We use cookies to make your experience better. To comply with the new e-Privacy directive, we need to ask for your consent to set the cookies. Learn more.
'DT' Current Transducers from NK Technologies combine a Hall effect sensor and signal conditioner into a single package for use in DC current applications up to 400A. The DT Series has jumper selectable current input ranges and industry standard 0-20mA, 4-20mA, 0-3VDC, 0-5VDC or 0-10VDC outputs. Available in solid or split-core packages.
NK Technologies DT Series DC Current Transducers, Jumper Selectable Input Ranges, 0 - 5 VDC, 0 - 10 VDC or 4 - 20 mADC Output. (Unipolar Output, Solid-Core)
Output Signal | • 0–20 mA, 4–20 mA, 0–5 VDC, 0–10 VDC • ±10 VDC (Bidirectional models only) |
Output Limit | • 0–20 mA, 4–20 mA: 23 mA • 0–5 VDC: 5.75 VDC • 0–10 VDC: 11.5 VDC |
Accuracy | • Solid-core: 1% FS • Split-core: 2% FS |
Repeatability | 1.0% FS |
Response Time | • Solid-core: 20 ms (to 90% of step change) • Split-core: 100 ms (to 90% of step change) |
Frequency Range | DC |
Power Supply | • 120 VAC (split-core only) • 24 VAC/DC, 2 VA max. |
Power Consumption | 2 VA |
Loading | • 0–20 mA, 4–20 mA: 500 max. • 0–3 or 5 VDC: 25 KΩ min. • 0–10 VDC: 50 KΩ min. |
Isolation Voltage | 3 KV (monitored line to output) |
Linearity | 0.75% FS |
Current Ranges | • Solid-core: 0–200 max. • Split-core: 0–50 min., 0–400 max. |
Sensing Aperture | • FL Case: 0.75” (19.1 mm) dia. • SP Case: 0.85” (21.6 mm) sq. |
Case | UL94 V0 Flammability Rated |
Environmental | -4 to 122°F (-20 to 50°C) 0–95% RH, non-condensing |
Listings | UL 508 Industrial Control Equipment (USA & Canada), CE |