher and works with now over 30 different Fluke products. The Fluke Connect family offers the largest system of connected test tools in the world. Please see out Fluke Connect category for the complete collection of Fluke Connect Products. Take me to Fluke Connect (Click Here).
The 1664 FC also allows test results to be saved to Fluke Cloud™ storage. The advanced technology of cloud storage eliminates the need to manually hand write results decreasing room for error. Fluke Cloud™ storage quickly and safely stores data and even has the capability to create test certificates with Fluke DMS.
Set up and sustain preventive maintenance procedures easily using the Fluke Connect® system of wireless test tools and asset management software.
• Improve your ability to prevent or predict machine failures
• Make confident decisions with data you can trust and track
• Access your infrared images from anywhere, anytime with secure cloud storage
• Connect and collaborate with your team – even when you are in different places
• Provide more complete information to your maintenance teams
• Generate work orders that include measurements and infrared images
• Edit and analyze images; create and send reports from your smartphone directly from the field
1 mA @ 50 kΩ 1 mA @ 100 kΩ 1 mA @ 250 kΩ 1 mA @ 500 kΩ 1 mA @ 1 MΩ
Loop and line impedance (ZI)
Range
10 Ω / 0.001 Ω / High current mΩ mode
Resolution
0.01 Ω / 0.1 Ω / 1 Ω
Prospective earth fault current, PSC test
Range
1000 A / 10 kA (50 kA)
Resolution
1 A / 0.1 kA
Computation
Prospective earth fault current (PEFC) or Prospective short circuit current (PSC) determined by dividing measured mains voltage by measured loop (L-PE) resistance or line (L-N) resistance, respectively.
RCD testing, RCD types tested
RCD Type
AC¹ G²,S³
Model 1664
A, AC, B5, S
Notes
¹Responds to AC ²General, no delay ³Time delay 4Responds to pulsed signal 5Responds to smooth DC signal
Tripping speed test (ΔT)
Current settings¹
10-30-100-300-500-1000 mA – VAR 10-30-100 mA
Multiplier
x ½, x 1 x 5
Measurement range
RCD Type G
310 ms 50 ms
RCD Type S
510 ms 160 ms
Notes
¹1000 mA type AC only 700 mA maximum type A in VAR mode VAR mode not available for type B.
RCD/FI-Tripping Current Measurement/Ramp Test (IΔN)
Current range
30% to 110% of RCD rated current¹
Step size
10% of IΔN²
Dwell time
Type G
300 ms/step
Type S
500 ms/step
Measurement accuracy
±5%
Specified trip current ranges (EN 61008-1)
50% to 100% for Type AC 35% to 140% for Type A (>10 mA) 35% to 200% for Type A (≤10 mA) 50% to 200% for Type B ²5% for Type B
Notes
¹30% to 150% for Type A IΔN > 10 mA 30% to 210% for Type A IΔN = 10 mA 20% to 210% for Type B
Earth Resistance Test (RE)
Range
200 Ω / 2000 Ω
Resolution
0.1 Ω / 1Ω
Frequency
128 Hz
Output Voltage
25 V
Phase Sequence Indication
Icon
Phase Sequence indicator is active.
General Specifications
Size (L x W x H)
10 x 25 x 12.5 cm
Weight (incl. batteries)
1.3 Kg
Battery size, quantity
Type AA, 6 ea.
Sealing
IP-40
Safety
Complies with EN61010-1 Ed 2.0 (2001-02), UL61010, ANSI/ISA –s82.02.01 2000 and CAN/CSA c22.2 No. 1010 2nd edition
Overvoltage
CAT III / 500V; CAT IV 300V
Performance
EN61557-1 to EN61557-7 Second Edition and EN61557-10 Second Edition
The store will not work correctly when cookies are disabled.
We use cookies to make your experience better.To comply with the new e-Privacy directive, we need to ask for your consent to set the cookies.Learn more.