Flowline EchoPod DL24 provides continuous level measurement up to 9.8 (3m) with a 4-20 mA signal output, and is configured via our free Webcal software. The level sensor has 4 programmable relays with selectable hysteresis and fail-safe logic. The embedded level controller can lower cost by replacing external control hardware.This non-contact liquid level sensor is ideally suited for corrosive, sticky or dirty liquids, and is widely selected for day tank, skid, IBC, sump and process tank level applications.
Specifications
Range:
9.8' (3m)
Accuracy:
± 0.2% of range
Resolution:
0.039" (1mm)
Dead band:
4" (10cm)
Beam width:
2" (5cm)
Configuration:
WebCal® PC Windows® USB 2.0
Memory:
Non-volatile
Supply voltage:
24 VDC (loop)
Consumption:
0.5W
Loop resist.:
400Ω max
Signal output:
4-20 mA, two-wire
Signal invert:
4-20 mA or 20-4 mA
Signal fail-safe:
4 mA, 20 mA, 21 mA, 22 mA or hold last
Contact type:
(4) SPST relays
Contact rating:
60 VA, 1A maximum
Contact fail-safe:
Power loss: Hold last Echo loss: Open, close or hold last
Hysteresis:
Selectable
Process temp.:
F: -4° to 140° C: -20° to 60°
Temp. comp.:
Automatic
Ambient temp.:
F: -31° to 140° C: -35° to 60°
Pressure:
MWP = 30 PSI (2 bar)
Enclosure rating:
Type 6P, encapsulated, corrosion resistant & submersible
Encl. material:
Polycarbonate
Trans. material:
PVDF
Cable jacket mat.:
Polyurethane
Cable type:
9-conductor, shielded
Cable length:
48" (1.2m)
Process mount:
1" NPT (1" G)
Mount gasket:
Viton®
Classification:
General purpose
Compliance:
CE, RoHS
Approvals:
cFMus
The store will not work correctly when cookies are disabled.
We use cookies to make your experience better.To comply with the new e-Privacy directive, we need to ask for your consent to set the cookies.Learn more.