Expanding their ProVu series, Precision Digital is offering their ProVu PD7000-6R 265 VAC Temperature Digital Panel Meter. The 1/8 DIN ProVu PD7000-6R digital panel meter accepts a direct temperature input from an expansive assortment of temperature measurement devices: type J, K, T, E, R, S, B, N, and C thermocouples and 100 or 1000 Ω platinum, 10 Ω copper, 120 Ω nickel RTDs. The measured temperature is presented in degrees Fahrenheit or degrees Celsius on the dual-line, 6-digit digital display. More still, the temperature indicator features an automatic cold junction compensation for thermocouples, in addition to the capacity to average up to 10 RTD sensors.
The PD7000-6R is equipped with a UL / C-UL listing, CE marking, NEMA 4X front and AC or DC power options. Users can suit the meter with up to 4 internal relays, 4-20 mA output and Modbus RTU serial communications.
General
Display: Upper display: 0.60" (15 mm) high. Lower display: 0.46" (12 mm) high. Both are 6 digits (-99999 to 999999), red LEDs.
Resolution: 1° (up to four digits) or 0.1° (up to five digits)
Display Intensity: Eight intensity levels
Display Update Rate: 5/second (200 ms)
Front Panel: NEMA 4X, IP65
Programming Methods:Four front panel buttons, digital inputs, PC and MeterView Pro software, Modbus registers.
F4 Digital Input Contacts: 3.3 VDC on contact. Connect normally open contacts across F4 to COM.
F4 Digital Input Logic Levels: Logic High: 3 to 5 VDC Logic Low: 0 to 1.25 VDC
Noise filter: Programmable from 2 to 199 (0 will disable filter)
Filter Bypass: Programmable from 0.1 to 99.9% of span
Recalibration: Recommended at least every 12 months.
Max/Min Display: Max / min temperature readings are stored until reset by the user or until power to the meter is cycled.
Non-Volatile Memory: All programmed settings are stored in nonvolatile memory for a minimum of ten years if power is lost.
Power Options:85-265 VAC 50/60 Hz, 90-265 VDC, 20 W max or 12-24 VDC ± 10%, 15 W max. Powered over USB for configuration only.
Normal Mode Rejection: Greater than 65 dB at 50/60 Hz
Isolation: 4 kV input/output-to-power line. 500 V input-to-output
Environmental:
Operating temperature range: -20 to 65°C
Storage temperature range: -40 to 85°C
Relative humidity: 0 to 90% non-condensing
Connections: Removable screw terminal blocks accept 12 to 22 AWG wire, RJ45 for external relays, digital I/O, and serial communication adapters.
Enclosure: 1/8 DIN, high impact plastic, UL 94V-0, color: black (92 mm x 45 mm). Two panel mounting bracket assemblies are provided.
Dimensions: 4.68" x 2.45" x 5.64" (119 mm x 62 mm x 143 mm) (W x H x D)
Weight: 9.5 oz (269 g)
UL File Number: UL & c-UL Listed. E160849; 508 Industrial Control Equipment.
Warranty: 3 years parts & labor
USB Connection: Compatibility: USB 2.0 Standard, Compliant
Connector Type: Micro-B receptacle
Cable: USB A Male to Micro-B Cable
Driver: Windows 98/SE, ME, 2000, Server 2003/2008, XP 32/64-Bit,
Vista 32/64-Bit, Windows 7 32/64-Bit, Windows 10 32/64-Bit
Power: USB Port
Temperature Input
Inputs: Thermocouple J, K, T, E, R, S, B, N, C; RTD 100 Ω platinum (0.00385 & 0.00392 curves), 10Ω copper, 120Ω nickel, 1000Ω platinum
Input Impedance: Greater than 100 kΩ
Offset Adjust: User programmable offset adjust ±50.0 degrees
Temperature Drift: ±2°C maximum from 0 to 65°C ambient temperature; ±4°C maximum from -20 to 0°C ambient temperature
Sensor Break: Display flashes "Open", relays can be programmed to go "On", "Off", or to "Ignore" (detected as an upscale condition).
Averaging: Up to 10 RTDs connected in parallel can be averaged.
Accuracy & Range:
Type |
Range (°F) |
Range (°C) |
Accuracy |
J |
-200 to 2000 |
-129 to 1093 |
±1°C |
K |
-200 to 2400 |
-129 to 1316 |
±1°C |
T |
-200 to 752 |
-129 to 400 |
±1°C |
E |
-200 to 1800 |
-129 to 982 |
±1°C |
R |
-50 to 3000 |
-46 to 1649 |
±2°C |
S |
-50 to 3000 |
-46 to 1649 |
±2°C |
B |
752 to 3300 |
400 to 1816 |
±2°C |
N |
-100 to 2300 |
-73 to 1260 |
±2°C |
C |
32 to 4100 |
0 to 2260 |
±2°C |
10 Ω |
-328 to 500 |
-200 to 260 |
±0.1°C |
100 Ω |
-328 to 1562 |
-200 to 850 |
±0.4°C |
120 Ω |
-110 to 500 |
-79 to 260 |
±0.1°C |
1000 Ω |
-328 to 900 |
-200 to 482 |
±0.4°C |
Relays
Rating: 2 or 4 SPDT (Form C) internal and/or 4 SPST (Form A) external; rated 3 A @ 30 VDC and 125/250 VAC resistive load; 1/14 HP (≈ 50 watts) @ 125/250 VAC for inductive loads such as contactors, solenoids, etc.
Noise Suppression: Noise suppression is recommended for each relay contact switching inductive loads.
Deadband: 0-100% of span, user programmable
High or Low Alarm: User may program any alarm for high or low trip point. Unused alarm LEDs and relays may be disabled (turned off).
Relay Operation: automatic (non-latching), latching (requires manual acknowledge), sampling (based on time), pump alternation control (2 to 8 relays), Off (disable unused relays and enable interlock feature, manual on/off control mode).
Time Delay: 0 to 999.9 seconds, on & off relay time delays. Programmable and independent for each relay.
Fail-Safe Operation: Programmable and independent for each relay.
Note: Relay coil is energized in non-alarm condition. In case of power failure, relay will go to alarm state.
Auto Initialization: When power is applied to the meter, relays will reflect the state of the input to the meter.
Isolated 4-20 mA Transmitter Output
Output Source: PV (temperature), max, min, set points 1-8, manual control setting, or Modbus input
Scaling Range: 1.000 to 23.000 mA for any display range
Calibration: Factory calibrated 4-20 mA output
Accuracy: ±0.1% of span ± 0.004 mA
Temperature Drift: 0.4 µA/°C max from 0 to 65°C ambient, 0.8 µA/°C max from -40 to 0°C ambient
Note: Analog output drift is separate from input drift.
Isolated Transmitter Power Supply: Terminals I+ & R: 24 VDC ± 10%. Isolated from the input at >500 V. May be used to power the 4-20 mA output or other devices. All models rated @ 40 mA max.
External Loop Power Supply: 35 VDC maximum
Output Loop Resistance:
Power supply |
Minimum |
Maximum |
24 VDC |
10 Ω |
700 Ω |
35 VDC (external) |
100 Ω |
1200 Ω |
Serial Communications
Protocol: Modbus RTU
Meter Address/Slave ID: 1 - 247
Baud Rate: 300 - 19,200 bps
Transmit Time Delay: Programmable between 0 and 199 ms or transmitter always on for RS-422 communication
Data: 8 bit (1 start bit, 1 or 2 stop bits)
Parity: Even, odd, or none with 1 or 2 stop bits
Byte-to-Byte Timeout: 0.01 - 2.54 seconds
Turn Around Delay: Less than 2 ms (fixed)
Digital I/O Expansion Module
Channels: 4 digital inputs & 4 digital outputs per module
System: Up to 2 modules for a total of 8 inputs & 8 outputs
Digital Input Logic: High: 3 to 5 VDC Low: 0 to 1.25 VDC
Digital Output Logic: High: 3.1 to 3.3 VDC Low: 0 to 0.4 VDC
Source Current: 10 mA maximum
Sink Current: 1.5 mA minimum
+5 V Terminal: To be used as pull-up for digital inputs only.
4-Relay Expansion Module
Relays: Four Form A (SPST) rated 3 A @ 30 VDC and 125/250 VAC resistive load; 1/14 HP (approx. 50 watts) @ 125/250 VAC for inductive loads.